21 RO1<br />

22 RO1<br />

23 RO1<br />

1 + 10 Vref Referentie uitgang<br />

(spanning voor potentiometer etc.)<br />

2 AI1 + Analoge ingang 1 (Volt signaal)<br />

3 AI1 <strong>–</strong> I/O massa<br />

4 AI2 + Analoge ingang 2 (mA signaal)<br />

5 AI2 <strong>–</strong><br />

6 +24 V +24 V uitgang (max. 0.1 A)<br />

7 GND I/O massa<br />

8 DIN1 Digitale Ingang 1 (Start vooruit)<br />

Relais 1<br />

NO/NC<br />

(storing)<br />

Fig. 5. NXL HVAC controle aansluitingen<br />

7<br />

9 DIN2 Digitale Ingang 2<br />

(Start terug)<br />

10 DIN3 Digitale Ingang 3<br />

(Preset speed 1,<br />

default: 10 Hz)<br />

11 GND I/O massa<br />

18 AO1 +<br />

19 AO1 <strong>–</strong><br />

A RS485<br />

B RS485<br />

HVAC FREQUENTIEREGELAARS<br />

Analoge uitgang 1<br />

Bereik 0<strong>–</strong>20 mA/RL,<br />

max. 500 Ω<br />

Modbus RTU, serieele bus<br />

30 +24V Ingang voor +24 V backup<br />

spanning<br />

12 + 24 V +24 V uitgang (max. 150 mA)<br />

13 GND I/O massa<br />

14 DIE1 Exp. Digitale ingang 1<br />

(Preset speed 2, default: 50 Hz)<br />

15 DIE2 Exp. Digitale ingang 2<br />

(Reset)<br />

16 DIE3 Exp. Digital Input 3<br />

(blokkering PID)<br />

25 ROE1<br />

26 ROE1<br />

28 TI+<br />

29 TI <strong>–</strong><br />

Thermistor Ingang;<br />

Rtrip = 4.7 k1Ω (PTC)<br />

Exp. Relais 1<br />

NO (bedrijf)