Phoenix_PowerSupply_QuintPS100_install_D602

Phoenix_PowerSupply_QuintPS100_install_D602 Phoenix_PowerSupply_QuintPS100_install_D602

wolff.carolin37
from wolff.carolin37 More from this publisher
27.06.2013 Views

Stromversorgungen / Power Supplies Alimentations stabilisées / Fuentes de alimentación QUINT POWER 13 14 DC OK + + – – DC 13 14 OK Output DC 24V 10A + + – – DC OK Adjust 22.5-28.5V Input AC 100-240V L N 5 QUINT POWER - die Universelle - the universal model - l’alimentation universelle - la universal AC 100-240V STEP POWER - die Flache - the low-profile model - la version basse - la baja DEUTSCH ENGLISH FRANÇAIS ESPAÑOL 2 POWER OVERLOAD PROTECTION DC 5 6 7 8 IN 100-240 V AC L(+) NC NC N(-) L NC NC N MINI POWER - die Schmale - the slim model - la version étroite - la estrecha 4.5-5.5 V DC DC OK MINI-PS-100-240AC/5DC/3 Power Supply INPUT OUTPUT AC: 100-240V 5V DC 50-60Hz ±1% Range: 3A 85-264V 0.4-0.2A DC: 90-350V 0.4-0.2A MINI POWER – – + + OUT 5 V DC Weitere Informationen zum Thema Stromversorgungen erhalten Sie unter: Further information on the subject of power supply units can be found at: Vous trouverez d’autres renseignements sur les alimentations en consultant notre site: Más información sobre el tema de las fuentes de alimentación se encuentra bajo: www.interface.phoenixcontact.com Phoenix Contact GmbH & Co. KG D-32823 Blomberg, Germany Fax +49-(0)5235-330999 Tel. +49-(0)5235-300 www.phoenixcontact.com Inhaltsverzeichnis Seite 1. QUINT POWER ........................................................................................ 4 2. Geräteansicht, -anschlüsse, -bedienungselemente ............................... 3/4 3. Sicherheits- und Warnhinweise ................................................................ 4 4. Installation 4.1. Montage.................................................................................................. 5 4.2. Anschluss .............................................................................................. 6 4.3. Signalisierung ........................................................................................ 8 5. Funktion .................................................................................................... 9 6. Technische Daten ................................................................................... 11 Table of Contents Page 1. QUINT POWER ...................................................................................... 14 2. View of the device, equipment connections and operating elements ... 3/14 3. Safety and warning notes ........................................................................ 14 4. Installation 4.1. Assembly .............................................................................................. 15 4.2. Connection ........................................................................................... 16 4.3. Signaling .............................................................................................. 18 5. Function .................................................................................................. 19 6. Technical Data ........................................................................................ 21 Sommaire Page 1. QUINT POWER vous offre ...................................................................... 24 2. Vue du module, éléments de connexion et de commande................... 3/24 3. Conseils de sécurité et avertissements ................................................... 24 4. Installation 4.1. Montage................................................................................................ 25 4.2. Raccordement ..................................................................................... 26 4.3. Signalisation ........................................................................................ 28 5. Fonctionnement ...................................................................................... 29 6. Caractéristiques techniques .................................................................... 31 Indice Página 1. QUINT POWER ...................................................................................... 34 2. Vista del módulo, conexiones, elementos de operación ...................... 3/34 3. Indicaciones de seguridad y advertencias............................................... 34 4. Instalación 4.1. Montaje ................................................................................................. 35 4.2. Conexión .............................................................................................. 36 4.3. Señalización ........................................................................................ 38 5. Función ................................................................................................... 39 6. Datos técnicos ......................................................................................... 41 Read installation instructions before connecting to mains www.interface.phoenixcontact.com LISTED CONTROL EQUIPMENT 43KA TECHNOLOGY EQUIPMENT TEMPERATURE - 25 … + 60 °C - 13 … + 140 °F APPROVALS U INDUSTRIAL u INFORMATION –25 Order No.: 29 38 71 4 Phoenix Contact GmbH & Co. KG D-32823 Blomberg, Germany Fax +49-(0)5235-330999, Tel. +49-(0)5235-300 www.interface.phoenixcontact.com TNR 9011670-00 / 06.2002 D GB F E Primär getaktete Stromversorgung für den universellen Einsatz Primary Switch-Mode Power Supply for universal use Alimentation à découpage primaire pour une utilisation universelle Fuente de alimentación de primario conmutado para empleo a escala mundial QUINT-PS-100-240AC/24DC/10 QUINT POWER 13 14 DC OK + + – – DC 13 14 OK Output DC 24V 10A + + – – DC OK Adjust 22.5-28.5V Input AC 100-240V L N 5 QUINT-PS-100-240AC/24DC/10 3 4 DC 13 14 OK CONTROL EQUIPMENT 43KA U INDUSTRIAL F LISTED Output DC 24V 10A –25 B EN 60950 EN 60204 EN 61558-2-17 EN 61000-6-2 EN 50081-1 - 25 … + 60 °C - 13 … + 140 °F APPROVALS Read installation instructions before connecting to mains www.interface.phoenixcontact.com Blockschaltbild / Block Diagram / Diagramme schématique / Esquema de conjunto 1 3 L (+) N (–) PE 13 14 DC OK + + – – DC 13 14 OK Output DCC 224V 10A 2 1 + + – – – DC active QUINT POWER PFC 13 14 DC OK + + – – + + – – DC OK Adjust 22.5-28.5V Input AC 100-240V L N 5 Art.-Nr.: 29 38 60 4 7 DC OK 13 14 6 5 Abb. 1 2 3 4

