CONTROL<br />

OPERATION OF THE MAIN MODULE<br />

COMPRESSOR ROTATION<br />

The processor also features other functions for the overall management of the unit. One example of this is compressor<br />

rotation. The compressor rotation function is enabled by setting the corresponding parameters. This means than when<br />

compressor operation is requested by the thermoregulator, the compressor that will start first is the one with the lowest<br />

number of operating hours, while the one that will stop first is the compressor with the highest number of hours. This<br />

function allows the number of operating hours to be divided evenly between both compressors. In any case, the first<br />

compressor can always be started first and the second compressor second, in the case of specific needs; the unit is<br />

delivered by the manufacturer with rotation enabled.<br />

COMPRESSOR TIMERS<br />

To maximise the quality of compressor operation, a number timers are required. Refer to the graph in Fig. 3-4 to better<br />

understand the meaning of the timers.<br />

Figure 3 Figure 4<br />

Comp. 1<br />

Compressor<br />

ON<br />

ON<br />

OFF<br />

Comp. 2<br />

Seconds<br />

ON<br />

OFF<br />

Seconds<br />

OFF<br />

ON-OFF safety time<br />

C01<br />

Seconds*10<br />

First-second compressor on interval<br />

C06<br />

First-second compressor off interval C07<br />

ON-ON safety time C02<br />

The graph in Fig. 4 shows two parameters. OFF-ON SAFETY TIME and ON-ON SAFETY TIME. The first parameter<br />

means that when a compressor stops a certain time must elapse before it can start again. This time is respected even<br />

when there is a request from the thermoregulator. The second parameter means that a certain time must elapse between<br />

two successive starts. In the case of units with two compressors, a further two parameters are used, that is, FIRST-<br />

SECOND COMPRESSOR ON INTERVAL and FIRST-SECOND COMPRESSOR OFF INTERVAL. The first parameter<br />

avoids simultaneous starts of the two compressors, mainly to avoid excessive current peaks. The second represents an<br />

interval between the shut-down of the first and the second compressor. The function of these two parameters are shown<br />

in the graph in Figure 3.<br />