Teknisk Datablad Hilti Firestop Sleeve CFS-SL Hilti Brannstopp hylse CFS-SL Europeisk Teknisk Godkjenning Utgave 2012 Hilti Firestop Sleeve CFS-SL | Issue 04/2011 page 1

<strong>Teknisk</strong><br />

<strong>Datablad</strong><br />

<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong><br />

<strong>Hilti</strong> <strong>Brannstopp</strong><br />

<strong>hylse</strong> <strong>CFS</strong>-<strong>SL</strong><br />

<strong>Europeisk</strong><br />

<strong>Teknisk</strong> Godkjenning<br />

Utgave 2012<br />

<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong> | Issue 04/2011 page 1


<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong><br />

<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong><br />

<strong>Brannstopp</strong> <strong>hylse</strong><br />

<strong>CFS</strong>-<strong>SL</strong><br />

Monteringsanvisning<br />

Enkel og rask branntetting av kabler<br />

Ideel ved etterinstallering av kabler<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Bruksområder<br />

■ Tetting av gjennomføringer med enkeltstående kabler og kabelbunter<br />

■ Velegnet for små og mellomstore sirkulære utsparinger i vegg og<br />

dekke<br />

■ Kan brukes i betong, mur og gips<br />

Fordeler<br />

■ Lett å montere - rask og enkel<br />

■ Funksjonell umiddelbart etter installasjon<br />

■ Enkelt å etterinstallere kabler: enkel åpne- og lukkefunksjon<br />

■ Røyktett uten å ha fugemasse mellom kablene<br />

■ Robust<br />

■ ETA dokumentert brannmotstand opp til 120 minutter<br />

<strong>Teknisk</strong> data<br />

<strong>CFS</strong>-<strong>SL</strong><br />

Ekspanderende<br />

Ja<br />

Maks bredde, fugen rundt<br />

7 mm<br />

Minimum tykkelse vegg<br />

100 mm<br />

Minimum tykkelse dekke<br />

150mm<br />

Andre komponent<br />

<strong>Brannstopp</strong> akryl fugemas. <strong>CFS</strong>-S ACR<br />

Brannklasse E (i henhold til EN 13501-1:2007)<br />

<strong>Europeisk</strong> teknisk godkjenning (ETA) kan du få ved henvende deg til<br />

<strong>Motek</strong><br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Bestillingsbetegnelse<br />

Anbefalt utsparing<br />

Art. nr.<br />

<strong>Brannstopp</strong> <strong>hylse</strong> <strong>CFS</strong>-<strong>SL</strong> S Ø 63-73 mm 72019717<br />

<strong>Brannstopp</strong> <strong>hylse</strong> <strong>CFS</strong>-<strong>SL</strong> M Ø 113-122 mm 72019718<br />

page 2 <strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong> | Issue 04/2011 <strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong> | Issue 04/2011 page 3


<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong><br />

<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong><br />

Kabelgjennomføringer<br />

Gips- og betong/murvegg<br />

Kabelgjennomføringer<br />

Betong- og murdekke<br />

<strong>Hilti</strong> <strong>Brannstopp</strong> <strong>hylse</strong> <strong>CFS</strong>-<strong>SL</strong> kan benyttes til å opprettholde ønsket brannklasse i:<br />

Gipsvegger (E), minimum 100 mm tykkelse (t E<br />

) og maks tykkelse 200 mm med tre- eller stålstendere, kledd med gips på begge<br />

sider og plater med en total tykkelse på minimum 25 mm. Mellom trestenderne må det være en minimum avstand på 100 mm<br />

mellom tettingen og stender, og hulrommet må fylles med minimum 100 mm isolasjon klasse A1 eller A2 i henhold til EN<br />

13501-1.<br />

Betong- og murvegger (E), minimum densitet/tetthet 650 kg/m 3 , minimum tykkelse 100 mm og maks 200 mm (t E<br />

).<br />

<strong>Hilti</strong> brannstopp <strong>hylse</strong> <strong>CFS</strong>-<strong>SL</strong> kan benyttes til gjennomføringstettinger (A) i betong- og murgulv (E) med minimum densitet/<br />

tetthet 550 kg/m 3 og minimum tykkelse 150 mm og maks tykkelse 200 mm (t E<br />

).<br />

Gjennomføringstetting (A) /<br />

Kabler(C)<br />

Dekke type (E) and tykkelse (t E<br />

)<br />

Klassifisering<br />

E = integritet<br />

I = isolasjon<br />

Andre kriterier<br />

Beskrivelse<br />

Gjennomføringstetting (A) /<br />

Kabler(C)<br />

Alle typer mantlet kabler 1) ≤<br />

diameter 21 mm<br />

Alle typer mantlet kabler 1) ≤<br />

diameter 50 mm<br />

Alle typer mantlet kabler 1) ≤<br />

diameter 80 mm<br />

Bundet kabelbunter maks<br />

diameter 36 mm, maks diameter<br />

enkeltstående kabler 21 mm<br />

Bundet kabelbunter maks<br />

diameter 86 mm, maks diameter<br />

enkeltstående kabler 21 mm<br />

Tom utsparing 2) (ingen kabler<br />

trukket gjennom)<br />

Vegg type (E) and tykkelse (t E<br />

)<br />

Gips- og betongvegg<br />

≥ 100 mm – ≤ 200 mm<br />

Klassifisering<br />

E = integritet<br />

I = isolasjon<br />

EI 60 (<strong>CFS</strong>-<strong>SL</strong> S)<br />

EI 120 (<strong>CFS</strong>-<strong>SL</strong> M)<br />

EI 90 (<strong>CFS</strong>-<strong>SL</strong> M)<br />

EI 60 (<strong>CFS</strong>-<strong>SL</strong> M)<br />

EI 60 (<strong>CFS</strong>-<strong>SL</strong> S)<br />

EI 90 (<strong>CFS</strong>-<strong>SL</strong> M)<br />

EI 60 (<strong>CFS</strong>-<strong>SL</strong> S)<br />

EI 120 (<strong>CFS</strong>-<strong>SL</strong> M)<br />

Andre kriterier<br />

Beskrivelse<br />

Fugen rundt <strong>hylse</strong>n må forsegels med <strong>Hilti</strong><br />

