<strong>SA</strong> <strong>07.1</strong> <strong>–</strong> <strong>SA</strong> <strong>16.1</strong>/<strong>SA</strong>R <strong>07.1</strong> <strong>–</strong> <strong>SA</strong>R <strong>16.1</strong> Styreenhet: elektro-mekanisk<br />

AC 01.1 Intrusiv Elektrisk tilkobling<br />

5.2.1 Åpne tilkoblingsrommet<br />

5.2.2 Tilkoble kabler<br />

Bilde 13: Forbindelse AUMA pluggforbindelse , versjon S<br />

[1] Deksel<br />

[2] Skruer deksel<br />

[3] O-ring<br />

[4] Skruer stikkontakt<br />

[5] Stikkontakt<br />

[6] Kabelinnføring<br />

[7] Plugg<br />

[8] Kabelinnføring (ikke inkludert i leveransen)<br />

Farlig spenning!<br />

Elektrisk støt er mulig.<br />

→Spenning må kobles fra før den åpnes.<br />

1. Løsne skruene [2] og ta av dekselet [1].<br />

2. Løsne skruene [4] og ta stikkontakten [5] ut av dekselet [1].<br />

3. Bruk kabelinnføringer [8] som passer til kablene.<br />

➥ Vernetypen IP... som er angitt på typeskiltet, er kun gyldig når det monteres<br />

kabelgjennomføringer av tilsvarende kapslingsgrad. Eksempel: Typeskilt for<br />

kapslingsgrad IP 68.<br />

4. Monter egnede plugger [7] på kabelinnføringer [6] som ikke brukes.<br />

5. Før kablene inn i kabelinnføringene [8].<br />

✔Tillatte tilkoplingstverrsnitt må overholdes.<br />

1. Avisoler kablene.<br />

2. Avisoler lederne.<br />

3. Ved fleksible ledninger: Bruk endehylser iht. DIN 46228.<br />

4. Tilkoble ledningen i henhold til det tilhørende koblingsskjemaet.<br />