9 FINAL INSTALLATION CHECKS<br />

Useful Functions (SM802AT-E only)<br />

In addition to the code checking by remote controller of the indoor unit, troubles of the outdoor unit can be diagnosed by <strong>LE</strong>D indications on the<br />

cycle control P.C. board of the outdoor unit. Utilize them for various checks.<br />

For the check by remote controller of the indoor unit, refer to the installation Manual of the indoor unit.<br />

Before a check, confirm each bit of the DIP switch is set to OFF position.<br />

<strong>LE</strong>D indication and code c hecking<br />

ON<br />

DIP switch<br />

SW802<br />

1 2 3 4<br />

Installation/Servicing Tools<br />

In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged accidentally, the service port diameter<br />

of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch)<br />

• In order to increase the pressure resisting strength of the refrigerant piping, flare processing diameter and size of opposite side of flare nuts<br />

has been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)<br />

New tools for R410A<br />

New tools for R410A Applicable to R22 model Changes<br />

Gauge manifold<br />

Charge hose<br />

Electronic balance<br />

for refrigerant charging<br />

Torque wrench<br />

(nominal diam. 1/2, 5/8)<br />

Flare tool<br />

(clutch type)<br />

Gauge for projection adjustment<br />

Vacuum pump adapter<br />

Gas leakage detector<br />

Cycle control P.C. board<br />

—<br />

Self-Diagnosis by <strong>LE</strong>D Indication<br />

<strong>LE</strong>D indication Cause<br />

D800 D801 D802 D803<br />

\ [ [ [ Heat exchanger sensor (TE) error<br />

[ [ \ [ Suction sensor (TS) error<br />

\ \ [ [ Discharge sensor (TD) error<br />

[ \ [ \ High-pressure protection error<br />

[ \ [ [ Outdoor temperature sensor (TO) error<br />

\ \ \ [ DC outside fan error<br />

\ [ [ \ Communication error between IPDU<br />

[ \ \ [ Discharge temp. error<br />

\ \ [ \ EEPROM error<br />

[ [ \ \ Communication error between IPDU<br />

[ [ [ G-Tr short-circuit protection<br />

[ [ [ Detect circuit error<br />

[ [ Current sensor error<br />

[ [ [ Comp. lock error<br />

[ [ Comp. break down<br />

[ [ [ Phase missing detection, Detection of coming-off of CT current sensor<br />

[ \ [ \ Serial communication error by thermo. operation of Comp. case<br />

—<br />

Changes in the pr oduct and components<br />

As pressure is high, it is impossible to measure by means of conventional gauge. In<br />

order to prevent any other refrigerant from being charged, each port diameter is<br />

changed.<br />

In order to increase pressure resisting strength, hose materials and port size are<br />

changed (to 1/2 UNF 20 threads per inch).<br />

When purchasing a charge hose, be sure to check the port size.<br />

As pressure is hight and gasification speed is fast, it is difficult to read the indicated<br />

value by means of charging cylinder, as air bubbles occur.<br />

The size of opposite sides of flare nuts have been increased. Incidentally, a common<br />

wrench is used for nominal diameters 1/4 and 3/8.<br />

By increasing the clamp bar’s receiving hole, strength of spring in the tool has been<br />

improved.<br />

Used when flare is made with using conventional flare tool.<br />

Connected to the conventional vacuum pump. It is necessary to use an adapter to<br />

prevent vacuum pump oil from flowing back to the charge hose.<br />

The charge hose connecting part has two ports-one for conventional refrigerant (7/16<br />

UNF 20 threads per inch) and one for R410A. If the vacuum pump oil (mineral) mixes<br />

with R410A a sludge may occur and damage the equipment.<br />

Exclusive for HFC refrigerant.<br />

<strong>LE</strong>D<br />

indication<br />

D800<br />

: Red<br />

\<br />

D801<br />

:Yellow<br />

\<br />

D802<br />

:Yellow<br />

\<br />

D803<br />

:Yellow<br />

\<br />

: Rapid flash<br />

[ : Go off<br />

\ : Go on<br />

• Incidentally, the “refrigerant cylinder” comes with the refrigerant designation (R410A) and protector coating in the U. S’s ARI specified rose<br />

color (ARI color code: PMS 507).<br />

• Also, the “charge port and packing for refrigerant cylinder” require 1/2 UNF 20 threads per inch corresponding to the charge hose’s port size.<br />

18