Assembly instructions<br />

Tipps and tricks:<br />

For the assembly of the fresh water module you need (apart from the <strong>FriWa</strong>):<br />

- as tools: level, folding rule, power drill with 10 mm masonry drill bit (for masonry assembly), flat<br />

wrench n°13 for the fixation screws and n°31and n° 37 in order to hold against during the<br />

assembly of the tubing and if necessary in order to retightening of the connecting nuts,<br />

- a 2 nd person for the wall assembly.<br />

Security equipment – please note:<br />

The fresh water module is provided with a membrane security valve ¾“x1“ which meets the<br />

appropriate regulations. The following advices need to be taken into consideration for the assembly<br />

and the operation:<br />

• The valve may not be impaired or rendered ineffective by blockages!<br />

• Dirt collectors or other constrictions are not permitted between the collector (field) and the safety<br />

valve.<br />

• The diameter of the blow line must equal the diameter of the valve outlet; the max. length may<br />

not exceed 2m. More than 2 bends are not permitted. If these maximum values (2 bends, 2m<br />

line) are exceeded, the next largest size must be selected for the blow line. However, it must also<br />

be noted that even with the larger size more than 3 bends and 4m line length are not permitted.<br />

• If the blow line is routed in a drain pipe with a funnel, the size of the drain pipe must be at least<br />

double that of the cross section of the valve inlet. You must also ensure that the blow line is laid<br />

at a slope; the mouth must be open and visible and routed such that the blowing process does<br />

not endanger persons.<br />

Order of work steps:<br />

- Determine the location of the system – possibly near the buffer storage. Install the <strong>FriWa</strong><br />

(see wall assembly).<br />

- Connect the pipes according to the appropriate regulations (heating side at least DN25) and<br />

connect the fresh water module (see connexion plan). In order to avoid any kind of<br />

electrochemical corrosion, you absolutely need to follow the installation order while using<br />

galvanised pipes and fittings! Tighten all the nuts and screwings.<br />

- Charge qualified personell with the electrotechnical connexion of the system. (see<br />

electrotechnical connexion). The corresponding regulations (VDE 0100 etc.) need to be<br />

respected.<br />

- Pressure test und commissioning of the system (see commissioning).<br />