Stromversorgungen / Power Supplies<br />

Alimentations stabilisées / Fuentes de alimentación<br />

QUINT POWER<br />

13 14 DC<br />

OK + + – –<br />

DC<br />

13 14 OK<br />

Output DC 24V 10A<br />

+ + – –<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Input<br />

AC 100-240V<br />

L N 5<br />

QUINT POWER<br />

- die Universelle<br />

- the universal model<br />

- l’alimentation universelle<br />

- la universal<br />

AC 100-240V<br />

STEP POWER<br />

- die Flache<br />

- the low-profile model<br />

- la version basse<br />

- la baja<br />

DEUTSCH<br />

ENGLISH<br />

FRANÇAIS<br />

ESPAÑOL<br />

2<br />

POWER<br />

OVERLOAD<br />

PROTECTION<br />

DC<br />

5 6 7 8<br />

IN 100-240 V AC<br />

L(+) NC NC N(-)<br />

L NC NC N<br />

MINI POWER<br />

- die Schmale<br />

- the slim model<br />

- la version étroite<br />

- la estrecha<br />

4.5-5.5<br />

V DC<br />

DC<br />

OK<br />

MINI-PS-100-240AC/5DC/3<br />

Power Supply<br />

INPUT OUTPUT<br />

AC:<br />

100-240V 5V DC<br />

50-60Hz ±1%<br />

Range: 3A<br />

85-264V<br />

0.4-0.2A<br />

DC:<br />

90-350V<br />

0.4-0.2A<br />

MINI POWER<br />

– – + +<br />

OUT 5 V DC<br />

Weitere Informationen zum Thema<br />

Stromversorgungen erhalten Sie unter:<br />

Further information on the subject of<br />

power supply units can be found at:<br />

Vous trouverez d’autres renseignements<br />

sur les alimentations en consultant notre<br />

site:<br />

Más información sobre el tema de las<br />

fuentes de alimentación se encuentra<br />

bajo:<br />

www.interface.phoenixcontact.com<br />

<strong>Phoenix</strong> Contact GmbH & Co. KG<br />

D-32823 Blomberg, Germany<br />

Fax +49-(0)5235-330999 Tel. +49-(0)5235-300<br />

www.phoenixcontact.com<br />

Inhaltsverzeichnis Seite<br />

1. QUINT POWER ........................................................................................ 4<br />

2. Geräteansicht, -anschlüsse, -bedienungselemente ............................... 3/4<br />

3. Sicherheits- und Warnhinweise ................................................................ 4<br />

4. Installation<br />

4.1. Montage.................................................................................................. 5<br />

4.2. Anschluss .............................................................................................. 6<br />

4.3. Signalisierung ........................................................................................ 8<br />

5. Funktion .................................................................................................... 9<br />

6. Technische Daten ................................................................................... 11<br />

Table of Contents Page<br />

1. QUINT POWER ...................................................................................... 14<br />

2. View of the device, equipment connections and operating elements ... 3/14<br />

3. Safety and warning notes ........................................................................ 14<br />

4. Installation<br />

4.1. Assembly .............................................................................................. 15<br />

4.2. Connection ........................................................................................... 16<br />

4.3. Signaling .............................................................................................. 18<br />

5. Function .................................................................................................. 19<br />

6. Technical Data ........................................................................................ 21<br />

Sommaire Page<br />

1. QUINT POWER vous offre ...................................................................... 24<br />

2. Vue du module, éléments de connexion et de commande................... 3/24<br />

3. Conseils de sécurité et avertissements ................................................... 24<br />

4. Installation<br />

4.1. Montage................................................................................................ 25<br />

4.2. Raccordement ..................................................................................... 26<br />

4.3. Signalisation ........................................................................................ 28<br />

5. Fonctionnement ...................................................................................... 29<br />

6. Caractéristiques techniques .................................................................... 31<br />

Indice Página<br />

1. QUINT POWER ...................................................................................... 34<br />

2. Vista del módulo, conexiones, elementos de operación ...................... 3/34<br />

3. Indicaciones de seguridad y advertencias............................................... 34<br />

4. Instalación<br />

4.1. Montaje ................................................................................................. 35<br />

4.2. Conexión .............................................................................................. 36<br />

4.3. Señalización ........................................................................................ 38<br />

5. Función ................................................................................................... 39<br />

6. Datos técnicos ......................................................................................... 41<br />

Read <strong>install</strong>ation instructions<br />

before connecting to mains<br />

www.interface.phoenixcontact.com<br />

LISTED<br />

CONTROL<br />

EQUIPMENT<br />

43KA<br />

TECHNOLOGY<br />

EQUIPMENT<br />

TEMPERATURE - 25 … + 60 °C<br />

- 13 … + 140 °F<br />

APPROVALS<br />

U INDUSTRIAL<br />

u INFORMATION<br />

–25<br />

Order No.: 29 38 71 4<br />

<strong>Phoenix</strong> Contact GmbH & Co. KG<br />

D-32823 Blomberg, Germany<br />

Fax +49-(0)5235-330999, Tel. +49-(0)5235-300<br />

www.interface.phoenixcontact.com<br />

TNR 9011670-00 / 06.2002<br />

D<br />

GB<br />

F<br />

E<br />

Primär getaktete Stromversorgung<br />

für den universellen Einsatz<br />

Primary Switch-Mode Power Supply<br />

for universal use<br />

Alimentation à découpage primaire<br />

pour une utilisation universelle<br />

Fuente de alimentación de primario conmutado<br />

para empleo a escala mundial<br />

QUINT-PS-100-240AC/24DC/10<br />

QUINT POWER<br />

13 14 DC<br />

OK<br />

+ + – –<br />

DC<br />

13 14 OK<br />

Output DC 24V 10A<br />

+ + – –<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Input<br />

AC 100-240V<br />

L N 5<br />

QUINT-PS-100-240AC/24DC/10<br />

3<br />

4<br />

DC<br />

13 14 OK<br />

CONTROL<br />

EQUIPMENT<br />

43KA<br />

U INDUSTRIAL<br />

F<br />

LISTED<br />

Output DC 24V 10A<br />

–25<br />

B<br />

EN 60950<br />

EN 60204<br />

EN 61558-2-17<br />

EN 61000-6-2<br />

EN 50081-1<br />

- 25 … + 60 °C<br />

- 13 … + 140 °F<br />

APPROVALS<br />

Read <strong>install</strong>ation instructions<br />

before connecting to mains www.interface.phoenixcontact.com<br />

Blockschaltbild / Block Diagram / Diagramme schématique /<br />

Esquema de conjunto<br />

1<br />

3<br />

L (+)<br />

N (–)<br />

PE<br />

13 14 DC<br />

OK<br />

+ + – –<br />

DC<br />

13 14 OK<br />

Output DCC 224V<br />

10A<br />

2<br />

1<br />

+ + – – –<br />

DC<br />

active<br />

QUINT POWER<br />

PFC<br />

13 14 DC<br />

OK + + – –<br />

+ + – –<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Input<br />

AC 100-240V<br />

L N 5<br />

Art.-Nr.: 29 38 60 4<br />

7<br />

DC OK<br />

13<br />

14<br />

6<br />

5<br />

Abb. 1<br />

2<br />

3<br />

4


Stromversorgung - primär getaktet für den universellen Einsatz<br />

QUINT-PS-100-240AC/24DC/10<br />

Artikelnr.: 29 38 60 4<br />

1. QUINT POWER bietet Ihnen:<br />

• Weltweiten Einsatz durch Weitbereichseingang<br />

• Hohe Betriebssicherheit auch an schwierigen globalen Netzen<br />

• POWER BOOST - Leistungsreserve für schwierige Lasten<br />

• Präventive Funktionsüberwachung durch professionelle Signalisierung<br />

2. Geräteansicht, -anschlüsse, -bedienungselemente nach Abb. 1:<br />

1 AC-Eingang:<br />

Eingangsspannung<br />

85-264 V AC<br />

Frequenz 45-65 Hz<br />

(0,2 mm 2 bis 2,5 mm 2 starr)<br />

(0,2 mm 2 bis 2,5 mm 2 flexibel)<br />

(AWG 24-12)<br />

Interne Sicherung 6,3 AT<br />

Empfohlene Vorsicherung<br />

10 A oder 16 A LS/<br />

Charakteristik B<br />

3. Sicherheits- und Warnhinweise<br />

Um einen sicheren Betrieb des Gerätes zu gewährleisten und alle Funktionen<br />

nutzen zu können, lesen Sie diese Anleitung bitte vollständig durch!<br />

QUINT POWER sind Einbaugeräte. Die Installation und Inbetriebnahme darf nur von<br />

entsprechend qualifiziertem Fachpersonal durchgeführt werden. Dabei sind die jeweiligen<br />

landesspezifischen Vorschriften (z.B. VDE, DIN) einzuhalten.<br />

Insbesondere ist vor der Inbetriebnahme sicherzustellen, dass<br />

• der Netzanschluss fachgerecht ausgeführt und der Schutz gegen elektrischen Schlag<br />

sichergestellt ist!<br />

• das Gerät nach den Bestimmungen der EN 60950 außerhalb der Stromversorgung<br />

spannungslos schaltbar ist (z.B. durch den primärseitigen Leitungsschutz)!<br />

• der Schutzleiter angeschlossen ist!<br />

• alle Zuleitungen ausreichend abgesichert und dimensioniert sind!<br />

• alle Ausgangsleitungen dem max. Ausgangstrom des Gerätes entsprechend<br />

dimensioniert oder gesondert abgesichert sind!<br />

• ausreichend Konvektion gewährleistet ist!<br />

Je nach Umgebungstemperatur und Belastung des Gerätes kann die<br />

Gehäusetemperatur hohe Werte annehmen!<br />

Im Gerät befinden sich Bauelemente mit lebensgefährlicher Spannung<br />

und hoher gespeicherter Energie!<br />

4<br />

DEUTSCH<br />

2 DC-Ausgang:<br />

Ausgangsspannung<br />

24 V DC (voreingestellt),<br />

von 22,5 - 28,5 V DC einstellbar<br />

über Potentiometer 5<br />

(0,2 mm 2 bis 2,5 mm 2 starr)<br />

(0,2 mm 2 bis 2,5 mm 2 flexibel)<br />

(AWG 24-12)<br />

Das Gerät ist leerlauf- und<br />

kurzschlussfest.<br />

Vorsicht: Niemals bei anliegender Spannung arbeiten!<br />

Lebensgefahr!<br />

4.1.2. Schmale Einbaulage<br />

Das Gerät wird ab Werk für eine schmale<br />

Einbaulage ausgeliefert.<br />

Montage:<br />

6<br />

Setzen Sie das Modul mit der<br />

Tragschienenführung an die Oberkante<br />

der Tragschiene an und rasten<br />

Sie es nach unten ein (Abb. 4a).<br />

Demontage: Ziehen Sie den Schnappriegel mit<br />

Hilfe eines Schraubendrehers auf<br />

und hängen das Modul an der Unterkante<br />

der Tragschiene aus (Abb. 4b).<br />

3 DC OK-Ausgang aktiv<br />

44 DC OK-Ausgang<br />

potentialfrei<br />

5 Potentiometer (abgedeckt)<br />

22,5 - 28,5 V DC<br />

6 DC OK-Kontrollleuchte<br />

77 Universal-Tragschienen-<br />

Adapter UTA 107<br />

4.1.3. Flache Einbaulage<br />

Eine flache Einbaulage erreichen Sie durch Montage 90 ° zur Tragschiene.<br />

Montieren Sie dazu den Tragschienenadapter (UTA 107) 7 wie in Abb. 5 beschrieben<br />

(Befestigungsschrauben Torx T10, Anzugsmoment 0,8 - 0,9 Nm).<br />

Hierzu ist kein weiteres Montagematerial erforderlich.<br />

4.2. Anschluss<br />

Netzformen: 100-240 V AC-Netze<br />

TN-S-Netz TN-C-Netz TT-Netz<br />

L N PE<br />

QUINT<br />

+ –<br />

L<br />

N<br />

PE<br />

L N PE<br />

QUINT<br />

+ –<br />

L<br />

PEN<br />

L N PE<br />

QUINT<br />

+ –<br />

Abb. 6a Abb. 6b Abb. 6c<br />

L<br />

N<br />

Abb. 4a<br />

Abb. 4b<br />

Abb. 5<br />

4. Installation<br />

4.1. Montage<br />

Die Stromversorgung ist auf alle Tragschienen<br />

nach EN 50022-35 aufrastbar und soll waagerecht<br />

erfolgen (Eingangsklemmen unten).<br />

4.1.1. Einbaumaße<br />

290<br />

Um eine ausreichende Konvektion<br />

zu gewährleisten, empfehlen wir<br />

den folgenden Mindestabstand zu<br />

anderen Modulen:<br />

8,0 cm in vertikaler Richtung und<br />

1,5 cm in horizontaler Richtung.<br />

Schmale Einbaulage:<br />

Einbautiefe 125 mm (+ Tragschiene)<br />

145<br />

80<br />

15<br />

QUINT POWER<br />

115 15 15 152<br />

85 122<br />

DC<br />

13 14 OK + + – –<br />

Output DC 24V 10A<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Input<br />

