C O M M U N I C A T I O N6.1.4 Programmable output contactsThe UPS system has three programmable output contacts:One relay output.Select „SETTINGS“, „USER SETTINGS“, “RELAYCONFIGURATION“ and then „STANDARD“.Two potential free outputs (optocoupler, max. 5mA)in the RS-232 communication interface (Pin 1 and 8).Select „SETTINGS“, „USER SETTINGS“, “RELAYCONFIGURATION“ and then „RS232-1“ or „RS232-8“.For the position of the interfaces, see Figure 10.CAUTIONThe relay output contact may not be connected to circuitsthat are connected with the mains power supply network.A reinforced insulation to the mains is required The relayoutput contact have a maximum nominal value of 30VAC /1A and 60VDC / 2A.Signal"UPS ok""On Bypass""On Battery""BatteryLow"DescriptionUPS is in normal mode, battery mode or bypass modeand no warning messages are active.UPS is in bypass mode.UPS is in battery modeafter a defined time “On Battery Notice Delay”.UPS is in battery mode and battery low signalafter a defined time “Battery Low Alarm”.Table 8: Programmable output contacts optionsFigure 13: Connections of the standard relay interface118 / 222XS700-XS3000_manual_ger_eng_it_V1.1.0.doc ........................................................... R. Kistler