9. Malfunctions and remedial measure faults<br />

Faults<br />

Fault display control unit<br />

High water floater 2+ high water<br />

sensor<br />

Water level in the aeration chamber<br />

has exceeded maximum level.<br />

Danger of plant overflowing.<br />

Causes<br />

- Level set too low<br />

- Feed quantity too high<br />

- Clear water syphon defective or<br />

clogged<br />

- Water cannot drain off.<br />

Backup<br />

Elimination<br />

- Setting to 150 cm<br />

- Checking the plant's feed quantities<br />

- Checking the clear water syphon's<br />

hydraulic performance<br />

and cleaning it if necessary<br />

- Providing free drainage in the<br />

sampling duct.<br />

Low water sensor:<br />

Water level in the aeration chamber<br />

has dropped below the minimum<br />

level.<br />

- Level set too high<br />

- Plant not sufficiently filled after<br />

maintenance<br />

- Tank leaky<br />

- Setting to 80 cm<br />

- Filling the plant with 1.20 m of<br />

water<br />

- Sealing the tank<br />

Excess pressure:<br />

Exceeding the maximum<br />

set pressure of the<br />

pressure monitoring system<br />

- Pressure set too low<br />

- Compressor builds up excessive<br />

backpressure:<br />

- Valve block does not switch<br />

- Vent hose is kinked<br />

- Air syphons are clogged<br />

- Aerator spark plug is clogged<br />

- Setting to 350 mbar<br />

- Checking and if necessary replacing<br />

the valve block<br />

- Removing any kinks<br />

- Cleaning the air syphons<br />

- Cleaning the aerator spark plug<br />

Negative pressure:<br />

Falling below the maximum set<br />

pressure of the pressure monitoring<br />

system<br />

- Pressure is set too high<br />

- Compressor does not work or<br />

works only inadequately<br />

- Leak inside the <strong>INNO</strong>-CLEAN ®<br />

system<br />

- Setting to 10 mbar<br />

- Checking the compressor's<br />

efficiency (see chapter<br />

"Maintenance")<br />

- Checking all connections and<br />

hoses for possible leakages<br />

Overcurrent<br />

(Current consumption too high)<br />

- Value set too low<br />

- Defect on the compressor<br />

- Setting to 2.0 A<br />

- Replacing the electrical components<br />

and if necessary testing by<br />

a qualified electrician<br />

Undercurrent<br />

(Current consumption too low)<br />

- Value set too high<br />

- Compressor does not switch on<br />

- Defective<br />

- Internal microfuse in<br />

control unit (3.15 A) has tripped<br />

- Setting to 0.1 A<br />

- Checking the compressor's<br />

mains connection on the control<br />

unit<br />

- Replacement/ fuse<br />

Battery voltage too low<br />

- Battery defective or service life<br />

exceeded<br />

- Replacement battery<br />