MSAT 102-122-142-162-182-202-242
MSAT 102-122-142-162-182-202-242
MSAT 102-122-142-162-182-202-242
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
DIMENSIONS AND WEIGHT DISTRIBUTION<br />
Key:<br />
1 - Compressor<br />
2 - Liquid line fitting dia. G1 first circuit<br />
2’ - Liquid line fitting dia. G1 second circuit<br />
3 - Gas line fitting dia. G2 first circuit<br />
3’ - Gas line fitting dia. G2 second circuit<br />
4 - Electrical panel<br />
5 - Helical fans<br />
6 - Electrical inlet<br />
7 - Condenser coil<br />
8 - Access to electrical panel and compressor<br />
DIMENSIONS<br />
WEIGHTS<br />
Size A B C D E F G H I L O dia. dia. no. of W1 W2 W3 W4 Tot.<br />
G1 G2 fans<br />
<strong>102</strong> 1530 678 1400 128 73 75 628 42 1255 800 - 14 22 2 88 42 95 50 275<br />
<strong>122</strong> 1530 678 1400 128 73 75 628 42 1255 800 - 16 28 2 89 42 98 51 280<br />
<strong>142</strong> 1563 1107 1570 128 130 75 1058 42 1077 900 153 16 28 4 121 58 132 69 380<br />
<strong>162</strong>/<strong>182</strong> 1563 1107 1570 128 130 75 1058 42 1077 900 153 18 28 4 155 74 168 88 485<br />
<strong>202</strong>/<strong>242</strong> 2098 1107 1570 128 130 75 1058 42 1612 900 153 22 35 6 191 95 200 104 590<br />
Note: The dimensions are expressed in mm, the weights in kg.<br />
PROTECTION AND CONTROL DEVICE SETTINGS<br />
Open Close<br />
High pressure switch (kPa) 2750 2000 Safety fuse plug ( °C ) 120<br />
Low pressure switch (kPa) 230 360 Max. compressor starts per hour ( n° ) 10<br />
Safety discharge thermostat ( °C ) 120<br />
Note:<br />
The “high pressure switch” and “safety<br />
discharge thermostat” safety devices can<br />
be manually reset by the control unit.<br />
The “low pressure switch” is<br />
automatically reset.<br />
SOUND LEVELS<br />
Sound power level (dB)<br />
Total<br />
sound<br />
press.<br />
Size<br />
Octave band (Hz)<br />
level<br />
63 125 250 500 1000 2000 4000 8000 dB(A)<br />
<strong>102</strong> 80 84 75 73 69 63 60 42 59<br />
<strong>122</strong> 80 76 73 73 71 65 62 43 59<br />
<strong>142</strong> 87 80 74 73 71 69 66 63 60<br />
<strong>162</strong> 87 81 76 73 70 69 65 62 60<br />
<strong>182</strong> 84 78 78 74 69 70 62 55 60<br />
<strong>202</strong> 86 79 78 77 72 67 62 54 61<br />
<strong>242</strong> 86 82 81 75 70 73 63 65 62<br />
Note:<br />
- The sound levels refer to units operating at full<br />
load with maximum fan speed, condenser air<br />
intake 35°C, saturated suction temperature + 5°C.<br />
- Sound pressure level at 1 metre from the external<br />
surface of the unit.<br />
- Sound power level ref.: 1x10 -12 w<br />
- Sound pressure level ref.: 2 x 10 -5 Pa<br />
35