28.03.2022 Views

ABB AV2123000 Positioner User Manual

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

TROUBLESHOOTING

Excessive air consumption

(exhaust

loud)

Slow response

Full range cannot be

obtained with

mechanical zero and

span adjustment

Leakage at the joint

of the manifold

assembly (if

equipped).

Pilot valve body seal

is leaking.

Tubing disconnected.

Signal diaphragm

leaking.

I/P converter out of

calibration or not

functioning.

Signal diaphragm

leaking.

I/P converter out of

calibration or not

functioning.

I/P converter is

defective.

Table 6-1. Positioner Errors

Error Probably Cause Corrective Action

Remove manifold and check O-rings. Refer to Manifold in

Section 8.

Remove pilot valve body and check O-rings. Refer to Pilot

Valve Assembly in Section 8.

Check connection at pressure regulator and I/P converter.

Replace signal diaphragm. Refer to Diaphragm Assembly in

Section 8.

Calibrate I/P converter. Refer to TROUBLESHOOTING CALI-

BRATION ADJUSTMENTS in Section 4. If unable to calibrate,

replace I/P converter. Refer to I/P Converter in

Section 8.

Replace diaphragm. Refer to Diaphragm Assembly in

Section 8.

Calibrate I/P converter. Refer to TROUBLESHOOTING CALI-

BRATION ADJUSTMENTS in Section 4. If unable to calibrate,

replace I/P converter. Refer to I/P Converter in

Section 8.

Replace I/P converter. Refer to I/P Converter in Section 8.