4.2.2 External set back<br />

To utilise the set-back funtion and roll back the current set<br />

point by 3.5°C: Connect a closing contact between the FP<br />

terminal and phase terminal e.g. a closing timer switch.<br />

When the contact is closed and active signal present, the<br />

symbol "P" is displayed in the upper left corner indicating<br />

activation.<br />

To enable manual control mode: Push the confirmation<br />

button in 3 sec. Normal set temperature control is active.<br />

Push again the confirmation button < > in 3 sec. for<br />

leaving the Manual mode to Booster mode. Push the<br />

confirmation button<br />

< > again 3 sec to go the AUTO mode.<br />

4.2.3 Lock<br />

Lock and unlock the thermostat<br />

Possible to lock all the set possibilities for the thermostat.<br />

(eg public buildings)<br />

Lock: Push simultaneously < > and < > and < ><br />

Unlock: Push simultaneously < > and < > and < ><br />

5. Trouble shooting<br />

5.1 Error codes<br />

Number Error type<br />

ER 1 Wrong floor sensor (100 kΩ)<br />

ER 2 Short circuit on floor sensor<br />

ER 3 Open circuit on floor sensor<br />

ER 4 Short circuit on room sensor<br />

ER 5 Open circuit on room sensor<br />

ER 6 Other error<br />

5.2 Monitoring of the temperature sensor<br />

In the event of damage or malfunction of one of the<br />

temperature sensors, the heating output cuts off (fail safe)<br />

and an errorcode is displayed.<br />