28.03.2022 Views

ABB AV2123000 Positioner User Manual

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

INSTALLATION

Refer to Appendix A for detailed information about position transmitters.

NOTE: Route the wiring inside the positioner so it does not

become entangled with moving parts. A cable clamp (Fig. 3-1 or

4-1) is provided inside the positioner so entanglement can be

avoided.

3. Grounding positioners should be done in accordance with

local electrical codes (in U.S, National Electrical Code, ANSI/

NFPA 70. In Canada, Canadian Electrical Code, CSA c22.1). A

grounding screw is provided inside the enclosure for grounding,

denoted by .

NOTES:

1. The grounding screw located inside the enclosure is a safety

ground and should not be used to ground the shielded pair.

2. The positioner must be grounded to avoid ground loop

conditions.

RADIO FREQUENCY INTERFERENCE

Most electronic equipment is influenced by radio frequency interference

(RFI). Caution should be exercised with regard to the use

of portable communications equipment in the area.

ABB recommends posting appropriate signs in the plant. Refer to

the Site Planning and Preparation instruction for additional information

on RFI.

WIRING REQUIREMENTS

Under ideal conditions, the use of conduit and shielded wire may

not be required. However, to avoid noise problems, it is recommended

that wiring be enclosed in conduit. Just prior to entering

the housing, rigid conduit should be terminated and a short length

of flexible conduit should be installed to reduce any stress.

RADIO FREQUENCY INTERFERENCE

3 - 15

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!