3004346_2012_12_07.fm Electrical connections<br />

Current leakage During operation the EC control emits a leakage current of less than 3.5 mA. The leakage current<br />

must be earthed, as otherwise there would be a risk of the motor becoming a live conductor.<br />

Earth leak circuit<br />

breakers<br />

Only type A circuit breakers must be used for single-phase EC controls in compliance with IEC755<br />

Amendment 2, for leakage current with DC content (pulsating DC).<br />

These circuit breakers are marked with:<br />

Requirements Disconnection time of max 0.3 seconds<br />

Dimensioning of<br />

the neutral<br />

conductor.<br />

Multiple one-phase <strong>DTH</strong> with EC installations in a shared network with a common neutral require<br />

special dimensioning of the neutral, as the current is not a pure sine wave.<br />

Example If three EC controls are installed, sharing 3 phases, the neutral current is the sum of the three<br />

motors’ current.<br />

Existing<br />

installations<br />

Lightning conductor<br />

If you are fitting motors to an existing installation, check that the neutral conductor can cope with<br />

the resultant load.<br />

Any lightning conductor connected to the fan must be in accordance with applicable regulations<br />

and legislation.<br />

EXHAUSTO provi<strong>de</strong>s a two-year manufacturer's warranty on the fan.<br />