10.07.2015 Views

Benutzerhandbuch - Online USV Systeme

Benutzerhandbuch - Online USV Systeme

Benutzerhandbuch - Online USV Systeme

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

C O M M U N I C A T I O N6.1.5 Programmable signal inputsThe UPS system has two programmable signal inputs:One signal input in the RS-232communication interface (Pin 3).Select „SETTINGS“, „USER SETTINGS“, „SIGNAL INPUTS“and then „RS232-3“.One signal input over the optional relay card respectively theAS400-Interface, see Slot for Interface Cards.Select „SETTINGS“, „USER SETTINGS“, „SIGNAL INPUTS“and then „XRCARD SIGNAL“.For the position of the interfaces, see Figure 10.Signal"Not Used""Force Bypass""RemoteShutdown"“DelayedShutdown”(and restart)"On Generator""Buildingalarm 1"DescriptionThe input only functions as serial input (RxD) or has no function.Note: With xRCard signal und using a SNMP adapter, this optionmust be enabled.UPS is switched in bypass mode.UPS is switched after a defined time "Remote Shutdown Delay" instandby mode.The UPS system will not automatically switch in the normal mode,when the main power returns.UPS is switched after a defined time "Delayed Shutdown Delay" instandby mode.The UPS system will automatically switch in the normal mode,when the main power returns.UPS is switched unsynchronized to bypass mode.UPS generates the "Building alarm 1" warning message.Table 9: Programmable signal inputs optionsLine input"high""low"DescriptionActive state of the high potential (+UDC)Active state of the low potential ( GND or -UDC)Note: Using a relay card or a AS400-Interface, this option must beenabled.Table 10: Polarity options119 / 222XS700-XS3000_manual_ger_eng_it_V1.1.0.doc ........................................................... R. Kistler

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!