HIGH PRESSURE SHUTDOWN<br />

HIGH PRESSURE SHUT-DOWN<br />

YES<br />

Ventilation working<br />

efficiently?<br />

NO<br />

Check the coil<br />

( 1 )<br />

Check the fan<br />

( 2 )<br />

Check the fan module<br />

( 3 )<br />

Check the probe<br />

( 4 )<br />

YES<br />

Outside air temperature<br />

lower than the operating<br />

limits?<br />

NO<br />

Check the design data<br />

( 5 )<br />

YES<br />

Refrigerant charge correct?<br />

NO<br />

Check liquid subcooling<br />

( 6 )<br />

YES<br />

Absence of incondensables?<br />

NO<br />

Empty and recharge<br />

( 7 )<br />

YES<br />

Intake temperature and/or<br />

pressure correct?<br />

NO<br />

Check operation<br />

of the indoor unit ( 8 )<br />

Check operation of the<br />

liquid line on-off valve<br />

( 9 )<br />

Unit working<br />

Notes<br />

The condenser must provide the maximum heat exchange, and as a consequence must be free of dirt, deposits or obstacles<br />

to the flow of air.<br />

2) Check the condition of the fan and replace it if damaged.<br />

3) Check that the voltage output from the board proportionally modulates the fan speed. If not, replace the module.<br />

4) Check the positioning: it must be in close contact with the shaped exchanger coil pipe. The resistance values must be<br />

perfectly in line with the temperature; check the resistance values using a special ohmmeter.<br />

5) Check:<br />

- Operating limits. (see the general section)<br />

- That the coil not is exposed to direct sunlight or placed near reflecting surfaces.<br />

- That there are no hot air streams of any type in the immediate vicinity.<br />

- That the same air is not recirculated.<br />

6) For information on how to perform the checks, please refer to section on START-UP. NB the flooding of the exchanger coil<br />

circuits to the point of the probe socket will cause the anomalous operation of the fan speed controller.<br />

7) One condition that may arise is a very high condensing temperature (25/30 degrees above the air temperature) combined<br />

with low refrigerant efficiency. This may cause the same symptoms as an excessive refrigerant charge. Check the charge<br />

and, if correct, evaluate this possibility and perform all the emptying and charging operations again.<br />

8) Check that the air flow-rate not is too high and that the ambient air temperature is not too high. These conditions may<br />

increase the output of the machine and consequently the heat to be dispersed by the condenser.<br />

9) Check that all the on-off devices on the liquid line are completely open.<br />