LOW PRESSURE SHUTDOWN<br />
LOW PRESSURE SHUT-DOWN<br />
YES<br />
Indoor unit working<br />
correctly?<br />
NO<br />
Check operation<br />
of the indoor unit ( 1 )<br />
Check operating conditions<br />
of the indoor unit ( 2 )<br />
Check connection pipes<br />
( 3 )<br />
YES<br />
Dewatering filter<br />
working efficiently?<br />
NO<br />
Check ∆t from upstream<br />
to downstream ( 4 )<br />
YES<br />
Refrigerant charge<br />
correct?<br />
NO<br />
Check<br />
superheating ( 5 )<br />
YES<br />
Intake valve completely<br />
open?<br />
NO<br />
Check and open if<br />
necessary<br />
YES<br />
Intake temperature and/or<br />
pressure correct?<br />
NO<br />
Check operation<br />
of outdoor unit ( 6 )<br />
Unit working<br />
Notes<br />
1) Check:<br />
- That there is sufficient air flow.<br />
- That the direction of rotation of the fans is correct.<br />
- That the exchanger is not dirty or blocked, and can provide maximum heat exchange.<br />
- That the solenoid valve is working.<br />
- That the thermostat is working.<br />
2) Check that the temperature/humidity conditions of the air being treated falls within the design conditions.<br />
3) Check that the layout and the diameter of the pipes are correctly sized (see the section on REFRIGERANT PIPES). If not,<br />
unacceptable pressure drops may occur for the correct operation of the unit.<br />
4) Check, using a thermometer in direct contact, the temperature upstream and downstream of the dewatering filter. If the<br />
difference in temperature is higher than 1°C, the filter is not working efficiently or is under-rated; in both cases, replace the<br />
filter.<br />
5) For information on how to perform the checks, please refer to section on START-UP.<br />
6) If the condensing pressure is below 1200kPa there may be irregular supply to the expansion device and as a<br />
consequence too low inlet pressure.<br />
Check that the ventilation system for the outdoor unit is working perfectly (that is, modulates or stops the fans).<br />
49