M A I N T E N A N C E9. Press the plug connections of the internal battery togetheragain. Connect red with red and black with black. Press bothparts together firmly to ensure a good connection.10. Only for device types up to 1500 VA: If the cable for an additionalbattery module is not connected, secure the cable again tothe corresponding holder on the battery cover (see Figure 17).11. Reinsert the front cover of the UPS system. For an additionalbattery module, make sure that the cable of the battery moduleis guided through the cable ejection. Slide the cover to theright until it engages in the holder on the left side of the housing.Reattach the two screws on the right side of the front cover.12. Proceed with section Testing the new batteries.7.4.4 Replacing the battery module of the rack modelCAUTIONThe battery module is very heavy. At least two persons arerequired for lifting the housing.1. Remove the front cover of each individual battery module (seeFigure 18). To remove the cover, unscrew and remove the twoscrews on the right side of the cover. Grasp the cover on twosides, slide it to the left and remove it from the housing.Figure 18: Removing the front cover of the battery module129 / 222XS700-XS3000_manual_ger_eng_it_V1.1.0.doc ........................................................... R. Kistler