24Vac ± 10% 50/60Hz<br />
230Vac ± 10% 50/60Hz<br />
115Vac ± 10% 50/60Hz<br />
10.3 Analog input for temperature sensors<br />
Thermocouples K, S, R;J;<br />
Respect polarities<br />
When extending thermocouples be sure to use the<br />
correct extension/compensating cable<br />
Pt 100 3 Wires<br />
Only model AD<br />
To assure optimal operation of the device, use<br />
ground-isolated sensors.<br />
Otherwise use single isolated transformers for<br />
each controller<br />
For a three-wires PT100 use cables with the same<br />
diameter;<br />
For a two-wires Pt100 shortcircuit pins 10 and 12.<br />
3<br />
2<br />
1<br />
For<br />
PTC 1000 ohm<br />
NTC 10 K<br />
PT500, PT1000<br />
Linear potentiometers 6K or 150K<br />
10.4 Analog input V / mA<br />
Signals<br />
0…10V<br />
Respect polarities<br />
Ri>=110KΩ<br />
Signals<br />
0 ÷ 20mA or 4 ÷ 20mA<br />
with three-wires sensors<br />
Respect polarities<br />
A= sensor supply<br />
Check power supply requirements on technical<br />
data sheet of sensor!<br />
Capacity 12…24V / 30mA for models AD<br />
10