MSAT 102-122-142-162-182-202-242
MSAT 102-122-142-162-182-202-242
MSAT 102-122-142-162-182-202-242
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
POSITIONING<br />
The units are designed for outdoor installation.<br />
• Check that the support surface can bear the weight of the unit (see weights and weight distribution on page 35) and that<br />
both are level.<br />
Place a layer of rubber between the base of the unit and the support (to prevent noise and vibrations).<br />
• Respect the functional clearances.<br />
• If the unit is installed on a balcony or on the roof, it should be placed on special antivibration mounts; in this case, the<br />
connection tubing must be fitted with elastic joints.<br />
• Position the unit so that the long sides are not facing prevailing wind.<br />
• Anchor the unit to the ground.<br />
FUNCTIONAL CLEARANCES<br />
The choice of the location of the unit is of fundamental importance for correct operation.<br />
Obstacles that block the flow of air (such as drains, hot air), difficulty in air circulation, leaves or other objects that may block<br />
the exchanger coils, winds that contrast or excessively assist the air flow, can cause operating anomalies or shut-down the<br />
machine.<br />
The unit requires minimum spaces for operation and maintenance.<br />
The following drawings show some types of installation; check on a case-by-case basis, keeping in mind the information<br />
provided in this manual.<br />
Note: The measurements are in mm<br />
Free side<br />
UNITS WITH INDEPENDENT CIRCUITS<br />
UNITS WITH SEPARATE COMPRESSOR CONTROL<br />
BASE ANTIVIBRATION MOUNTS<br />
(accessory)<br />
(accessory)<br />
The units can be supplied upon request with separate compressor control,<br />
fitted for connection to two distinct terminal units.<br />
The power supply is still shared in common.<br />
34