MSAT 102-122-142-162-182-202-242

MSAT 102-122-142-162-182-202-242 MSAT 102-122-142-162-182-202-242

ecvest.com1.ru
from ecvest.com1.ru More from this publisher
30.10.2014 Views

ALARMS The alarm codes appear on the display of the use interface terminal when errors occur. If the alarms displayed feature automatic reset, they will disappear as soon as the problem has been resolved, while those with manual reset must be reset by a service engineer. The alarms appear on the user interface terminal following the sequence shown in Table. It should also be highlighted that if more than one alarm is active, only the first will be displayed, and when this is reset the second will appear, and so on until no more alarms are active. Note: in standby mode, or alternatively when the unit is OFF, the alarms are not signalled and the cumulative fault relay is not activated. The alarms, if present, are signalled and the cumulative fault relay is activated when the operating mode is selected. Table 2 Codice Tipo di guasto Blocchi Ripristino E01 Max pressure circ. 1 Compressor MANUAL E02 Min pressure circ. 1 Compressor fan AUTOMATIC (After 5 manual reset signals) E03 Compressor 1 thermal Compressor fan MANUAL E04 Fan thermal cut-out circ. 1 Compressor fan MANUAL E07 Probe fault BT3/BP3 Compressor fan AUTOMATIC E21 Max pressure circ. 2 Compressor fan MANUAL E22* Min pressure circ. 2 Compressor fan AUTOMATIC (After 5 manual reset signals) E24 Fan thermal cut-out circ. 2 Compressor fan MANUAL E27 Probe fault BT5/BP5 Compressor fan AUTOMATIC E45 Configuration Compressor MANUAL 46

TROUBLESHOOTING The following provides indications on some possible anomalies and their corresponding solutions. The resulting operations are the full responsibility of the person performing them. An authorised technician possessing the legal requisites for each operation must be contacted to reset the operation of the unit. The activation of a safety device indicates an operating anomaly: before resetting the device, check and eliminate the causes of the anomaly. The following are possible problems and their corresponding causes and solutions. WARNING THE OPERATIONS SHOWN HERE ARE THE FULL RESPONSIBILITY OF THE PERSON PERFORMING THEM; AN AUTHORISED TECHNICIAN POSSESSING THE LEGAL REQUISITES FOR EACH OPERATION MUST BE CONTACTED TO RESET THE CORRESPONDING FUNCTION. All faults and anomalous operating conditions are handled by the main control module. When an anomalous condition or fault arises, the module, as well as placing the unit in safety mode, can display the event remotely. 47

ALARMS<br />

The alarm codes appear on the display of the use interface terminal when errors occur. If the alarms displayed feature<br />

automatic reset, they will disappear as soon as the problem has been resolved, while those with manual reset must be<br />

reset by a service engineer. The alarms appear on the user interface terminal following the sequence shown in Table. It<br />

should also be highlighted that if more than one alarm is active, only the first will be displayed, and when this is reset the<br />

second will appear, and so on until no more alarms are active.<br />

Note: in standby mode, or alternatively when the unit is OFF, the alarms are not signalled and the cumulative fault relay<br />

is not activated. The alarms, if present, are signalled and the cumulative fault relay is activated when the operating mode<br />

is selected.<br />

Table 2<br />

Codice Tipo di guasto Blocchi Ripristino<br />

E01 Max pressure circ. 1 Compressor MANUAL<br />

E02 Min pressure circ. 1 Compressor fan AUTOMATIC (After 5 manual reset signals)<br />

E03 Compressor 1 thermal Compressor fan MANUAL<br />

E04 Fan thermal cut-out circ. 1 Compressor fan MANUAL<br />

E07 Probe fault BT3/BP3 Compressor fan AUTOMATIC<br />

E21 Max pressure circ. 2 Compressor fan MANUAL<br />

E22* Min pressure circ. 2 Compressor fan AUTOMATIC (After 5 manual reset signals)<br />

E24 Fan thermal cut-out circ. 2 Compressor fan MANUAL<br />

E27 Probe fault BT5/BP5 Compressor fan AUTOMATIC<br />

E45 Configuration Compressor MANUAL<br />

46

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!