O P E R A T I O N4.8 Configuring the battery settings4.8.1 Configuring the UPS system for battery modulesConfigure the UPS system for the correct number of external batterymodules to ensure a maximum battery runtime:1. Press any button on the front display to activate the menuoptions and select the "SETTINGS", "USER SETTINGS" and"NUMBER OF BATTERY STRINGS".2. Select the number of battery rows depending on your UPSconfiguration using the or button:Number of battery stringsAll UPS systems and battery modules0 UPS system only (no internal batteries)1 (standard) UPS system only (internal batteries)3 UPS system + 1 battery module5 UPS system + 2 battery modules7 UPS system + 3 battery modules9 UPS system + 4 battery modulesTable 5: Number of battery rowsNOTEIf 0 was selected, no internal batteries and no additionalbattery modules are connected and all warning messagesrelated to the batteries are disabledThe UPS system contains one battery row; each batterymodule contains two battery rows3. Press the button to save the setting.4. Press the esc button until the start screen is displayed.110 / 222XS700-XS3000_manual_ger_eng_it_V1.1.0.doc ........................................................... R. Kistler