INSERT COMPANY LOGO Building Air Leakage Test Results In Compliance with European Norm EN13829
Building Details Building Address: Nieuw Zuid, 's-Hertogenbosch Test technician: Gregor Leppers Dennis Strijards Test company: <strong>Nieman</strong> Raadgevende Ingenieurs Elevation: 7 m Height above ground: 0 m Building Volume, V: 7.850 m³ Total envelope area, A T BAT 2.194 m² Building exposure to wind: Onbeschermd gebouw Accuracy of measurements: 0% Testing Details Fan Model: Retrotec 3000SR Fan SN: Gauge Model: DM-2 Gauge SN: 205895 Onderdruk set Date: 2012-09-15 Time: 11:03 to 11:13 Environmental Conditions: Barometric Pressure: 101,3 KPa from Standaard temperatuur en druk. Wind speed: 2. lichte wind Temperature: Initial: indoors 20 °C outdoors 15 °C. Final: indoors 20 °C outdoors 15 °C. Test Data: 3 bias pressures taken for 10 sec each. 9 building pressures taken for 20 sec each. Bias, initial [Pa] Building Test Pressure [Pa] Bias, final[Pa] Door Fan Pressure, [Pa] Total flow, V r [m 3 /h] Corrected flow, V env [m 3 /h] -0,49 -0,04 -0,25 -21,2 -29,1 -40,0 -49,2 -59,5 -70,7 -80,7 -91,6 -99,2 -0,32 -0,39 -0,43 13,8 26,7 42,5 55,9 72,2 86,9 101,6 123,1 135,4 504,4 699,8 885, 0 1013, 4 1157, 8 1273, 3 1382, 5 1524, 5 1602, 9 495,4 687,2 869,2 995,2 1137 1251 1358 1497 1574 Error [%] -6,2% 3,4% 4,1% 2,5% 2,3% -0,7% -1,9% -1,2% -1,9% Bias pressure Averages: initial [Pa] ∆P 01 -0,26, ∆P 01- -0,26, ∆P 01+ 0,00 final [Pa] ∆P 01 -0,38, ∆P 01- -0,38, ∆P 01+ 0,00