INSTALLATION

4. Lock all linkage components in place.

CAM

CAM ROLLER

CAM FOLLOWER ARM

T00771A

Figure 3-8. Cam Roller Alignment

TUBING CONNECTIONS

Type AV positioners are available with (Type AV___1___ and

AV___2___) or without (AV___0___) manifolds. The following outlines

supply air information and describes the piping connections.

Air Supply Pressure

CAUTION

Do not exceed the maximum supply pressure of 1034 kilopascals

(150 pounds per square inch gage). Exceeding this

pressure could cause equipment damage.

The air supply pressure range is 172 to1034 kilopascals (25 to

150 pounds per square inch gage).

NOTE: The minimum supply pressure should be 34.4 kilopascals

(5 pounds per square inch gage) above the operating pressure

required by the actuator.

Air Supply Filtering

An external filter is recommended for Type AV positioners for primary

filtration of the supply air. ABB provides supply air filters as

accessories. Refer to Table 1-12 for part numbers.

NOTE: Primary air supply filters are recommended for positioners

with a manifold (AV___1/2___), without a manifold

(AV___0___) or with a gage block (AV___3___).

TUBING CONNECTIONS

3 - 8