AC 100-240V<br />

L N 5<br />

QUINT POWER<br />

13 14 DC<br />

OK<br />

+ + – –<br />

DC<br />

13 14 OK<br />

Output DC 24V 10A<br />

+ + – –<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Input<br />

AC 100-240V<br />

L N 5<br />

- 25 … + 60 °C<br />

- 13 … + 140 °F<br />

APPROVALS<br />

Read <strong>install</strong>ation instructions<br />

before connecting to mains www.interface.phoenixcontact.com<br />

U INDUSTRIAL<br />

F<br />

LISTED<br />

–25<br />

B<br />

CONTROL<br />

EQUIPMENT<br />

43KA<br />

EN 60950<br />

EN 60204<br />

EN 61558-2-17<br />

EN 61000-6-2<br />

EN 50081-1<br />

Abb. 2<br />

Flache Einbaulage:<br />

Einbautiefe 1) 103 mm (+ Tragschiene)<br />

1) (inkl. 15 mm Konvektionsabstand)<br />

15<br />

130<br />

Abb. 3<br />

4.2.1. Verbindungskabel:<br />

Das Gerät ist mit COMBICON-Steckverbindern ausgerüstet. Diese zuverlässige und<br />

montagefreundliche Verbindungsart ermöglicht einen schnellen Geräteanschluss und<br />

eine sichtbare Trennung der elektrischen Verbindung im Bedarfsfall.<br />

Steckverbinder nur leistungslos betätigen!<br />

Sie können folgende Kabelquerschnitte anschließen:<br />

Starr [mm 2 ] Flexibel [mm 2 ] AWG Anzugsmoment [Nm]<br />

1 Eingang: 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />

22 Ausgang: 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />

4 Signal: 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />

Für zuverlässigen und berührsicheren Anschluss:<br />

• Isolieren Sie die Anschlussenden 8 mm ab<br />

(siehe Abb. 7)!<br />

4.2.2. Eingang (Abb.8)<br />

Der 100-240 V-AC Anschluss erfolgt über die<br />

Schraubverbindungen L, N und 5 .<br />

Absicherung der Primärseite<br />

Die Installation des Gerätes muss entsprechend den<br />

Bestimmungen der EN 60 950 erfolgen. Das Gerät<br />

muss über eine geeignete Trennvorrichtung außerhalb<br />

der Stromversorgung spannungslos schaltbar<br />

sein. Hierzu eignet sich z.B. der primärseitige Leitungsschutz.<br />

Ein weiterer Geräteschutz ist nicht erforderlich, da<br />

eine interne Sicherung vorhanden ist.<br />

Empfohlene Vorsicherung:<br />

Leitungsschutzschalter 10 A oder 16 A, Charakteristik B (oder funktionsgleich).<br />

Bei DC-Anwendungen ist eine geeignete Sicherung vorzuschalten!<br />

Löst die interne Sicherung aus, liegt mit<br />

hoher Wahrscheinlichkeit ein Gerätedefekt<br />

vor.<br />

In dem Fall ist eine Überprüfung des<br />

Gerätes im Werk erforderlich!<br />

4.2.3. Ausgang (Abb.9)<br />

Der 24 V DC-Anschluss erfolgt über die Schraubverbindungen<br />

"+" und "–" am Schraubanschluss 22 .<br />

Die eingestellte Ausgangsspannung beträgt bei Auslieferung<br />

24 V DC. Am Potentiometer 55 ist die Ausgangsspannung<br />

von 22,5 bis 28,5 V DC einstellbar.<br />

8 mm<br />

Input<br />

AC 100-240V<br />

L N 5<br />

4 3<br />

13 14 DC<br />

OK<br />

+ + – –<br />

DC<br />

13 14 OK<br />

Output DC 24V 10A<br />

+ + – –<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Abb. 7<br />

Abb. 8<br />

2<br />

5<br />

Abb. 9<br />

5<br />

7


Absicherung der Sekundärseite:<br />

Das Gerät ist elektronisch kurzschluss- und leerlauffest. Die Ausgangsspannung wird im<br />

Fehlerfall auf maximal 35 V DC begrenzt.<br />

Es ist sicherzustellen, dass alle Ausgangsleitungen dem maximalen Ausgangsstrom entsprechend<br />

dimensioniert oder gesondert abgesichert sind.<br />

Die sekundärseitigen Kabel sollten große Querschnitte haben, um die Spannungsfälle<br />

auf den Leitungen so klein wie möglich zu halten.<br />

4.3. Signalisierung<br />

Die beiden DC OK-Ausgänge dienen der präventiven Funktionsüberwachung der Stromversorgung.<br />

Es steht ein potentialfreier Signalkontakt 4 und ein aktives DC OK-Signal 3<br />

zur Verfügung. Zusätzlich ermöglicht die DC OK-LED 6 eine Funktionsauswertung der<br />

Stromversorgung direkt am Einsatzort.<br />

4.3.1. Potentialfreier Kontakt (Abb.10)<br />

Der potentialfreie Signalkontakt meldet durch Öffnen eine<br />

Unterschreitung der eingestellten Ausgangsspannung um<br />

mehr als 10 %. Es können Signale und ohmsche Lasten bis<br />

max. 30 V und Ströme von max. 1 A geschaltet werden.<br />

Bei stark induktiven Lasten wie z.B. einem Relais ist eine<br />

geeignete Schutzbeschaltung (z.B. Freilaufdiode) erforderlich.<br />

4.3.2. Aktiver Signalausgang (Abb.11)<br />

Das 24 V DC-Signal liegt zwischen den Anschlussklemmen<br />

"DC OK" und "–" an und kann bis zu 40 mA belastet werden.<br />

Dieser Signalausgang meldet durch Wechsel von "aktiv<br />

high" auf "low" eine Unterschreitung der eingestellten Ausgangsspannung<br />

um mehr als 10 %.<br />

Das DC OK-Signal ist vom Power-Ausgang entkoppelt. Somit<br />

ist eine Fremdeinspeisung durch parallelgeschaltete Geräte<br />

ausgeschlossen.<br />

Das 24 V DC-Signal kann zur Auswertung direkt an einen Logikeingang angeschlossen<br />

werden.<br />

4.3.3. Signalschleife (Abb.12)<br />

Die beiden vorher genannten Signalausgänge lassen sich auf einfache<br />

Weise kombinieren.<br />

Beispiel: Überwachung von zwei Geräten.<br />

Nutzen Sie den aktiven Meldeausgang vom Gerät<br />

1 und schleifen Sie den potentialfreien Meldeausgang<br />

von Gerät 2 ein. Bei Funktionsstörung<br />

erhalten Sie eine Sammelstörmeldung. Es<br />

können beliebig viele Geräte eingeschleift werden.<br />

Diese Signalkombination spart Verdrahtungskosten<br />

und Logikeingänge.<br />

8<br />

10<br />

24 V DC<br />

40 mA<br />

13 14<br />

Output 24V DC<br />

DC OK<br />

+ + – –<br />

DC OK<br />

max.<br />

30 VAC/DC, 1 A Abb. 10<br />

13 14<br />

24 V DC<br />

40 mA<br />

Output 24V DC<br />

DC OK<br />

Gerät 1<br />

Output 24V DC<br />

13 14<br />

DC OK<br />

+ + – –<br />

DC OK<br />

+ + – –<br />

DC OK<br />

Abb. 11<br />

Gerät 2<br />

Outpu<br />

13 14<br />

DC OK<br />

Abb. 12<br />

5.3. Parallelbetrieb<br />

Typgleiche Geräte können sowohl zur Redundanz als auch zur Leistungserhöhung<br />

parallelgeschaltet werden. Im Lieferzustand ist dazu kein weiterer Abgleich erforderlich.<br />

Wird eine Justierung der Ausgangsspannung durchgeführt, so wird eine gleichmäßige<br />

Stromaufteilung durch eine exakte Einstellung sämtlicher parallel betriebener Stromversorgungen<br />

auf eine gleiche Ausgangsspannung gewährleistet.<br />

Für eine symmetrische Stromaufteilung empfehlen wir, alle Kabelverbindungen von der<br />

Stromversorgung zu einer Sammelschiene in gleicher Länge und mit gleichem Leiterquerschnitt<br />

auszuführen!<br />

Systembedingt sollte bei der Parallelschaltung von mehr als zwei Stromversorgungen<br />

eine Schutzbeschaltung an jedem einzelnen Geräteausgang <strong>install</strong>iert werden (z.B. Entkoppeldiode<br />

oder DC-Sicherung). Somit werden bei einem sekundären Gerätedefekt<br />

hohe rückwärtsgespeiste Ströme vermieden.<br />

5.3.1. Redundanzbetrieb (Abb. 15)<br />

Redundante Schaltungen eignen sich zur Versorgung<br />

von Anlagen, die besonders hohe Anforderungen an<br />

die Betriebssicherheit stellen. Kommt es im Primärkreis<br />

der ersten Stromversorgung zu einem Defekt, so<br />

übernimmt automatisch das zweite Gerät unterbrechungsfrei<br />

die vollständige Stromversorgung und umgekehrt.<br />

Zu diesem Zweck werden die parallel zu schaltenden<br />

Stromversorgungen so dimensioniert, dass der Gesamtstrombedarf<br />

aller Verbraucher von einer Stromversorgung<br />

vollständig abgedeckt werden kann.<br />

100 % Redundanz erfordert externe Entkoppeldioden!<br />

5.3.2. Leistungserhöhung (Abb. 16)<br />

Bei n parallel geschalteten Geräten kann der Ausgangsstrom<br />

auf n x I N erhöht werden.<br />

Die Parallelschaltung zur Leistungserhöhung findet ihren<br />

Einsatz bei der Erweiterung bestehender Anlagen.<br />

Es wird eine Parallelschaltung empfohlen, wenn die<br />

Stromversorgung nicht den Strombedarf des leistungsstärksten<br />

Verbrauchers abdeckt. Ansonsten sollten die<br />

Verbraucher auf voneinander unabhängige<br />

Einzelgeräte aufgeteilt werden.<br />

Es können maximal fünf Geräte parallelgeschaltet werden!<br />

QUINT QUINT<br />

10 A + – 10 A + –<br />

+<br />

–<br />

+ –<br />

Σ = 10 A<br />

Abb. 15<br />

QUINT QUINT<br />

10 A + – 10 A + –<br />

+<br />

–<br />

+ –<br />

Σ = 20 A<br />

Abb. 16<br />

4.3.4. DC OK-LED<br />

Die grüne DC OK-LED ermöglicht eine Funktionsauswertung vor Ort am Schaltschrank.<br />

