REPAIR AND REPLACEMENT

b. If manual override is not available, disconnect (and

secure) the linkage. Plug ports 01 and 02 if necessary.

2. Apply the supply pressure.

3. Apply the maximum input signal to the positioner:

• AV11: 103.4 kPa (15.0 psig).

• AV12:186.2 kPa (27.0 psig).

• AV23: 20 mA.

3

4. Use the long ⁄ 32 -inch Allen wrench, adjust the top adjustment

screw (Fig. 8-4) appropriately until the measurement matches the

value shown in Figure 8-3. Figure 8-3 also shows the way the measurement

is taken.

5. Apply the minimum input span to the positioner:

• AV11: 20.7 kPa (3.0 psig).

• AV12: 20.7 kPa (3.0 psig).

• AV23: 4 mA.

3

6. Use the long ⁄ 32 -inch Allen wrench to adjust the lower stroke

adjustment screw (Fig. 8-4). Adjust the screw until the measurement

matches the value shown in Figure 8-3.

0.030

STEM IS

FLUSH

WITH BODY

0.030

STEM POSITION AT

BALANCE CONDITION

STEM POSITION TOP

ADJUSTMENT SCREW

STEM POSITION LOWER

ADJUSTMENT SCREW

T00777A

Figure 8-3. Pilot Valve Measurement for Maximum Speed

PILOT VALVE STROKE ADJUSTMENT

8 - 8

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!