108 MNS DTR / MNS Service

Item

no.

Work to be performed

Measured, test and limit values, operating and auxiliary

materials

Frequency

Install. category

A B C Remarks

• Check electrical contacts

− Main contact • Visual inspection 2a 1 1a 1 X Refer to

• Check of contact force Chapter 5.5

• Greasing Refer to chapter 5.6

− Control plug

• Fastening of outgoing cable unit • Position; the outgoing cable unit might be pressed out of

its normal position by strong cable forces

• Protective conductor connection • Condition of the roller in the compartment bottom plate

2.2 Plug-in, disconnectable, railable technique Cf. also item no. 1.3:

General inspection

2.2.1 MCC’s and outgoing energy distribution feeders

2.2.2 Compensation modules with and without reactor

Check electrical equipment in every module 1a 6m X Check of contact gaps,

• Visual inspection of main contacts X01 contact condition and

• Condition of short-circuit protection lubrication not necessary

− LV HRC fuse • Fuse continuity

• Fuse tripped Signs of overload by

mains

− Circuit breaker • Contact condition resonance in accordance

• Lubricate contact blades of LV HRC fuses • Klüberlectric KR44-102 with manufacturer´s

• Check capacitor contactor instructions

− Check for contact corrosion • Contact condition

− Switching performance • No humming, bouncing or chattering of reactor

• Visual inspection of filter circuit reactor

Connections and windings • Condition

• Capacitor • Setpoints see chapter 5.15 Use measuring log

− Design without reactor: measure all step • Limit value: I B ≤ 1,3 x I n according chapter 5.17

currents

3-phase or capacitance values

− Design with reactor: measure the terminal

capacitance

• Discharging device

− Reactor • Residual voltage after 1 min ≤ 50 V

− Resistor bank • Color change, missing elements

1

Main contact to be checked either according mentioned the time intervals or latest after 100 cycles.

Konserwacja i czci zamienne Maintenance

and Spare Parts 5