LED leuchtet Normaler Betrieb der Stromversorgung<br />

LED blinkt Die eingestellte Ausgangsspannung ist um mehr als 10 % abgesunken.<br />

Es liegt ein sekundärer Verbraucherkurzschluss bzw. Überlast außerhalb<br />

des POWER BOOST-Bereiches vor.<br />

LED aus Es liegt keine Netzspannung an bzw. es liegt ein Gerätedefekt vor.<br />

5. Funktion<br />

5.1. Ausgangskennlinie<br />

Das Gerät kann bei Umgebungstemperaturen<br />

T amb < +40 °C kontinuierlich 15 A bei 24 V DC Ausgangsspannung<br />

(P ab = 360 W) liefern.<br />

Bei stärkerer Belastung durchläuft der Arbeitspunkt<br />

die in Abb.13 dargestellte U/I-Kennlinie. Der Ausgangsstrom<br />

wird auf I BOOST begrenzt.<br />

Die Sekundärspannung wird dabei so lange abgesenkt,<br />

bis der sekundärseitige Kurzschluss behoben<br />

ist.<br />

Die U/I-Kennlinie gewährleistet, dass sowohl stark<br />

kapazitive Lasten als auch Verbraucher mit DC/DC-<br />

Wandlern im Eingangskreis problemlos mit QUINT POWER versorgt werden können.<br />

Nachgeschaltete Sicherungen werden zuverlässig ausgelöst. Die Selektivität in ihrem<br />

Anlagenaufbau ist zu jeder Zeit garantiert.<br />

5.2. Temperaturverhalten<br />

Bei einer Umgebungstemperatur bis zu +40 °C<br />

stellt das Gerät einen kontinuierlichen Ausgangsstrom<br />

von 15 A zur Verfügung.<br />

Das Gerät kann den Nennausgangsstrom von 10 A<br />

bis zu einer Umgebungstemperatur von +60 °C liefern.<br />

Bei Umgebungstemperaturen über +60 °C muss<br />

die Ausgangsleistung um 2,5 % je Kelvin Temperaturerhöhung<br />

reduziert werden.<br />

UOUT<br />

[V]<br />

UN 24<br />

< 60 °C<br />

240 W<br />

15<br />

IBOOST<br />

Bei Umgebungstemperaturen über +70 °C bzw.<br />

thermischer Überlastung schaltet das Gerät nicht ab. Die Ausgangsleistung wird so weit<br />

reduziert, dass ein Geräteschutz gegeben ist. Nach Abkühlung wird die Ausgangsleistung<br />

wieder erhöht.<br />

Ausgangsstrom [A]<br />

15<br />

10<br />

10<br />

IN<br />

< 40 °C<br />

U OUT = 24 V<br />

360 W<br />

0<br />

0 20 40 60<br />

Umgebungstemperatur [°C]<br />

IOUT<br />

[A]<br />

Abb. 13<br />

Abb. 14<br />

6. Technische Daten QUINT-PS-100-240AC/24DC/10<br />

Artikel Nr.<br />

Eingangsdaten 1<br />

29 38 60 4<br />

Nenneingangsspannung 100 - 240 V AC (Weitbereichseingang)<br />

Eingangsspannungsbereich 85 - 264 V AC 90 - 350 V DC<br />

Frequenz 45 - 65 Hz 0 Hz<br />

Stromaufnahme (bei Nennwerten)<br />

Einschaltstrombegrenzung / I<br />

ca. 2,4 A (120 V AC) / 1,3 A (230 V AC)<br />

2t (+25 °C) ca. 15 A / 1,5 A2 Netzausfallüberbrückung<br />

s<br />

bei Nennlast (typ.) > 40 ms (120 V AC) / > 40 ms (230 V AC)<br />

Einschaltzeit nach Anlegen der Netzspannung<br />

< 1 s<br />

Transientenüberspannungsschutz Varistor<br />

Eingangssicherung, intern 6,3 AT (Geräteschutz)<br />

Empfohlene Vorsicherung Leitungsschutzschalter 10 A oder 16 A,<br />

Charakteristik B (EN 60 898)<br />

Ableitstrom gegen PE < 3,5 mA<br />

Ausgangsdaten 2<br />

Nennausgangsspannung U N / Toleranz 24 V DC / ± 1 %<br />

Einstellbereich der Ausgangsspannung 22,5 - 28,5 V DC<br />

Ausgangsstrom bei Konvektionskühlung:<br />

•POWER BOOST I BOOST -25 bis +40 °C<br />

•Nennausgangsstrom I N -25 bis +60 °C<br />

15 A (U out = 24 V DC)<br />

10 A (U out = 24 V DC)<br />

Derating ab +60 °C 2,5 % pro Kelvin<br />

Strombegrenzung bei Kurzschluss ca. I BOOST ≈ 15 A<br />

Anlauf kapazitiver Lasten unbegrenzt<br />

Regelabweichung bei:<br />

•Laständerung statisch 10 - 90 %<br />

•Laständerung dynamisch 10 - 90 %<br />

typ. < 1 %<br />

typ. < 2 %<br />

typ. < 0,1 %<br />

•Eingangsspannungsänderung ± 10 %<br />

max. Verlustleistung Leerlauf/Nennlast ca. 4 W / 33 W<br />

Wirkungsgrad > 88 % (bei 230V AC und Nennwerten)<br />

Anstiegszeit Uout (10 % - 90 %) typ. 10 ms<br />

Restwelligkeit / Schaltspitzen (20 MHz)<br />

Parallelschaltbar<br />

< 100 mVSS (bei Nennwerten)<br />

zur Redundanz und Leistungserhöhung<br />

Überspannungsschutz gegen interne<br />

Überspannungen<br />

ja, begrenzt auf ca. 35 V DC<br />

Rückeinspeisungsfestigkeit<br />

Signalausgangsdaten<br />

35 V DC<br />

DC OK 3 aktiv:<br />

+24 V DC-Signal (in Bezug auf Gerätemasse)<br />

(Uout > 0,9 x UN = High-Signal) max. 40 mA<br />

DC OK 4 potentialfrei:<br />

(Uout > 0,9 x UN = Kontakt geschlossen)<br />

max. 30 V AC/DC; max. 1 A<br />

LED 6 (Uout < 0,9 x UN = LED blinkt) LED grün<br />

9<br />

11


Allgemeine Daten<br />

Isolationsspannung Ein- /Ausgang<br />

Eingang / PE<br />

Ausgang / PE<br />

Zulassungspaket<br />

12<br />

6. Technische Daten QUINT-PS-100-240AC/24DC/10<br />

4 kV AC (Typprüfung)/2 kV AC (Stückprüfung)<br />

3,5 kV AC (Typprüfung)/2 kV AC (Stückprüfung)<br />

500 V DC (Stückprüfung)<br />

CB<br />

scheme<br />

Elektrische Ausrüstung von Maschinen EN 60 204 (Überspannungskategorie III)<br />

