Perform the assembly without mechanical stresses acting on the pump.<br />

Avoid the installation in misaligned pipe work.<br />

Install the pump with horizontal motor shaft axis (fig. A).<br />

The direction of the water flow is indicated by the arrow on the pump<br />

body, as shown in fig. B.<br />

The motor body can be rotated in the positions shown in figure C.<br />

Pay utmost care to prevent people from getting in contact with the<br />

hot surfaces of the pump.<br />

Rotate the motor body after having loosened the screws (fig. D).<br />

CAuTION!<br />

3.2 electric connection<br />

Pay attention not to damage the seal of the pump body.<br />

The electric connection has to be performed by a qualified electrician in compliance<br />

with the national regulations. follow the safety regulations.<br />

The connection to the mains must be carried out in compliance with<br />

the standards incorporating in the fixing wiring a disconnection device<br />

from the supply mains having a contact separation in all poles that<br />

provide full disconnection under overvoltage category III conditions.<br />

All electric information concerning the circulation pump is born on the<br />

signaling plate.<br />

The connection cord must be laid in such a way as it cannot come in<br />

contact with the hosing or the motor body. In case of use of the pump<br />

with fluids at a temperature higher than 70 °C, use a connection cord resistant to<br />

high temperatures.<br />

Connect the power supply conductors to the terminals according to the diagram<br />

given in fig. F.<br />

Insert the terminal board (fig. G) in the proper seat (fig. H), connecting the red wire<br />

with letter N and the blue wire with letter L. Screw the two screws (fig. I) and tighten<br />

the sealing nuts (fig. L) to the fairlead.<br />

The pump belongs to class II and therefore grounding is not necessary.<br />

The pump does not require any external protection of the motor.<br />

Compare the frequency and the voltage of the mains with the rating data.<br />

17