GENERAL TECHNICAL SPECIFICATIONS<br />

Model <strong>MSAT</strong> <strong>102</strong> <strong>122</strong> <strong>142</strong> <strong>162</strong> <strong>182</strong> <strong>202</strong> <strong>242</strong><br />

Standard voltage 400 / 3 / 50<br />

Model <strong>MSAT</strong> R-22<br />

Cooling capacity kW 31.3 36.4 41.3 48.7 53.8 63.9 77.9<br />

Compressor power input kW 8.5 10.3 11.3 13.5 15.8 17.5 22.3<br />

Model <strong>MSAT</strong> R-407C<br />

Cooling capacity kW 29.8 34.1 39.2 44.1 50.3 62.8 72.8<br />

Compressor power input kW 9.4 11.2 12.6 14.7 17.8 20.3 25.2<br />

The data refers to:<br />

Outside air temperature +35°C<br />

Saturated suction temperature<br />

(SST) 7.5°C R-22,<br />

(SST) 9.5°C (dew point) R-407C<br />

Compressor type<br />

SCROLL<br />

RPM rpm 2900<br />

Oil content<br />

L<br />

2x 2x 2x<br />

1,55 1,65 2,5<br />

Capacity steps 2<br />

Motor protection<br />

NTC<br />

2x<br />

4<br />

Type of oil<br />

SUNISO 3GS OIL<br />

Note: for units with R407C,<br />

type of oil<br />

- MOBIL EAL ARTIC 22 CC<br />

- 32 MMMA POE<br />

Condenser<br />

Material<br />

Copper pipes/aluminium fins<br />

Quantity 2<br />

Tot. front surf. m 2 3 3,6 4,9<br />

Fin spacing mm 1,6 2,1 1,6 1,6<br />

No. of rows 2<br />

Pipe dia. mm 9,52<br />

Test pressure kPa 3000<br />

Axial-flow fans<br />

No. and diameter no. x dia. 2x560 4x450 6x450<br />

RPM rpm 680 840<br />

Air flow-rate L/s 3056 4125 6120<br />

Rated power kW 2x0,22 4x0,16 6x0,16<br />

Freon connections<br />

Liquid valve ∅ 14 16 18 22<br />

Intake valve ∅ 22 28 28 35<br />

Refrigerant<br />

R-22 charge kg 8.2 8,2 9 9 9.6 12 12<br />

R-407C charge kg 9.2 9,2 10 10 10.6 13 13<br />

The data refers to:<br />

- Motor with external rotor<br />

- Safety grid<br />

Note:<br />

Welded fittings<br />

Note:<br />

Charge to be completed<br />

during start-up<br />

Weights and Volumes<br />

Approx. shipping weight kg 275 280 380 420 485 580 590<br />

Approx. packaging volume m 3 1,50 3,20 4,30<br />

Operating limits<br />

Max. condenser air R-22 49 47,5 47,5 47,5 45 49 46<br />

intake temp.<br />

SST = +5 °C R-407C 47 45 45 44,5 43,5 46 43<br />

Min. condenser air R-22 -4 -4 -4 -4 -8 -4 -8<br />

intake temp.<br />

SST = +5 °C<br />

R-407C -5 -5 -5 -5 -9 -5 -9<br />

Max. saturated gas R-22 12,5<br />

suction temperature °C R-407C 12,5<br />

Note:<br />

SST Saturated suction<br />

temperature<br />

Suction gas superheating<br />

+ 5°K<br />