Sicherheitstransformatoren für<br />

Schaltnetzteile<br />

EN 61 558-2-17<br />

Elektrische Sicherheit (von Einrichtungen<br />

der Informationstechnik)<br />

EN 60950 / VDE 0805,<br />

UL/C-UL Recognized UL 60 950 u 1)<br />

Industrielle Regeleinrichtung 1)<br />

UL/C-UL Listed UL 508 U<br />

LISTED<br />

Schiffbau Germanischer Lloyd F<br />

Ausrüstung von Starkstromanlagen mit<br />

elektronischen Betriebsmitteln<br />

EN 50 178 (VDE 0160)<br />

Schutzkleinspannung PELV (EN 60 204)<br />

SELV (EN 60 950)<br />

Sichere Trennung VDE 0100-410<br />

Schutz gegen elektrischen Schlag DIN 57 100-410<br />

Schutz gegen gefährliche Körperströme,<br />

Grundanforderungen für sichere Trennung<br />

in elektrischen Betriebsmitteln<br />

DIN VDE 0106-101<br />

Begrenzung Netz-Oberschwingungsströme<br />

gemäß EN 61 000-3-2<br />

Einbaulage auf waagerechter Tragschiene NS 35 nach<br />

EN 50 022<br />

Schutzart IP 20<br />

Schutzklasse Ι, mit PE Anschluss<br />

MTBF > 500 000 h nach IEC 1709 (SN 29 500)<br />

Ausführung des Gehäuses AluNox (AlMg1), geschlossen<br />

Abmessungen (B x H x T) Lieferzustand: 90 ° gedreht:<br />

+ Tragschiene (85 x 130 x 125) mm (122 x 130 x 160) mm<br />

Gewicht<br />

Klimatische Daten<br />

ca. 1,3 kg<br />

Umgebungstemperatur Betrieb -25 °C bis +70 °C (> +60 °C Derating)<br />

Lagerung -40 °C bis +85 °C<br />

Feuchtigkeit bis 95 % bei +25 °C, keine Betauung<br />

Vibration nach IEC 68-2-6 < 15 Hz, Amplitude ± 2,5 mm<br />

15 Hz-150 Hz, 2,3 g,<br />

90 min. in Resonanzfrequenz<br />

Schock nach IEC 68-2-27 30 g in alle Raumrichtungen<br />

Verschmutzungsgrad 2 (nach EN 50 178)<br />

Klimaklasse 3K3 (nach EN 60 721)<br />

1) UL-Zulassung für AC-Eingangsspannung und Umgebungstemperatur<br />

bis +70 °C (+158 °F)<br />

B<br />

c<br />

Konform zur EMV-Richtlinie 89/336/EWG<br />

und zur Niederspannungsrichtlinie 73/23/EWG<br />

EMV (Elektromagnetische Verträglichkeit) Anforderungen QUINT-PS-100-240AC/<br />

Störfestigkeit nach EN 61000-6-2<br />

EN 61 000-6-2 24DC/10<br />

EN 61000-4-2 2)<br />

Gehäuse<br />

Level 4<br />

• Entladung statischer Kontaktentladung: 4 kV<br />

8 kV<br />

Elektrizität (ESD) Luftentladung: 8 kV<br />

15 kV<br />

EN 61000-4-3 1)<br />

Gehäuse<br />

Level 3<br />

• elektromagnetisches Frequenz: 80-1000 MHz<br />

80-1000 MHz/1,4-2,0GHz<br />

HF-Feld<br />

Feldstärke: 10 V/m<br />

10 V/m<br />

EN 61000-4-4 2)<br />

• schnelle Transienten<br />

(Burst):<br />

Eingang:<br />

Ausgang:<br />

Signal:<br />

2 kV unsymmetrisch 4)<br />

2 kV unsymmetrisch 4)<br />

1 kV unsymmetrisch 4)<br />

4 kV (Level 4)<br />

2 kV (Level 3)<br />

1 kV (Level 2)<br />

EN 61000-4-5 2)<br />

• Stoßstrombelastungen<br />

(Surge):<br />

Eingang:<br />

Ausgang:<br />

Signal:<br />

2 kV unsymmetrisch 4)<br />

1 kV symmetrisch 3)<br />

0,5 kV unsymmetrisch 4)<br />

0,5 kV symmetrisch3) 1 kV unsymmetrisch4) 4 kV (Inst.-Klasse 4)<br />

2 kV (Inst.-Klasse 4)<br />

0,5 kV (Level 1)<br />

0,5 kV (Level 1)<br />

1 kV (Level 2)<br />

EN 61000-4-6 1)<br />

E/A/S:<br />

unsymmetrisch<br />

• leitungsgeführte Frequenz:<br />

Beeinflussung<br />

Uo: 4)<br />

Level 3<br />

0,15-80 MHz<br />

0,15-80 MHz<br />

EN 61000-4-11<br />

10 V<br />

10 V<br />

2) Eingang: 30 % Reduktion der siehe Eingangsdaten:<br />

• Spannungseinbrüche<br />

Ausgangsspannung für Netzausfallüberbrückung<br />

0,5-Perioden<br />

> 20 ms<br />

ENV 50204<br />

Frequenz: nicht gefordert 900 MHz/ 1800 MHz<br />

• Simulation Funktelefone Feldstärke:<br />

20 V/m<br />

Störabstrahlung nach EN 50081-2<br />

• Funkstörstrahlung EN 55011<br />

Klasse A 5)<br />

EN 55011 (EN 55022)<br />

Klasse B 6)<br />

• Funkstörspannung EN 55011<br />

Klasse A 5)<br />

EN 55011 (EN 55022)<br />

Klasse B 6)<br />

EN 55011 entspricht der CISPR11 / EN 55022 entspricht der CISPR22<br />

EN 61000 entspricht der IEC 1000<br />

1) Kriterium A: Normales Betriebsverhalten innerhalb der festgelegten Grenzen.<br />

2)<br />

Kriterium B: Vorübergehende Beeinträchtigung des Betriebsverhaltens,<br />

die das Gerät selbst wieder korrigiert.<br />

3) symmetrisch: Leitung gegen Leitung.<br />

4) unsymmetrisch: Leitung gegen Erde.<br />

5)<br />

Klasse A: Einsatzgebiet Industrie.<br />

6) Klasse B: Einsatzgebiet Industrie und Wohnbereich.<br />

13


Primary Switched-Mode Power Supply Unit - for Universal Use<br />

QUINT-PS-100-240AC/24DC/10<br />

Order No.: 29 38 60 4<br />

1. QUINT POWER offers:<br />

• Worldwide application due to wide-range input<br />

• High operational reliability even in complex global networks<br />

• POWER BOOST power reserve for complex loads<br />

• Preventive function monitoring thanks to professional signaling<br />

2. View of the device, equipment connections and operating elements acc. to fig. 1:<br />

1 AC input:<br />

Input voltage<br />

85-264 V AC<br />

Frequency 45-65 Hz<br />

(0.2 mm2 to 2.5 mm2 solid)<br />

0.2 mm2 to 2.5 mm2 2 DC output:<br />

stranded)<br />

(AWG 24-12)<br />

Internal fusing 6.3 AT<br />

Recommended backup fuse<br />

10 A or 16 A m.c.b./<br />

characteristic B<br />

3. Safety and warning notes<br />

In order to guarantee safe operation of the device and to be able to make use of all<br />

the functions, please read these instructions thoroughly!<br />

QUINT POWER are devices for <strong>install</strong>ation as built-in equipment. The device may only be<br />

<strong>install</strong>ed and put into operation by qualified personnel. The corresponding national<br />

regulations (e.g. VDE, DIN) must be observed.<br />

Before putting the device into operation, ensure that<br />

• the mains connection has been carried out by a competent person and protection<br />

against electric shock is guaranteed!<br />

• the device can be disconnected outside the power supply unit in accordance with the<br />

regulations as in EN 60950 (e.g. through primary side line protection)!<br />

• the ground conductor is connected!<br />

• all feed lines are sufficiently protected and dimensioned!<br />

• all output lines are dimensioned according to the maximum output current of the device<br />

or separately protected!<br />

• sufficient convection is guaranteed!<br />

Depending on the ambient temperature and load of the device, the temperature of<br />

the housing can become very high!<br />

Components with dangerously high voltage and high stored energy are located in<br />

the device!<br />

14<br />

16<br />

ENGLISH<br />

Output voltage<br />

24 V DC (preset),<br />

can be adjusted from 22.5 to<br />

28.5 V DC via potentiometer 5<br />

(0.2 mm 2 to 2.5 mm 2 solid)<br />

(0.2 mm 2 to 2.5 mm 2 stranded)<br />

(AWG 24-12)<br />

The device is protected<br />

against idling and shortcircuit.<br />

Caution: Never carry out work on live parts!<br />

Danger of fatal injury!<br />

4.1.2. Slim-style <strong>install</strong>ation<br />

The device is supplied ready for <strong>install</strong>ation in a<br />

narrow position.<br />

Assembly:<br />

Position the module with the<br />

mounting rail guide on the upper<br />

edge of the mounting rail, and snap it<br />

in with a downward motion (Fig. 4a).<br />

Dismantling: Pull the snap lever open with the aid<br />

of a screwdriver and slide the module<br />

out at the lower edge of the mounting<br />

rail (Fig. 4b).<br />

3 DC OK output active<br />

44 DC OK output<br />

floating<br />

5 Potentiometer (covered)<br />

22.5 – 28.5 V DC<br />

6 DC OK control lamp<br />

7 Universal mounting rail<br />

adapter UTA 107<br />

4.1.3. Low-profile <strong>install</strong>ation<br />

Low-profile <strong>install</strong>ation can be achieved by mounting the device at right-angles to the<br />

mounting rail. Mount the mounting rail adapter (UTA 107) 7 as described in Fig. 5<br />

(T10 torx screws, tightening torque 0.8 - 0.9 Nm).<br />

No additional mounting material is required.<br />

4.2. Connection<br />

Network types: 100-240 V AC networks<br />

TN-S network TN-C network TT network<br />

L N PE<br />

QUINT<br />

+ –<br />

L<br />

N<br />

PE<br />

L N PE<br />

QUINT<br />

+ –<br />

L<br />

PEN<br />

L N PE<br />

QUINT<br />

+ –<br />

Fig. 6a Fig. 6b Fig. 6c<br />

L<br />

N<br />

Fig. 4a<br />

Fig. 4b<br />

Fig. 5<br />

4. Installation<br />

4.1. Installation<br />

The power supply unit can be snapped onto all<br />

mounting rails in acc. with EN 50022-35. They<br />

should be horizontal (input terminal blocks below)<br />

4.1.1. Installation dimensions<br />

290<br />

In order to guarantee sufficient<br />

convection, we recommend<br />

observing the following minimum<br />

distance to other modules:<br />

8.0 cm in a vertical direction and<br />

1.5 cm in a horizontal direction.<br />

Slim-style <strong>install</strong>ation:<br />

Installation depth 125 mm (+ mount. rail)<br />

145<br />

80<br />

15<br />

QUINT POWER<br />

115 15 15 152<br />

85 122<br />

DC<br />

13 14 OK + + – –<br />

Output DC 24V 10A<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Input<br />

AC 100-240V<br />

L N 5<br />

QUINT POWER<br />

13 14 DC<br />

OK<br />

+ + – –<br />

DC<br />

13 14 OK<br />

Output DC 24V 10A<br />

+ + – –<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Input<br />

AC 100-240V<br />

L N 5<br />

- 25 … + 60 °C<br />

- 13 … + 140 °F<br />

APPROVALS<br />

Read <strong>install</strong>ation instructions<br />

before connecting to mains www.interface.phoenixcontact.com<br />

U INDUSTRIAL<br />

F<br />

LISTED<br />

–25<br />

B<br />

CONTROL<br />

EQUIPMENT<br />

43KA<br />

EN 60950<br />

EN 60204<br />

EN 61558-2-17<br />

EN 61000-6-2<br />

EN 50081-1<br />

Fig. 2<br />

Low-profile <strong>install</strong>ation:<br />

Installation depth 1) 103 mm (+ mount. rail)<br />

1) (incl. 15 mm convection distance)<br />

15<br />

130<br />

Fig. 3<br />

4.2.1. Connecting cable:<br />

The device is equipped with COMBICON plug connectors. This reliable and easy-toassemble<br />

connection method enables a fast connection of devices and a visible isolation<br />

of the electric connection if necessary.<br />

Only plug in or unplug connectors in a power off state!<br />

You can connect the following cable cross sections:<br />

2<br />

Solid [mm ]<br />

2<br />

Stranded [mm ] AWG Torque [Nm]<br />

1 Input: 0.2-2.5 0.2-2.5 24-12 0.5 - 0.6<br />

22 Output: 0.2-2.5 0.2-2.5 24-12 0.5 - 0.6<br />

4 Signal: 0.2-2.5 0.2-2.5 24-12 0.5 - 0.6<br />

To achieve a reliable and shockproof connection:<br />

• Strip the connecting ends 8 mm<br />

(see Fig. 7)!<br />

4.2.2. Input (Fig.8)<br />

The 100-240 V AC connection is made using the L, N<br />

and 5 screw connections.<br />

Protection of the primary side<br />

The device must be <strong>install</strong>ed in acc. with the<br />

regulations as in EN 60 950. It must be possible to<br />

disconnect the device using a suitable isolating facility<br />

outside the power supply. The primary side line<br />

protection, for example, is suitable.<br />

No further device protection is necessary, since there<br />

is an internal fuse.<br />

Recommended backup fuse:<br />

Power circuit-breaker 10 A or 16 A, characteristic B (or identical function).<br />

