CLOSE CONTROL AIR CONDITIONERS<br />

OPERATION AND ROUTINE MAINTENANCE MANUAL<br />

4.1 MAINTENANCE OF THE AIR FILTERS<br />

On TECNAIR LV <strong>air</strong> <strong>conditio</strong>ners, all <strong>air</strong> filters are equipped with differential pressure switches to monitor pressure loss<br />

caused by clogging. The microprocessor signals when the measured pressure difference exceeds the set value. To change the trip<br />

setting of a differential pressure switch, simply unscrew the cover and turn the setting dial to the desired pressure differential value.<br />

4.1.1 AIR FILTER REPLACEMENT<br />

Page 18 of 80<br />

FILTER TYPE POSITION VALUE [Pa]<br />

G4 / F7 filter Suction 250<br />

NOTE:<br />

G4 can be partially regenerated by washing in hot water and neutral detergents.<br />

To ensure the efficiency of the filters, it is necessary to install the 15x3 mm seal<br />

(supplied with replacement filters)<br />

To replace the <strong>air</strong> filters the following instructions must be observed, as well as full compliance with safety obligations<br />

regarding use of the equipment:<br />

1. Set the main switch to “0”.<br />

2. Open the front panels via the relative safety locks.<br />

3. Remove the filter support by means of the fixing screws.<br />

4. Replace clogged filters with clean or regenerated versions.<br />

5. Position the support and secure by means of the fixing screws.<br />

6. Close the front panels and return the main switch to “I”.<br />

Air filter position<br />

For more detailed and specific information on causes of the alarm, refer to the<br />

INSTALLATION OPERATION AND MAINTENANCE MANUAL of the unit en<strong>close</strong>d with the<br />

IT media supplied.