LOW PRESSURE SHUTDOWN<br />

LOW PRESSURE SHUT-DOWN<br />

YES<br />

Indoor unit working<br />

correctly?<br />

NO<br />

Check operation<br />

of the indoor unit ( 1 )<br />

Check operating conditions<br />

of the indoor unit ( 2 )<br />

Check connection pipes<br />

( 3 )<br />

YES<br />

Dewatering filter<br />

working efficiently?<br />

NO<br />

Check ∆t from upstream<br />

to downstream ( 4 )<br />

YES<br />

Refrigerant charge<br />

correct?<br />

NO<br />

Check<br />

superheating ( 5 )<br />

YES<br />

Intake valve completely<br />

open?<br />

NO<br />

Check and open if<br />

necessary<br />

YES<br />

Intake temperature and/or<br />

pressure correct?<br />

NO<br />

Check operation<br />

of outdoor unit ( 6 )<br />

Unit working<br />

Notes<br />

1) Check:<br />

- That there is sufficient air flow.<br />

- That the direction of rotation of the fans is correct.<br />

- That the exchanger is not dirty or blocked, and can provide maximum heat exchange.<br />

- That the solenoid valve is working.<br />

- That the thermostat is working.<br />

2) Check that the temperature/humidity conditions of the air being treated falls within the design conditions.<br />

3) Check that the layout and the diameter of the pipes are correctly sized (see the section on REFRIGERANT PIPES). If not,<br />

unacceptable pressure drops may occur for the correct operation of the unit.<br />

4) Check, using a thermometer in direct contact, the temperature upstream and downstream of the dewatering filter. If the<br />

difference in temperature is higher than 1°C, the filter is not working efficiently or is under-rated; in both cases, replace the<br />

filter.<br />

5) For information on how to perform the checks, please refer to section on START-UP.<br />

6) If the condensing pressure is below 1200kPa there may be irregular supply to the expansion device and as a<br />

consequence too low inlet pressure.<br />

Check that the ventilation system for the outdoor unit is working perfectly (that is, modulates or stops the fans).<br />