In DC applications, a suitable backup fuse must be wired in!<br />

If the internal fuse is triggered, there is<br />

most probably a malfunction in the device.<br />

In this case, the device must be inspected<br />

in the factory!<br />

4.2.3. Output (Fig. 9)<br />

The 24 V DC connection is made using the "+" and "–"<br />

screw connections on screw connector 22 .<br />

At the time of delivery, the output voltage is 24 V DC.<br />

The output voltage can be set from 22.5 to 28.5 V DC<br />

on the potentiometer 5.<br />

8 mm<br />

Input<br />

AC 100-240V<br />

L N 5<br />

4 33<br />

13 14 DC<br />

OK<br />

+ + – –<br />

DC<br />

13 14 OK<br />

Output DC 24V 10A<br />

+ + – –<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Fig. 7<br />

Fig. 8<br />

22<br />

5<br />

Fig. 9<br />

15<br />

17


Protection of the secondary side:<br />

The device is electronically protected against short-circuit and idling. In the event of a<br />

malfunction, the output voltage is limited to 35 V DC.<br />

Make sure that all output lines are dimensioned according to the maximum output current<br />

or are separately protected!<br />

The cables on the secondary side should have large cross sections in order to keep the<br />

voltage drops on the lines as low as possible.<br />

4.3. Signaling<br />

The two DC OK outputs are for preventive monitoring of the functions of the power supply<br />

unit. A floating signal contact 44 and an active DC OK signal 3 are available. The DC OK<br />

LED 6 also enables evaluation of the function of the power supply directly on site.<br />

4.3.1. Floating contact (Fig.10)<br />

The floating signal contact opens and signalizes a drop in<br />

the output voltage as set of more than 10 %. Signals and<br />

ohmic loads of up to 30 V and currents of up to 1 A can be<br />

connected.<br />

For heavily inductive loads such as a relay, a suitable<br />

protection circuit (e.g. damping diode) is necessary.<br />

4.3.2. Active signal output (Fig. 11)<br />

The 24 V DC signal is applied between the "DC OK" and "–"<br />

connection terminal blocks and can carry up to 40 mA. This<br />

signal output signalizes when the output voltage is more<br />

than 10 % below the set output voltage by switching from<br />

"active high" to "low".<br />

The DC OK signal is decoupled from the power output. It is<br />

thus not possible for parallel switched devices to provide<br />

external supply.<br />

The 24 V DC signal can be directly connected to a logic input for evaluation.<br />

4.3.3. Signal loop (Fig.12)<br />

The two above-mentioned signal outputs can be easily combined.<br />

Example: Monitoring of two devices.<br />

Use the active signal output of device 1 and loop<br />

in the floating signal output of device 2. In the<br />

event of malfunctioning, a common alarm is<br />

output. Any number of devices can be looped in.<br />

This signal combination saves wiring costs and<br />

logic inputs.<br />

18<br />

20<br />

24 V DC<br />

40 mA<br />

13 14<br />

Output 24V DC<br />

DC OK<br />

+ + – –<br />

DC OK<br />

max.<br />

30 VAC/DC, 1 A Fig. 10<br />

13 14<br />

24 V DC<br />

40 mA<br />

Output 24V DC<br />

DC OK<br />

Device 1<br />

Output 24V DC<br />

13 14<br />

DC OK<br />

+ + – –<br />

DC OK<br />

+ + – –<br />

DC OK<br />

Fig. 11<br />

Device 2<br />

Outpu<br />

13 14<br />

Fig. 12<br />

5.3. Parallel operation<br />

Devices of the same type can be connected in parallel to enable both redundancy and an<br />

increase in efficiency. No other alignment is necessary when in the state of delivery.<br />

If the output voltage is adjusted, a uniform distribution of power is guaranteed by setting<br />

all parallel operated power supply units to exactly the same output voltage.<br />

To ensure symmetrical distribution of power, we recommend designing all cable<br />

connections from the power supply unit to a busbar of the same length and with the same<br />

conductor cross section.<br />

The system makes it advisable to <strong>install</strong> a protective circuit at the output of each device<br />

when more than two power supply units are connected in parallel (e.g. decoupling diode<br />

or DC fuse). This prevents high reverse feed currents in the event of a secondary device<br />

fault.<br />

5.3.1. Redundant operation (Fig. 15)<br />

Redundant circuits are suitable for the supply of<br />

systems which make especially high requirements on<br />

the operational safety. If a fault occurs in the primary<br />

circuit of the first power supply unit, the second device<br />

automatically takes over the entire power supply,<br />

without interruption, and vice versa.<br />

For this reason, the power supply units to be<br />

connected in parallel are dimensioned in such a way<br />

that the total current requirement of all consumers can<br />

be completely covered by one power supply unit.<br />

100% redundancy makes external decoupling diodes necessary!<br />

5.3.2. Increased capacity (Fig. 16)<br />

For n parallel connected devices, the output current<br />

can be increased to n x I N .<br />

Parallel connection to increase efficiency is used for<br />

the expansion of existing systems. It is advisable to use<br />

parallel connection if the power supply unit does not<br />

cover the current requirement of the most powerful<br />

consumer. Otherwise the consumers should be spread<br />

among individual devices independent of one another.<br />

A maximum of five devices can be connected in parallel!<br />

QUINT QUINT<br />

10 A + – 10 A + –<br />

+<br />

–<br />

+ –<br />

DC OK<br />

Σ = 10 A<br />

Fig. 15<br />

QUINT QUINT<br />

10 A + – 10 A + –<br />

+<br />

–<br />

+ –<br />

Σ = 20 A<br />

Fig. 16<br />

4.3.4. DC OK LED<br />

The green DC OK LED enables evaluation of the function locally in the control cabinet.<br />

LED lit Normal operation of the power supply<br />

LED flashes The set output voltage has dropped by more than 10 %.<br />

There is a secondary consumer short-circuit or overload outside the<br />

POWER BOOST area.<br />

LED off There is no mains voltage or there is a device fault.<br />

5. Function<br />

5.1. Output characteristic curve<br />

In the case of ambient temperatures Tamb < +40°C,<br />

the device can continuously supply 15 A with 24 V<br />

DC output voltage (Pamb = 360 W).<br />

In the event of a higher load, the operating point<br />

follows the U/I characteristic curve depicted in<br />

Fig. 13. The output current is limited to IBOOST. The secondary voltage is reduced until the short<br />

circuit on the secondary side has been remedied.<br />

The U/I characteristic curve ensures that both<br />

heavily capacitive loads and devices with DC/DC<br />

converters in the primary circuit can be fed without<br />

problems using QUINT POWER.<br />

Downstream fuses are triggered reliably. Selectivity in the design of your system is<br />

guaranteed at all times.<br />

5.2. Thermal behavior<br />

With an ambient temperature of up to +40°C, the<br />

device supplies a continuous output current of 15 A.<br />

The device can supply a nominal output current of<br />

10 A with ambient temperatures of up to +60°C.<br />

In the case of ambient temperatures above +60°C,<br />

the output capacity has to be reduced by 2.5% per<br />

Kelvin increase in temperature.<br />

UOUT<br />

[V]<br />

UN 24<br />

< 60 °C<br />

240 W<br />

15<br />

IBOOST<br />

The device does not switch off at ambient<br />

temperatures of +70°C or thermal overload. The<br />

Fig. 14<br />

output capacity is reduced as far as necessary to<br />

provide device protection. After it has cooled down, the output capacity is increased<br />

