Installation<br />

Scope of delivery<br />

Manifold supply and return mounted on brackets<br />

end pieces for filling manual ventilation, draining<br />

with ball valves and instruction manual and identifying<br />

labels for rooms and <strong>circuit</strong>s adjustable screw<br />

fitting flowmeter and valve maximum opened.<br />

D<br />

Installation<br />

• In in-wall or on-wall cabinet<br />

• Directly on the wall (sound protection not<br />

included)<br />

GB<br />

Cabinet width<br />

Number of <strong>circuit</strong>s (Size)<br />

0 560 mm 4 3 2 - - -<br />

I 700 mm 7 6 4 3 2 -<br />

II 900 mm 11 10 7 7 6 4<br />

III 1.100 mm 12 12 12 11 11 8<br />

IV 1.300 mm 12 12 12 12 12 12<br />

0 550 mm 4 3 2 - - -<br />

I 750 mm 8 7 5 4 3 -<br />

II 950 mm 12 11 8 8 7 5<br />

III 1.150 mm 12 12 12 12 12 9<br />

F<br />

Connection of the<br />

heating and cooling<br />

<strong>circuit</strong>s<br />

• Connection of main supply and return<br />

1" (male) flat sealed<br />

• Connection of the heating/cooling <strong>circuit</strong>s<br />

with compression fittings or press connections<br />

¾" euro cone<br />

I<br />

Compression fittings Ø 11, 14, 16, 17, 20 Press connection Ø 14, 16, 17, 20<br />