Report For Signalisten by David Villarroel November 15, 2007<br />
Laboratory Test Results of the Ventilation ducts<br />
Introduction<br />
Signalisten, a social housing corporation in northern Stockholm, approached Tetex<br />
Konsulter AB and KTH for a ventilation retrofit project concerning air quality within<br />
their apartments. Signalisten’s apartments will need to meet future government<br />
regulations in indoor radon emission levels together with low energy use. To accomplish<br />
this task, a new ventilation duct system was proposed to increase air flow into the<br />
apartments. The apartments would be fitted with a new duct system for supplied air to<br />
each of the rooms.<br />
Purpose<br />
As suggested by the introduction, the new duct system is to be tested before any<br />
installation occurs in the apartments. Signalisten would like the duct design to meet<br />
appropriate pressure drops and air flow requirements, therefore an experiment conducted<br />
over a configuration of ducts was proposed. The experiment is located in KTH’s Energi<br />
Tillämpad Termodynamik (ETT) laboratories. Further tests will be conducted in a test<br />
apartment, where a prototype of the duct system will be installed.<br />
In cooperation with Tetex Konsulter AB, pressure drops and air flows were measured to<br />
evaluate the performance of the different duct configurations. These results will confirm<br />
the sizing of the air supply fans to meet required indoor air quality.<br />
As with every air duct installation, the sound the air makes in the ducts must be observed.<br />
High sound levels in the ducts would cause tenants unnecessary nuisance and therefore<br />
must be eliminated. The experiments conducted will also cover sound tests in the<br />
laboratory and at the test apartment.<br />
Equipment:<br />
The following is the equipment and instruments used<br />
in the experiments.<br />
Fan: Östberg<br />
Type: CK100 A Man Tp<br />
Article No.: 7000001<br />
Characteristics: 230 V; 50 Hz; 0,041 kW;<br />
0.18 A; 3 μF/450 V; 1730 rpm; IP44;<br />
ISO cl F 80˚C<br />
Orifice Flow Regulator: Lindab DIRU100<br />
Serial Number: 2777511<br />
Bilaga 5 sid 1 (6)<br />
Figure 1. Fan and orifice flow regulator<br />
1