28.03.2022 Views

ABB AV2123000 Positioner User Manual

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

INSTALLATION

square function (Table 3-1). Cam B is in place when the positioner

is shipped from the factory. The cams may be shaped to conform

to special applications. Refer to Appendix C for information about

cam shaping.

NOTE: If the application is reverse acting, the reverse acting

cam (red radial lines) must be installed and the connections to

ports 01 and 02 must be reversed.

RADIAL

LINES

CONCENTRIC

ARCS

45° CAM

AV??1????

90° CAM

AV??2????

T00805A

Figure 3-7. Cam

Positioning

Cam

Any Stroke

Table 3-1. Cam Characteristics

Piston or Valve Position (P)

vs

Control Signal (I)

Figure

Number

A Square root ( I = P)

C-1

B Linear ( I = P)

C-2

C Square ( I = P 2 )

C-3

The cam, camshaft and drive arm rotate as an assembly. Cam

motion is 90 degrees (Type AV__2____) or 45 degrees (Type

AV__1____) depending on the positioner type specified by

nomenclature (Figure 3-7).

Each cam shape (A, B or C) has its own eight-point center hole for

mounting on the camshaft (Fig. 3-7). Place the cam in one of the

eight 45-degree positions so that the midpoint of the cam corresponds

to the mid stroke of the actuator. The drive arm should be

perpendicular to the motion of the actuator with the actuator at mid

stroke.

3. Adjust the connecting linkage so that the zero radial line on

the cam intersects the center of the cam roller when the actuator

is at its zero position (Fig. 3-8).