MNS DTR / MNS Service 109Itemno.Work to be performedMeasured, test & limit values, operating & auxiliary materials• Cable connection • Insulation molten or even corroded• Screwed connection at electrical equipment • For tightening torque, cf. manufacturer´s instructions− InsulationFrequencyInstall. categoryA B C RemarksCheck controller module• Check controller settings− C/k value • In accordance with manufacturer´s operating instructions− cosϕ setpoint− response time • Approximate value 60 s• Check step triggering Power circuit open, i.e.fused switch disconnectorremoved2.3 Direct connection (incoming and outgoing feederswith circuit breaker)Analogous to item 1.3“Gen. inspection ofswitchgear assembly”Additional checks:• Check main switching device • Visual inspection of main connections 1° 6m X Procedure in• Color change at switch main connections accordance with• Condition of main and eroded contacts manufacturer´s• Function test 1a 6m X instructions• Check current transformer arrangement • Fastening of transformers• Secondary cable routing• Condition of transformer housings• Check supports at angle and connection sets • Check screwed connections• Mechanical condition of supporting plate 1a 6m X• Condition of partitioning (if available) • Formation of creepage paths• Check external connections • Check screwed connections• Check cable strain relief• Cable routing, min. bending radii, edge protection, etc.Konserwacja i czci zamienne Maintenanceand Spare Parts 5
- Page 65 and 66: Konserwacja i czci zamienneMaintena
- Page 67 and 68: Konserwacja i czci zamienneMaintena
- Page 69 and 70: Konserwacja i czci zamienneMaintena
- Page 71 and 72: Konserwacja i czci zamienneMaintena
- Page 73 and 74: Konserwacja i czci zamienneMaintena
- Page 75 and 76: Konserwacja i czci zamienneMaintena
- Page 77 and 78: Konserwacja i czci zamienneMaintena
- Page 79 and 80: Konserwacja i czci zamienneMaintena
- Page 81 and 82: Konserwacja i czci zamienneMaintena
- Page 83 and 84: Konserwacja i czci zamienneMaintena
- Page 85 and 86: Konserwacja i czci zamienneMaintena
- Page 87 and 88: Konserwacja i czci zamienneMaintena
- Page 89 and 90: Konserwacja i czci zamienneMaintena
- Page 91 and 92: Konserwacja i czci zamienneMaintena
- Page 93 and 94: Konserwacja i czci zamienneMaintena
- Page 95 and 96: Konserwacja i czci zamienneMaintena
- Page 97 and 98: Konserwacja i czci zamienneMaintena
- Page 99 and 100: Konserwacja i czci zamienneMaintena
- Page 101 and 102: Konserwacja i czci zamienneMaintena
- Page 104: MNS DTR / MNS Service 1031.3 Sposó
- Page 108: MNS DTR / MNS Service 105Czstotliwo
- Page 112: MNS DTR / MNS Service 1071.3 Genera
- Page 118 and 119: AneksAppendix6Lista rysunków / Lis
- Page 120 and 121: AneksAppendix6Rys./Fig.Opis Descrip
- Page 122 and 123: AneksAppendix6posadowienie 31, 33,
- Page 124 and 125: AneksAppendix6Index wordPageIndex w
- Page 126 and 127: AneksAppendix6Index wordPageIndex w
MNS DTR / MNS Service 109
Item
no.
Work to be performed
Measured, test & limit values, operating & auxiliary materials
• Cable connection • Insulation molten or even corroded
• Screwed connection at electrical equipment • For tightening torque, cf. manufacturer´s instructions
− Insulation
Frequency
Install. category
A B C Remarks
Check controller module
• Check controller settings
− C/k value • In accordance with manufacturer´s operating instructions
− cosϕ setpoint
− response time • Approximate value 60 s
• Check step triggering Power circuit open, i.e.
fused switch disconnector
removed
2.3 Direct connection (incoming and outgoing feeders
with circuit breaker)
Analogous to item 1.3
“Gen. inspection of
switchgear assembly”
Additional checks:
• Check main switching device • Visual inspection of main connections 1° 6m X Procedure in
• Color change at switch main connections accordance with
• Condition of main and eroded contacts manufacturer´s
• Function test 1a 6m X instructions
• Check current transformer arrangement • Fastening of transformers
• Secondary cable routing
• Condition of transformer housings
• Check supports at angle and connection sets • Check screwed connections
• Mechanical condition of supporting plate 1a 6m X
• Condition of partitioning (if available) • Formation of creepage paths
• Check external connections • Check screwed connections
• Check cable strain relief
• Cable routing, min. bending radii, edge protection, etc.
Konserwacja i czci zamienne Maintenance
and Spare Parts 5