Distance between the pressure taps is as follows:<br />

Figure 4. Length 3 large area duct setup with<br />

Tap 2 in the foreground<br />

Results<br />

Table 1 Pressure tap distances<br />

Pressure Taps Distance<br />

Tap 1 to Tap 2 255 cm<br />

Tap 2 to Tap 3 211,5 cm<br />

Tap 3 to Tap 4 110 cm<br />

The results of the laboratory experiment are below.<br />

Once the ducts were put together, one size i.e., the<br />

large area duct, was connected to the fan system.<br />

The fan was set to deliver seven liters per second<br />

and later twelve liters per second of air through the<br />

ducts. Pressure drops were first measured for ten<br />

minutes from Tap 1 to Tap 2, then Tap 1 to Tap 3,<br />

then Tap 1 to Tap 4 or Length 1, Length 2 and<br />

Length 3 respectively. This procedure was repeated<br />

on the other duct system of different area.<br />

To measure the sound, the sound meter was pointed<br />

at the outlet of the duct, approximately one meter<br />

away. According to building code standards, low<br />

frequency sounds need to be minimized. The sound<br />

experiments measured decibels from 125 Hz, 250<br />

Hz and 500 Hz. In the laboratory, background noise<br />

was reduced to a minimum, by performing tests<br />

during non-working hours.<br />

Bilaga 5 sid 3 (6)<br />

3