MSAT 102-122-142-162-182-202-242
MSAT 102-122-142-162-182-202-242
MSAT 102-122-142-162-182-202-242
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
COIL FAN CONTROLLER<br />
In the <strong>MSAT</strong> units, as standard the fan speed is controlled according to the temperature, with pressure-based control<br />
available upon request; the latter configuration is supplied in a kit. The operating principle described below is the same<br />
for both type of control.<br />
- FAN CONTROL IN COOLING<br />
The following graph shows operation in cooling mode, Fig. 6.<br />
EXTERNAL FAN IN COOL OPERATION<br />
Speed<br />
Prop. Cooling band F09<br />
Figure 6<br />
Temperature<br />
Pressure<br />
When the compressor is started, the fans are forced on, that is, the fans are not managed directly by the controller but<br />
rather are switched on for a set time at maximum speed, according to the value of a parameter, unless the temperature is<br />
below the CUT-OFF value; in this case, the fans are started at minimum speed for the same period. That being stated,<br />
we will now describe the operation of the controller.<br />
The first parameter to be defined is the CUT-OFF, which corresponds to a special condensing temperature value below<br />
which the fans are off. The CUT-OFF HYSTERESIS is a parameter that defines the field within which the fans switch<br />
from operation at minimum speed to off, and vice-versa. In summary, the fans start operating at minimum speed when<br />
the temperature is equal to the CUT-OFF + CUT-OFF HYSTERESIS, while they stop based on the difference between<br />
the COOLING set point and the CUT-OFF DELTA. When the condensing temperature exceeds the COOLING FAN SET<br />
POINT, the controller starts to control the speed of the fans proportionally to the condensing temperature. In the case of<br />
Clivet units, contrary to the operation described in the graph, the control functions are maintained until the MAX<br />
COOLING FAN SET POINT is reached. For completion, the description of the parameters MAX SILENT SPEED and<br />
COOLING PROPORTIONAL BAND are also described. The first defines a maximum fan speed threshold corresponding<br />
to a certain condensing temperature, below which the speed is controlled, while the PROPORTIONAL BAND defines the<br />
gradient of the straight line corresponding to the speed control function. The CLIVET units are designed to control the<br />
fans up to the maximum speed.<br />
43