again.<br />

Output current [A]<br />

15<br />

10<br />

10<br />

IN<br />

< 40 °C<br />

U OUT = 24 V<br />

360 W<br />

0<br />

0 20 40 60<br />

Ambient temperature [°C]<br />

IOUT<br />

[A]<br />

Fig. 13<br />

6. Technical data QUINT-PS-100-240AC/24DC/10<br />

Order No.<br />

Input data 1<br />

29 38 60 4<br />

Nominal input voltage 100-240 V AC (Wide-range input)<br />

Input voltage range 85-264 V AC 90 - 350 V DC<br />

Frequency 45-65 Hz 0 Hz<br />

Current consumption (at nom. values)<br />

Inrush current limitation / I<br />

approx. 2.4 A (120 V AC) / 1.3 A (230 V AC)<br />

2t (+25°C) approx. 15 A / 1.5 A2 Mains buffering<br />

s<br />

at nominal load (typ.) > 40 ms (120 V AC) / > 40 ms (230 V AC)<br />

Turn-on time after applying the mains<br />

voltage<br />

88 % (at 230 V AC and nominal values)<br />

Ascent time Uout (10 % - 90 %) 10 ms, typical<br />

Residual ripple / peak switching<br />

voltages (20 MHz)<br />

Can be connected in parallel<br />

< 100 mVpp (at nominal values)<br />

for redundancy and increased capacity<br />

Surge voltage protection against<br />

internal surge voltages<br />

yes, limited to approx. 35 V DC<br />

Resistance to reverse feed<br />

Signal output data<br />

35 V DC<br />

DC OK 3 active:<br />

+24 V DC signal (with regard to equip. dim.)<br />

(Uout > 0.9 x UN = High signal)<br />

max. 40 mA<br />

DC OK 4 floating:<br />

max. 30 V AC/DC; max. 1 A<br />

(Uout > 0.9 x UN = contact closed)<br />

LED 6 (Uout < 0.9 x UN = LED flashes) LED green<br />

19<br />

21


General data<br />

Isolation voltage input/output<br />

input / PE<br />

output / PE<br />

Approval package<br />

22<br />

6. Technical data QUINT-PS-100-240AC/24DC/10<br />

4 kV AC (type test)/2 kV AC (routine test)<br />

3.5 kV AC (type test)/2 kV AC (routine test)<br />

500 V DC (routine test)<br />

Electrical equipment of machines EN 60 204 (Surge voltage category III)<br />

Safety transformers for switched-mode<br />

power supply units<br />

EN 61 558-2-17<br />

Electrical safety (of information<br />

technology equipment)<br />

EN 60950 / VDE 0805,<br />

UL/C-UL Recognized UL 60 950 u 1)<br />

Industrial regulating devices 1)<br />

UL/C-UL Listed UL 508 U<br />

LISTED<br />

Shipbuilding German Lloyd F<br />

Electronic equip. for use in electr. power<br />

inst. and assembly in electr. power inst.<br />

EN 50 178 (VDE 0160)<br />

Protective low voltage PELV (EN 60 204)<br />

SELV (EN 60 950)<br />

Safe isolation VDE 0100-410<br />

Protection against electric shock DIN 57 100-410<br />

Protection against shock currents, basic<br />

requirements for protective separation<br />

in electrical equipment<br />

DIN VDE 0106-101<br />

Limitation of mains harmonic currents acc. to EN 61 000-3-2<br />

Installation position on horizontal NS 35 mounting rail in acc. with<br />

EN 50 022<br />

Degree of protection IP 20<br />

Class of protection Ι, with PE connection<br />

MTBF > 500 000 h in acc. with IEC 1709 (SN 29 500)<br />

Type of housing AluNox (AlMg1), enclosed<br />

Dimensions (W x H x D) State of delivery: 90° turned:<br />

(85 x 130 x 125) mm (122 x 130 x 160) mm<br />

Weight approx. 1.3 kg<br />

Climatic data<br />

Ambient temperature operation<br />

storage<br />

CB<br />

scheme<br />

-25°C to +70°C (> +60°C derating)<br />

-40°C to +85°C<br />

Humidity up to 95% at +25°C, no condensation<br />

Vibration in acc. with IEC 68-2-6 < 15 Hz, amplitude ± 2.5 mm<br />

15 Hz-150 Hz, 2.3 g,<br />

90 min. in resonant frequency<br />

Shock in acc. with IEC 68-2-27 30 g in all directions<br />

Contamination class 2 (in acc. with EN 50 178)<br />

Climatic class 3K3 (in acc. with EN 60 721)<br />

1) UL approval for AC input voltage and ambient temperature up to +70°C (+158°F)<br />

B<br />

c<br />

in conformance with EMC guideline 89/336/EEC<br />

and low voltage directive 73/23/EEC<br />

EMC (electromagnetic compatibility) Requirements<br />

Immunity to interference acc. to EN 61000-6-2 EN 61 000-6-2<br />

EN 61000-4-2 2)<br />

Housing<br />

• Discharge of static Contact discharge: 4 kV<br />

electricity (ESD) Discharge in air: 8 kV<br />

EN 61000-4-3 1)<br />

Housing<br />

• Electromagnetic Frequency: 80-1000 MHz<br />

HF field<br />

Field intensity: 10 V/m<br />

EN 61000-4-4 2)<br />

• Fast transients<br />

(Burst):<br />

Input:<br />

Output:<br />

Signal:<br />

2 kV asymmetrical 4)<br />

2 kV asymmetrical4) 1 kV asymmetrical4) EN 61000-5-4 2)<br />

• Surge voltage capacities<br />

(Surge):<br />

Input:<br />

Output:<br />

Signal:<br />

2 kV asymmetrical4) 1 kV symmetrical3) 0.5 kV asymmetrical 4)<br />

0.5 kV symmetrical 3)<br />

1 kV asymmetrical 4)<br />

EN 61000-4-6 1)<br />

I/O/S:<br />

asymmetrical<br />

• Conducted disturbance Frequency:<br />

Uo: 4)<br />

0.15-80 MHz<br />

10 V<br />

EN 61000-11-4 2) Input: 30% reduction in output<br />

• Voltage dips<br />

voltage for 0.5 periods<br />

ENV 50204<br />

• Simulation mobile phones<br />

Frequency:<br />

Field intensity:<br />

QUINT-PS-100-240AC/<br />

24DC/10<br />

Level 4<br />

8 kV<br />

15 kV<br />

Level 3<br />

80-1000 MHz/1.4-2.0 GHz<br />

10 V/m<br />

4 kV (Level 4)<br />

2 kV (Level 3)<br />

1 kV (Level 2)<br />

4 kV (Inst. class 4)<br />

2 kV (Inst. class 4)<br />

0.5 kV (Level 1)<br />

0.5 kV (Level 1)<br />

1 kV (Level 2)<br />

Level 3<br />

0.15-80 MHz<br />

10 V<br />

see input data: Mains<br />

buffering > 20 ms<br />

not required 900 MHz/1800 MHz<br />

20 V/m<br />

Noise emission acc. to EN 50081-2<br />

• Emitted radio<br />

EN 55011<br />

interference<br />

class A 5)<br />

• Radio interference<br />

EN 55011<br />

voltage<br />

class A 5)<br />

EN 55011 corresponds to CISPR11 / EN 55022 corresponds to CISPR22<br />

EN 61000 corresponds to IEC 1000<br />

EN 55011 (EN 55022)<br />

class B 6)<br />

EN 55011 (EN 55022)<br />

class B 6)<br />

1) Criterion A: Normal operating behavior within the defined limits.<br />

2)<br />

Criterion B: Temporary impairment to operational behavior that is corrected by the device<br />

itself.<br />

3) Symmetrical: Conductor to conductor.<br />

4)<br />

Asymmetrical: Conductor to ground.<br />

5)<br />

Class A: Area of application industry<br />

6) Class B: Area of application industry and residential<br />

23


Alimentation à découpage primaire universelle<br />

QUINT-PS-100-240AC/24DC/10<br />

Référence: 29 38 60 4<br />

1. QUINT POWER vous offre :<br />

• une utilisation universelle grâce à une plage étendue de tensions d'entrée<br />

• une sécurité de fonctionnement élevée même sur des réseaux globaux difficiles<br />

• POWER BOOST - réserve de puissance pour des charges difficiles<br />

• une surveillance fonctionnelle préventive par une signalisation professionnelle<br />

2. Vue du module, éléments de connexion et de commande selon la fig. 1:<br />

1 Entrée AC :<br />

Tension d’entrée<br />

85-264 V AC<br />

Fréquence 45-65 Hz<br />

(0,2 mm 2 à 2,5 mm 2 rigide)<br />

(0,2 mm 2 à 2,5 mm 2 souple)<br />

(AWG 24-12)<br />

Fusible interne 6,3 AT<br />

Fusible amont recommandé<br />

disjoncteur de circuit 10 A ou<br />

16 A / Caractéristique B<br />

3. Conseils de sécurité et avertissements<br />

Pour garantir un fonctionnement fiable du module et pouvoir utiliser toutes ses<br />

fonctions, veuillez lire la présente notice dans son intégralité !<br />

Les QUINT POWER sont des modules à encastrer. Leur <strong>install</strong>ation et leur mise en<br />

service ne doivent être confiées qu'à un personnel spécialisé dûment qualifié. Il faut par<br />

ailleurs respecter les normes nationales spécifiques applicables (par exemple NF, etc.).<br />

Il faut en particulier, avant la mise en service, s'assurer que<br />

• la connexion au réseau est réalisée selon les règles et que la protection contre les<br />

chocs électriques est assurée !<br />

• l'appareil peut être mis hors tension selon les dispositions de la norme EN 60950 en<br />

dehors de l'alimentation (par ex. via le disjoncteur du circuit côté primaire) !<br />

• le conducteur de protection est raccordé !<br />

• toutes les lignes d'arrivée sont suffisamment dimensionnées et protégées !<br />

• toutes les lignes de sortie sont dimensionnées pour l'intensité max. de sortie de l'appareil<br />

ou protégées par un fusible spécial !<br />

• la convection est suffisante !<br />

Selon la température ambiante et la sollicitation du module, la température du boîtier<br />

peut atteindre des valeurs élevées !<br />

Le module contient des éléments présentant une tension dangereuse et une forte<br />

accumulation d'énergie !<br />

24<br />

26<br />

FRANÇAIS<br />

2 Sortie DC :<br />

Tension de sortie<br />

24 V DC (préréglée),<br />

de 22,5 - 28,5 V DC réglable<br />

via potentiomètre 5<br />

(0,2 mm2 à 2,5 mm2 rigide)<br />

(0,2 mm 2 à 2,5 mm 2 3 Sortie DC OK active<br />

souple)<br />

44 Sortie DC OK<br />

indépend. du potentiel<br />

5 Potentiomètre (recouvert)<br />

22,5 - 28,5 V DC<br />

6 Témoin DC OK<br />

(AWG 24-12)<br />

77 Adaptateur pour profilé<br />

Ce module est protégé contre<br />

la marche à vide et les courtscircuits.<br />

universel UTA 107<br />

Attention : Ne jamais travailler sur un module sous tension !<br />

Danger de mort !<br />

4.1.2. Montage faible largeur<br />

Le module est livré départ usine pour être monté<br />

dans un emplacement étroit.<br />

Montage :<br />

Posez le module en plaçant le dispositif<br />

de guidage pour le profilé sur le<br />

bord supérieur du profilé et encliquetez-le<br />

vers le bas (Fig. 4a).<br />

Démontage : Tirez la fixation à ressort vers le haut<br />

à l'aide d'un tournevis et décrochez le<br />

module du bord inférieur du profilé<br />

(Fig. 4b).<br />

4.1.3. Montage faible hauteur<br />

Vous obtiendrez un montage de faible hauteur en tournant le module à 90° par rapport au<br />

profilé. Pour cela, montez l'adaptateur (UTA 107) 77 comme cela est décrit dans la fig. 5<br />

