APPENDIX A - POSITION TRANSMITTERS

INTRODUCTION

This appendix provides operation and calibration information for

ABB position transmitter options. Refer to Table 1-4 (potentiometric

position transmitter) or Table 1-5 (four to 20-milliamp position

transmitter) for position transmitter performance specifications. A

position transmitter provides additional control features to Type AV

positioners and can be ordered through nomenclature.

Position transmitters sense the position of the positioner cam

shaft. Two variations exist:

• Potentiometric option (AV____1__).

• 4 to 20-milliamp option (AV____2__).

DESCRIPTION AND OPERATION

Position transmitters are available as options (order through

nomenclature).

The Type AV____1__ potentiometric position transmitter option

uses a high durability plastic film potentiometer. Gears connect

the potentiometer to the positioner cam shaft. The position of the

potentiometer shaft indicates the position of the actuator.

The relationship between the potentiometer and the cam shaft

results in one degree of rotation of the cam shaft corresponding to

approximately 9.9 ohms of resistive change at the potentiometer

wiper. Three leads from the potentiometer are for customer use

and are available at terminals TB1-1, TB1-2 and TB1-3.

The Type AV____2 __ four to 20-milliamp position transmitter

option also uses a high durability plastic film potentiometer and

electronic circuitry. Gears connect the potentiometer shaft to the

positioner cam shaft. The resistive change of the potentiometer

outputs to a bridge circuit, producing a proportional voltage. EMI/

RFI protected circuitry converts the bridge voltage to a four to

20-milliamp current signal. Terminals TB1-1 (+) and TB1-2 (-) of

the Type AV positioner provide customer access to the four to

20-milliamp control signal. Jumper position determines direct or

reverse acting operation. Test jacks are available for in-line current

monitoring.

INTRODUCTION

A - 1