HIGH PRESSURE SHUTDOWN<br />
HIGH PRESSURE SHUT-DOWN<br />
YES<br />
Ventilation working<br />
efficiently?<br />
NO<br />
Check the coil<br />
( 1 )<br />
Check the fan<br />
( 2 )<br />
Check the fan module<br />
( 3 )<br />
Check the probe<br />
( 4 )<br />
YES<br />
Outside air temperature<br />
lower than the operating<br />
limits?<br />
NO<br />
Check the design data<br />
( 5 )<br />
YES<br />
Refrigerant charge correct?<br />
NO<br />
Check liquid subcooling<br />
( 6 )<br />
YES<br />
Absence of incondensables?<br />
NO<br />
Empty and recharge<br />
( 7 )<br />
YES<br />
Intake temperature and/or<br />
pressure correct?<br />
NO<br />
Check operation<br />
of the indoor unit ( 8 )<br />
Check operation of the<br />
liquid line on-off valve<br />
( 9 )<br />
Unit working<br />
Notes<br />
The condenser must provide the maximum heat exchange, and as a consequence must be free of dirt, deposits or obstacles<br />
to the flow of air.<br />
2) Check the condition of the fan and replace it if damaged.<br />
3) Check that the voltage output from the board proportionally modulates the fan speed. If not, replace the module.<br />
4) Check the positioning: it must be in close contact with the shaped exchanger coil pipe. The resistance values must be<br />
perfectly in line with the temperature; check the resistance values using a special ohmmeter.<br />
5) Check:<br />
- Operating limits. (see the general section)<br />
- That the coil not is exposed to direct sunlight or placed near reflecting surfaces.<br />
- That there are no hot air streams of any type in the immediate vicinity.<br />
- That the same air is not recirculated.<br />
6) For information on how to perform the checks, please refer to section on START-UP. NB the flooding of the exchanger coil<br />
circuits to the point of the probe socket will cause the anomalous operation of the fan speed controller.<br />
7) One condition that may arise is a very high condensing temperature (25/30 degrees above the air temperature) combined<br />
with low refrigerant efficiency. This may cause the same symptoms as an excessive refrigerant charge. Check the charge<br />
and, if correct, evaluate this possibility and perform all the emptying and charging operations again.<br />
8) Check that the air flow-rate not is too high and that the ambient air temperature is not too high. These conditions may<br />
increase the output of the machine and consequently the heat to be dispersed by the condenser.<br />
9) Check that all the on-off devices on the liquid line are completely open.<br />