6. Commissioning/operating control<br />
6.1 General<br />
Flush system thoroughly without pump. See section 4.<br />
Fill and de-aerate the system properly.<br />
Only put the pump into operation when the system is full.<br />
Switch on the supply voltage.<br />
6.2 Venting<br />
The pump is vented automatically after a brief period of operation.<br />
A short period of dry running (max. 2 mins.) does not harm<br />
the pump. The pump is vented when it runs quietly.<br />
The pump also has an additional «venting» mode of operation:<br />
– The pump changes to the «venting» («- -») mode of operation<br />
after holding down the control button (for at least 5 secs.)<br />
The pump can then be switched on/off by pressing the button<br />
briefly.<br />
The percentage symbol («%») flashes when the pump is running.<br />
– Additional venting by opening the hot water tapping points<br />
several times.<br />
– The pump is returned to the normal mode of operation<br />
by keeping the control button pressed again (or automatically<br />
after 5 mins.)<br />
Warning<br />
The pump must not be operated without water!<br />
6.3 Operating check<br />
% lights = normal operation, pump does not run<br />
% flashes = normal operation, pump running<br />
The figure indicates the proportion of pump running time<br />
to the total operating time.<br />
6.4 Deblocking<br />
Owing to the very high torque of the permanent magnet motor,<br />
it is unnecessary to deblock the pump. The electronic system<br />
also has an automatic deblocking program.