<strong>Brannstopp</strong> akryl fugemasse <strong>CFS</strong>-S ACR<br />

på begge sider av veggen (A 2<br />

).<br />

Alle typer mantlet kabler 1) ≤<br />

diameter 21 mm<br />

Alle typer mantlet kabler 1) ≤<br />

diameter 50 mm<br />

Alle typer mantlet kabler 1) ≤<br />

diameter 80 mm<br />

Bundet kabelbunter maks<br />

diameter 36 mm, maks diameter<br />

enkeltstående kabler 21 mm<br />

Bundet kabelbunter maks<br />

diameter 86 mm, maks diameter<br />

enkeltstående kabler 21 mm<br />

Tom utsparing 2) (ingen kabler<br />

trukket gjennom)<br />

Betong- og murdekke<br />

≥150 mm – ≤ 200 mm<br />

EI 120 (<strong>CFS</strong>-<strong>SL</strong> S og<br />

<strong>CFS</strong>-<strong>SL</strong> M)<br />

EI 120 (<strong>CFS</strong>-<strong>SL</strong> M)<br />

EI 60 (<strong>CFS</strong>-<strong>SL</strong> M)<br />

EI 120 (<strong>CFS</strong>-<strong>SL</strong> S)<br />

EI 120 (<strong>CFS</strong>-<strong>SL</strong> M)<br />

EI 120 (<strong>CFS</strong>-<strong>SL</strong> S og<br />

<strong>CFS</strong>-<strong>SL</strong> M)<br />

1)<br />

Alle typer mantlet kabler som i dag er vanlig å bruke i Europa (f.eks. kraft, kontrol, signal, telekommunikasjon, data, optiske fiber kabler).<br />

2) Om kabler skal trekkes gjennom på et senerer tidspunkt, for påkrevd klassifisering se detaljer i ETA..<br />

Fugen rundt <strong>hylse</strong>n må forsegels med <strong>Hilti</strong><br />

<strong>Brannstopp</strong> akryl fugemasse <strong>CFS</strong>-S ACR<br />

på begge sider av veggen (A 2<br />

).<br />

1)<br />

Alle typer mantlet kabler som i dag er vanlig å bruke i Europa (f.eks. kraft, kontrol, signal, telekommunikasjon, data, optiske fiber kabler).<br />

2) Om kabler skal trekkes gjennom på et senerer tidspunkt, for påkrevd klassifisering se detaljer i ETA.<br />

page 4 <strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong> | Issue 04/2011 <strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong> | Issue 04/2011 page 5


<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong><br />

<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong><br />

Egenskapene til <strong>CFS</strong>-<strong>SL</strong><br />

Tester og dokumentasjon<br />

<strong>Hilti</strong> brannstopp produkter er omfattende testet og indivduelt tilpasser de tekniske krav til et byggs tekniske<br />

krav til elektiske installasjoner. Bedømmelsen av brukervennlighet er gjort i henhold til EOTA ETAG N o 026 del 2.<br />

Egenskaper Tester av egenskapene Norm, standard, test<br />

Helse og miljø<br />

Farlige substanser<br />

I henhold til produsentens deklarasjon, har<br />

produktets innhold blitt sammenlignet med<br />

listen over farlige substanser hos den<br />

<strong>Europeisk</strong>e kommisjon for å verifisere at det<br />

ikke innholder slike substanser over lovlige<br />

grenser. <strong>CFS</strong>-<strong>SL</strong> overholder registering, evaluering,<br />

autorisering og begrensninger av<br />

kjemikaler (REACH).<br />

HMS datablad<br />

Bestandighet<br />

<strong>Hilti</strong> brannstopp <strong>hylse</strong> <strong>CFS</strong>-<strong>SL</strong> har blitt vurdert<br />

ETAG 026-2<br />

til Z 2<br />

kategorien, og resultatet av testene<br />

viser at den er egnet for gjennomføringerstettinger<br />

til bruk i innemiljø, men ikke i fuktighetsklasse<br />

Z 1<br />

, det utelukker temperaturer under<br />

0°C<br />

Brannklassifisering Klasse E EN 13501-1<br />

Service<br />

Med mer enn 20 års erfaring fra hele verden innen passiv brannsikring, er <strong>Hilti</strong> en av de<br />

ledende leverandørene av brannstopp produkter. Vi vil gjerne hjelpe deg aktivt i ditt prosjekt<br />

med branntetting ved å tilby:<br />

• Veileding i produktvalg<br />

• Omfattende teknisk dokumentasjon<br />

• Våre selgere i <strong>Motek</strong> kommer dit du jobber og gir demonstrasjon og opplæring<br />

• Rask og effektiv levering av varer<br />

• Sikkerhet i forhold til offentlige krav til kvaliteten av produktene<br />

• Internationalt nettverk med <strong>Hilti</strong> brannstopp spesialister<br />

page 6 <strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong> | Issue 04/2011 <strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong> | Issue 04/2011 page 7


<strong>Hilti</strong> = registered trademark of <strong>Hilti</strong> Corp., Schaan I W 4088 0411 0-en I 2 Printed in Liechtenstein I © 2010 I Right of technical and programme changes reserved S. E. & O.<br />