- pulse-driven (depending on the need / requirements), the short opening of a hot water tap (tap<br />
pulse) starts the circulation pump. The circulation pump will then run for several minutes<br />
(adjustable).<br />
- time-dependant, the operation of the circulation pump can be adjusted within an arbitrary<br />
period of time on a “week clock”. The circulation will start at the beginning of the period of time<br />
chosen. It will stop after the end of the chosen period of time.<br />
- time- / temperature -dependant, the operation of the circulation pump can be adjusted<br />
within an arbitrary period of time on a “week clock. The circulation only starts when the<br />
adjustable min. temperature on the heat exchanger is exceeded within the period of operation<br />
chosen. The circulation stops after the required temperature has been reached i.e. after the end<br />
of the chosen period of time.<br />
While delivered, the circulation (see user’s manual of the controller, menu „OPTIONEN“) is<br />
preset on „NEIN“ (OFF). After the assembly of the circulation, it is obligatory to select one<br />
mode of operation.<br />
A circulation temperature of more than 55°C favorizes the calcination of the heat<br />
exchanger. The water preparation cannot be germfree at circulation temperatures of<br />
under 50°C!<br />
Gravity brakes<br />
The primary circuit (heating circuit) is provided with a<br />
gravity brake inside the thermovalve (7), in order to<br />
securely avoid unwished recirculations (gravity circulation).<br />
For the filling, dearating and purging of the system, the<br />
gravity brake has to be open. This is<br />
done by half-opening the<br />
thermovalve (7) (with a n° 14 flat<br />
wrench). The ball of the ball valve<br />
pushed the gravity brake open.<br />
9<br />
For the operation of the system, all<br />
ball valves and valves need to be<br />
open completely<br />
An inserted lock valve – serving as return flow inhibitor –<br />
is located in the connection of the circulation tubing (T,<br />
9). This way it can be assured that possible short-circuit<br />
flows through the circulation tubing during the hot water<br />
extraction can be avoided.<br />
7<br />
Frage: Entlüftung des Zirkul-stranges = ?????<br />