REPAIR AND REPLACEMENT

O-RINGS

T00781A

Figure 8-2. Manifold O-Rings

4. Remove the four hinge screws (Item 42) while holding the beam

assembly steady (Item 6). Remove the two screws that connect the

beam to the hinge first.

5. Remove the gain hinge spring.

6. Insert the new gain hinge spring.

NOTE: When installing the gain hinge spring, be sure it properly

seats (flush) between the steps. If the gain hinge spring hangs

up, remove and rotate the hinge 90°. Check for proper seating.

7. Insert and torque the screws to 2.6, ±0.2 Nm (23, ±2 in.-lbs) while

holding the beam assembly steady (Item 6). Insert the two screws

that secure the hinge to the housing first.

8. Transfer the positioner back to automatic operation (Section 5).

9. Perform the procedure outlined in PILOT VALVE STROKE

ADJUSTMENT.