YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Paigaldusjuhend</strong><strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong>, <strong>rakendus</strong> <strong>A260</strong>2.5.2 Elektriühendused, 230 V AC, elektritoide, pumbad, mootoriga reguleerventiilid jne.Rakendus <strong>A260</strong>Klemm Kirjeldus Maks koormus1615Häire4(2) A / 230 V AC*14 Ringluspumba faas13 Ärge kasutage12 P2 Ringluspump ON / OFF, kontuur 2 4(2) A / 230 V AC*11 P1 Ringluspump ON / OFF, kontuur 1 4(2) A / 230 V AC*10 Toitepinge 230 V (vahelduvvool) – null (N)9 Toitepinge 230 V (vahelduvvool) – faas (L)8 M1 Mootoriga reguleerventiili väljundi faas, kontuur 17 M1 Täiturmootor – avamine 0.2 A / 230 V AC6 M1 Täiturmootor – sulgemine 0.2 A / 230 V AC5 M2 Mootoriga reguleerventiili väljundi faas, kontuur 24 M2 Täiturmootor – avamine 0.2 A / 230 V AC3 M2 Täiturmootor – sulgemine 0.2 A / 230 V AC* Releekontaktid: 4 A oomilisel koormusel, 2 A induktiivkoormuselTehases paigaldatud ühendussillad:5–8, 9–14, L–5 ja L–9, N–10Kaabli ristlõige: 0.5 – 1.5 mm²Valed ühendused võivad kahjustada elektroonilisi väljundeid.Kuni 2 × 1.5 mm² kaableid tohib ühendada ühe kruviklemmi alla.<strong>Danfoss</strong> District Energy VI.LG.F1.26 DEN-SMT/DK 15