Principle of Operation7 Principle of OperationThe following diagram (fig. 1) shows a simplified typical grounded distribution system.Its equivalent circuit (fig. 2) is shown below. If R 1 , R 2 , R 3 , ... R n is combined as R eq ,then only R g and R eq are left in the circuit (see figure). If a constant voltage is appliedto the circuit, the following equation is valid:UI=R g+ R eqwhere1Req = , i = 1,2,...n1∑RIf R g and R 1 , R 2 , ... R n are about the same, and n is a large number (such as 200),then R eq will be much less than R g and maybe approach zero.iRg>>eq( R → 0)Example:If R g and R 1 , R 2 , ... R n are all 10 Ω, respectively and n = 200, then R eq by calculationequalsReq= 1= 0, Ω1 1 105+ + ... +10 10 10UI= R + R = 10 + 0,05 = 10, 05 →geqRgIn this example, we can see that as long as the number of multiple electrodes is largeenough, the equivalent resistance is negligible with respect to the ground resistance tobe measured.<strong>HEME</strong> <strong>GEO</strong> <strong>30</strong> 17SO81<strong>30</strong>Z Rev. B