24.07.2018 Views

Practical_Antenna_Handbook_0071639586

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

C h a p t e r 2 6 : T h e S m i t h C h a r t 579<br />

Now let’s summarize everything we’ve gleaned using the Smith chart. Recall that<br />

1.5 W of 4.5-ÂGHz microwave RF signal was applied to the input of a 50-ÂW transmission<br />

line that was 28 cm long. The load connected to the far end of the transmission line had<br />

an impedance of 36 + j40. From the Smith chart:<br />

Admittance (load) 0.62 – j0.69<br />

VSWR 2.6:1<br />

VSWR (dB):<br />

8.3 dB<br />

Reflection coefficient (V) 0.44<br />

Reflection coefficient (P) 0.2<br />

Reflection coefficient angle 84 degrees<br />

Return loss<br />

–7 dB<br />

Reflection loss<br />

–1.05 dB<br />

Transmission loss coefficient 1.5<br />

Note that in all cases the numerical calculation agrees with the graphical solution of the<br />

problem within the limits of the graphical method.<br />

Stub Matching<br />

A properly designed matching system will provide a conjugate match to a complex<br />

impedance. Some sort of matching system or network is likely to be needed any time<br />

the load impedance Z L differs significantly from the characteristic impedance Z 0 of the<br />

transmission line. In a transmission line system, a shorted stub is often connected in parallel<br />

with the line, at a specific distance back toward the generator from the mismatched<br />

load, in order to effect a match.<br />

As shown schematically in Fig. 26.8, a stub is simply a short section of transmission<br />

line whose two conductors are shorted together at one of its ends and individually attached<br />

to the two conductors of the system transmission line at its other end. A lossless<br />

shorted line exhibits a pure reactance that can vary from –∞ to +∞, depending upon its<br />

length (and repeating every l/2), so a line of critical length L 2 attached across a load<br />

impedance can cancel any possible reactive component. However, because the stub<br />

must also transform the resistive part of the load impedance up or down to match the<br />

system impedance (Z 0 ), another adjustable stub parameter is required. This turns out to<br />

be the stub attachment point L 1 —i.e., the distance from the load back toward the transmitter<br />

(or generator).<br />

Because the stub is connected in parallel with the line, it is generally easier to work<br />

with admittance parameters, rather than impedances. When we do that, at a certain<br />

stage of the process values on the Smith chart represent admittances, consisting of conductances<br />

and susceptances, rather than impedances. The pure resistance line becomes<br />

the pure conductance line, and circles of constant resistance become circles of constant<br />

conductance.<br />

Example 26.3 A parallel-Âwire transmission line is terminated by an antenna with an<br />

impedance Z L = 100 + j60, as shown in Fig. 26.8. Find the closest location (to the load)<br />

and the length of a shorted stub that will reduce the VSWR on the transmission line to<br />

the left of the stub to 1.0:1.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!