POSITION TRANSMITTERS

CALIBRATION

There are two procedures for calibration; one for the potentiometric

option (Type AV____1__) and another for the four to 20-milliamp

option (Type AV____2 __).

Calibrating the Potentiometric Position Transmitter

This calibration example using the potentiometric position transmitter

can be used as a guide for other applications. Final calibration

of the potentiometric position transmitter option depends on

the application. Field connections to the potentiometer are shown

on a label located inside the positioner cover. The label is shown

in Figure A-1.

TB1 CONNECTIONS

NOMENCLATURE

AV23?????

AV33?????

AV44?????

AV????1??

AV????2??

1 2 3

+ – +24

+ –

4 5

+ –

+ –

T00807A

Figure A-1. Terminal Block Connections

The nomenclature and terminal connections of Figure A-1 are:

AV23

AV33

AV44

AV____1__

AV____2__

The positive (+) and negative (-) connections at position TB1-4

and TB1-5 refer to the four to 20-milliamp signal to the I/P converter.

Not applicable.

Not applicable.

Depicts the connections for the potentiometric position transmitter

option.

The positive (+) and negative (-) connections at position TB1-1

and TB1-2 refer to the output signal from the four to 20-milliamp

position transmitter.

Direct acting cam rotation of zero to 100 percent produces

increasing resistance between terminal block TB1-1 and TB1-2.

Reverse acting cam rotation of zero to 100 percent produces

decreasing resistance between TB1-1 and TB1-2.