6. Technical data6.1 Electrical specificationsModel number YUNTO Q450 YUNTO Q700 YUNTO Q1250INPUTVoltage230 VAC (197 - 262 VAC)Frequency50 Hz ± 4Hz ; 60Hz±4HzAmperage2.6 A 4.0 A 7.0 A(maximum)Phase1ψ 2W, GroundOUTPUTPower rating 450 VA270 W700 VA420 W1250 VA750 WVoltage 230 VAC ± 10 %Frequency50 Hz ± 1Hz ; 60 Hz ± 1HzWave formSTEPRecharge time 8hr up to 90%OverloadprotectionLine mode ≧ 105%, ≦ 130% load 3 minutes to faultLine mode > 130%7s to faultBattery mode≧ 105%≦ 120% loadBattery mode > 120% load20s to shutdown5s to shutdownThese units bear the CE mark and comply with the following standards:EN 62040-1-1: 2003IEC 60950-1: 2001EN 50091-2: 1995EN 62040-2: 1999EN 61000-2-2: 1990IEC 61000-4-2: 2001IEC 61000-4-3: 2001IEC 61000-4-4: 2001IEC 61000-4-5: 2001YQ_manual_ger-eng-it_ 2009-09-29.doc269/29/2009, S. Spitzley