ELECTRICAL CONNECTIONS<br />

IMPORTANT<br />

MAKE SURE THE UNIT IS NOT CONNECTED TO THE POWER SUPPLY BEFORE STARTING WORK ON ANY<br />

ELECTRICAL CONNECTIONS<br />

FUNCTIONAL CONNECTIONS<br />

The following devices will have to be connected up before the unit can be started:<br />

CONNECTION TO THE MAINS POWER<br />

- Connect the trhee-phase line to the terminals indicated on the electrical panel with L1 L2 L3 of the general cut-out<br />

switch.<br />

- Connect the NEUTRAL conductor to terminal N of the electrical panel.<br />

- Connect the EARTH conductor to the Pe terminal of the electrical panel.<br />

- The installer must take particular care in sizing the wires for connection to the mains power supply, taking into<br />

consideration the data on the unit’s technical datasheet sticker on the electrical panel door. It is also important to fit<br />

a short circuit protection device rated suitably for the power capacity of the line. The protection device must present<br />

appropriate breaking power in relation to the calculated short circuit current in that section of the system.<br />

ELECTRICAL DATA<br />

SIZE <strong>102</strong> <strong>122</strong> <strong>142</strong> <strong>162</strong> <strong>182</strong> <strong>202</strong> <strong>242</strong><br />

Single compressor 230/3/50 19.7 22.9 25.3 24.1 31.2 35.8 45.2<br />

(A) 400/3/50 9.8 11.3 13.6 14.7 17.5 20.0 25.2<br />

F.L.A. Fans (A) 230/1/50 1.15x2 1.15x2 0.65 x 4 0.65 x 4 0.65 x 4 0.65 x 6 0.65 x 6<br />

Total<br />

(A)<br />

230/3/50 41.6 48.1 53.9 51.4 65.6 76.4 85.8<br />

400/3/50 21.8 25.0 30.3 32.5 38.1 44.9 55.2<br />

L.R.A. Compressor (A)<br />

230/3/50 132.5 164 171 166 211 224 280<br />

400/3/50 66 74 <strong>102</strong> 94 117 128 159<br />

Compressor (kW) 11.3 13.2 15.2 16.8 20.7 23.8 29.2<br />

F.L.I. Fan (kW) 0.22x2 0.22x2 0.17 x 4 0.17 x 4 0.17 x 4 0.17 x 6 0.17 x 6<br />

Total (kW) 11.8 13.6 15.9 17.5 21.4 24.8 30.2<br />

M.IC. Total (A)<br />

230/3/50 154.5 189.2 199.5 193.3 244.9 264.6 329.5<br />

400/3/50 78.1 87.6 118.8 111.9 137.2 152.3 189.0<br />

1) F.L.A. Full Load Amperes.<br />

2) L.R.A. Compressor Locked Rotor Amperes.<br />

3) F.L.I. Full Load Input of compressor (at maximum rated operating conditions).<br />

4) M.I.C. Maximum Inrush Current of unit.<br />

Voltage unbalance: max 2%<br />

Voltage: 400/3/50 ± 6%<br />

230/3/50 ± 6%<br />

OPTIONAL CONNECTIONS<br />

CONNECTING AN ANOMALY SIGNAL DEVICE<br />

Referring to the electrical diagram, the summation shut-down signalling line can be equipped with an audible or visual<br />

alarm device to signal anomalies detected on the unit.<br />

The signalling device should be powered at low voltage (24V, 300mA) as per the wiring diagram.<br />

CONNECTION TO REMOTE CONTROL PANEL<br />

The remote control module is a faithful reproduction of the keypad on the ENERGY LIGHT control module and allows all<br />

the operations on the machine to be performed from a remote location.<br />