11.2 Extended storage<br />

During extended storage in environments where the ambient temperature is –15 to +30 °C (+5 to +86 °F),<br />

charge the <strong>UPS</strong>’s battery every 6 months.<br />

During extended storage in environments where the ambient temperature is +30 to +45 °C<br />

(+86 to +113 °F), charge the <strong>UPS</strong>’s battery every 3 months.<br />

12. Specifications<br />

280 VA 420 VA 650 VA 1000 VA 1400 VA<br />

Acceptable input voltage 0 - 160 VAC<br />

Input voltage (on-line operation) 92-150 VAC<br />

Output voltage 103-132 VAC<br />

Nominal input frequency 50 or 60 Hz, autosensing<br />

Input Protection Resettable circuit breaker<br />

Frequency limits (on-line operation) 50 or 60 Hz, ±5%<br />

Transfer time 2 ms typical, 4 ms maximum<br />

Maximum load<br />

280 VA 180<br />

W<br />

420 VA 260<br />

W<br />

650 VA<br />

410 W<br />

1000 VA 670<br />

W<br />

On-battery output voltage 115 VAC<br />

On-battery frequency 50 or 60 Hz, ±0.1 Hz<br />

On-battery waveshape Stepped sine-wave Trapezoid<br />

1400 VA 950<br />

W<br />

Protection Overcurrent and short-circuit protected, latching shutdown on overload.<br />

Surge energy rating (one time, 10/1000 µs<br />

waveform)<br />

Surge current capability (one time, 8/20 µs<br />

waveform)<br />

Surge response time<br />

Surge voltage let-through (percentage of<br />

applied ANSI C62.41 Cat. A ±6 kV test<br />

waveform)<br />

320 J<br />

13kAmps maximum<br />

0 ns (instantaneous) normal mode;<br />