Carry on the filling and purging until it can be guaranteed that the system is completely deaerated!<br />

Any audible flow sounds during the operation of the circulation pump(s) are evidence to that fact that<br />

there still remains air in the system.<br />

Setting up the wanted potable water temperature<br />

The wanted (max.) hot water temperature is set up on the controller (see user’s manual for the<br />

controller, menu „EINSTELLWERTE“).<br />

In order to rule out the danger of scalds on the water tap, the maximum water temperature should<br />

never exeed 60°C. Already at 52°C a steadily germfree water preparation is warranted. The<br />

necessary temperature on the primary side (inside the buffer storage) depends on the wanted (max.)<br />

hot water temperature as well as on the quantity needed. The temperature inside the buffer storage<br />

has to be at least 5K higher that the wanted hot water temperature! The coefficients mentioned in<br />

the following chart can serve as indications.<br />

Tap potential / max. tap quantity / extraction power<br />

The tap potential [l/min] depends on the hot water temperature set up on the controller and the<br />

temperature available in the storage.<br />

The maximum volume flow of potable water for the FriwWa module is 40 l/min!<br />

The max. tap quantities mentioned below can be extractesd at once if the upper 200 l of the buffer<br />

storage are entirely heated to the required temperature. A further (post-) heating of the storage<br />

during the extraction was not taken into consideration.<br />

The extraction power is necessary in order to heat up the water quantity of the tap potential<br />

[l/min] from 10°C to 45°C.<br />

storage<br />

temperature<br />

50 °C<br />

60 °C<br />

70 °C<br />

80 °C<br />

hot water<br />

temperature<br />

set up on<br />

the<br />

controller<br />

tap potential at 45°C<br />

(on the water tap)<br />

max. tap quantity<br />

(on the water tap)<br />

at 200 l inside the<br />

storage with storage<br />

temperature<br />

extraction<br />

power<br />

45 °C 20,5 l/min 155 l 50 kW<br />

55 °C - / - - / - - / -<br />

45 °C 31,7 l/min 240 l 77 kW<br />

55 °C 23,7 l/min 180 l 61 kW<br />

45 °C 40,0 l/min 310 l 99 kW<br />

55 °C 35,4 l/min 265 l 90 kW<br />

45 °C 40,0 l/min 370 l 99 kW<br />

55 °C 44,7 l/min 335 l 114 kW<br />

Circulation operation (optional)<br />

The fresh water module is (optionally) provided with a circulation pump. The circulation pump can be<br />

retrofitted (while doing this, the paragraphs “Wall fastening, Connexion Diagram, Electrotechnical<br />

Connexion and Commissioning” have to be taken into consideration in particular).<br />

For the operatoin of the circulation pump, 3 possible modes of operation can be chosen on the<br />

controller (see also the user’s manual for the controller, menu “OPTIONEN”):<br />

18/59