(Vis "Torx" T10, couple de serrage 0,8 - 0,9 Nm).<br />

Vous n'avez besoin d'aucun autre accessoire.<br />

4.2. Raccordement<br />

Types de réseaux : Réseaux 100-240 V AC<br />

Système TN-S Système TN-C Système TT<br />

L N PE<br />

QUINT<br />

+ –<br />

L<br />

N<br />

PE<br />

L N PE<br />

QUINT<br />

+ –<br />

L<br />

PEN<br />

L N PE<br />

QUINT<br />

+ –<br />

Fig. 6a Fig. 6b Fig. 6c<br />

L<br />

N<br />

Fig. 4a<br />

Fig. 4b<br />

Fig. 5<br />

4. Installation<br />

4.1. Montage<br />

Cette alimentation s'encliquette sur tous les profilés<br />

EN 50022-35 et doit être montée verticalement<br />

(blocs de jonction d'entrée vers le bas).<br />

4.1.1. Cotes de montage<br />

290<br />

Pour garantir un refroidissement par<br />

convection suffisant, nous recommandons<br />

de respecter les distances<br />

minimales suivantes avec les autres<br />

modules :<br />

8,0 cm dans le sens vertical et<br />

1,5 cm dans le sens horizontal.<br />

Montage faible largeur :<br />

Prof. montage 125 mm (+ profilé)<br />

145<br />

80<br />

15<br />

QUINT POWER<br />

115 15 15 152<br />

85 122<br />

DC<br />

13 14 OK + + – –<br />

Output DC 24V 10A<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Input<br />

AC 100-240V<br />

L N 5<br />

QUINT POWER<br />

13 14 DC<br />

OK<br />

+ + – –<br />

DC<br />

13 14 OK<br />

Output DC 24V 10A<br />

+ + – –<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Input<br />

AC 100-240V<br />

L N 5<br />

- 25 … + 60 °C<br />

- 13 … + 140 °F<br />

APPROVALS<br />

Read <strong>install</strong>ation instructions<br />

before connecting to mains www.interface.phoenixcontact.com<br />

U INDUSTRIAL<br />

F<br />

LISTED<br />

–25<br />

B<br />

CONTROL<br />

EQUIPMENT<br />

43KA<br />

EN 60950<br />

EN 60204<br />

EN 61558-2-17<br />

EN 61000-6-2<br />

EN 50081-1<br />

Fig. 2<br />

Montage faible hauteur :<br />

Prof. montage 1) 103 mm (+ profilé)<br />

1) (incl. 15 mm distance de convection)<br />

15<br />

130<br />

Fig. 3<br />

4.2.1. Câble de liaison :<br />

Le module est équipé de connecteurs MINICONNEC. Ce mode de raccordement fiable<br />

et pratique permet un raccordement rapide des modules et, au besoin, une déconnexion<br />

visible de la liaison électrique.<br />

Les connecteurs ne doivent être manipulés que hors tension !<br />

Vous pouvez raccorder des câbles avec les sections suivantes :<br />

2<br />

Rigide [mm ]<br />

2<br />

Souple [mm ] AWG Couple de serrage [Nm]<br />

1 Entrée : 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />

22 Sortie : 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />

4 Signal : 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />

Pour un raccordement fiable et protégé contre les<br />

contacts fortuits :<br />

• Dénuder les extrémités à raccorder sur 8 mm (v. Fig. 7)!<br />

4.2.2. Entrée (Fig. 8)<br />

Pour le raccordement 100-240 V AC on utilise les connexions<br />

à vis L, N et 5 .<br />

Protection du côté primaire<br />

Installez le module conformément aux dispositions de<br />

la norme EN 60 950. Il doit pouvoir être mis hors tension<br />

au moyen d'un dispositif de sectionnement approprié<br />

en dehors de l'alimentation. Par exemple à<br />

l'aide du disjoncteur du circuit côté primaire.<br />

Il est inutile de prévoir une autre protection, puisque<br />

le module comporte un fusible interne.<br />

Fusible amont recommandé :<br />

Disjoncteur de protection 10 A ou 16 A, caractéristique B (ou équivalent).<br />

Pour les applications DC, prévoir un fusible adéquat en amont !<br />

Le déclenchement du fusible interne traduit<br />

très probablement un défaut au niveau<br />

du module.<br />

Dans ce cas, il convient de faire contrôler le<br />

module en usine !<br />

4.2.3. Sortie (Fig. 9)<br />

Le raccordement 24 V DC se fait via les connexions<br />

vissées "+" et "–" sur la borne à vis 22 .<br />

A la livraison, la tension de sortie est réglée sur 24 V<br />

DC. Le potentiomètre 5 permet de la régler de 22,5<br />

à 28,5 V DC.<br />

8 mm<br />

Input<br />

AC 100-240V<br />

L N 5<br />

4 33<br />

13 14 DC<br />

OK<br />

+ + – –<br />

DC<br />

13 14 OK<br />

Output DC 24V 10A<br />

+ + – –<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Fig. 7<br />

Fig. 8<br />

22<br />

5<br />

Fig. 9<br />

25<br />

27


Protection du côté secondaire :<br />

Le module est doté d'une protection électronique contre les courts-circuits et la marche<br />

à vide. En cas de défaut, la tension de sortie est limitée à 35 V DC.<br />

Il convient de s'assurer que toutes les lignes de sortie sont dimensionnées en fonction du<br />

courant de sortie max. ou qu'elles sont protégées par un fusible spécial.<br />

Du côté secondaire, choisir des câbles de grande section, afin de réduire au minimum les<br />

chutes de tension sur les lignes.<br />

4.3. Signalisation<br />

Les deux sorties DC OK permettent de surveiller le bon fonctionnement de l'alimentation.<br />

On dispose d'un contact de signalisation 4 et d'un signal DC OK actif 3. En outre, la<br />

LED DC OK 6 permet de contrôler le fonctionnement de l'alimentation directement sur<br />

place.<br />

4.3.1. Contact indépendant du potentiel (Fig. 10)<br />

L'ouverture du contact de signalisation indépendant du potentiel<br />

indique que la tension de sortie est inférieure de plus<br />

de 10 % à la tension réglée. Le module accepte des signaux<br />

et des charges ohmiques jusqu'à 30 V et des intensités<br />

jusqu'à 1 A max.<br />

Pour les charges fortement inductives, tel un relais, il est<br />

nécessaire de prévoir un circuit de protection approprié<br />

(par ex. une diode de roue-libre).<br />

4.3.2. Sortie signal active (Fig. 11)<br />

Le signal 24 V DC est situé entre les bornes "DC OK" et "–"<br />

et supporte des charges jusqu'à 40 mA. Lorsqu'elle passe<br />

de "active high" à "low", cette sortie de signal indique que la<br />

tension de sortie est inférieure de plus de 10 % à la tension<br />

réglée.<br />

Le signal DC OK est découplé de la sortie Puissance. On<br />

exclut ainsi les risques d'une alimentation extérieure via des<br />

modules branchés en parallèle.<br />

Le signal 24 V DC peut être raccordé directement à une entrée TOR d’automate.<br />

4.3.3. Boucle de signal (Fig. 12)<br />

Les deux sorties de signal ci-dessus peuvent être facilement combinées.<br />

Exemple : Surveillance de deux modules.<br />

Utilisez la sortie signalisation active du module 1<br />

et bouclez une ligne depuis la sortie de signalisation<br />

indépendante du potentiel du module 2. En<br />

cas de dysfonctionnement, vous obtenez une signalisation<br />

défaut groupée. Vous pouvez boucler<br />

en ligne un nombre quelconque de modules.<br />

Cette combinaison de signaux économise des<br />

frais de câblage et des entrées logiques.<br />

28<br />

30<br />

24 V DC<br />

40 mA<br />

13 14<br />

Output 24V DC<br />

DC OK<br />

+ + – –<br />

DC OK<br />

max.<br />

30 VAC/DC, 1 A Fig. 10<br />

13 14<br />

24 V DC<br />

40 mA<br />

Output 24V DC<br />

DC OK<br />

Module 1<br />

Output 24V DC<br />

13 14<br />

DC OK<br />

+ + – –<br />

DC OK<br />

+ + – –<br />

DC OK<br />

Fig. 11<br />

Module 2<br />

Outpu<br />

13 14<br />

Fig. 12<br />

5.3. Fonctionnement en parallèle<br />

Des modules de même type peuvent être branchés en parallèle pour réaliser un circuit<br />

redondant ou augmenter la puissance. Cela ne nécessite aucun réglage supplémentaire<br />

des modules sortant d'usine.<br />

Si vous ajustez la tension de sortie, le courant sera réparti de façon équilibrée grâce à un<br />

réglage précis de toutes les alimentations fonctionnant en parallèle sur une même tension<br />

de sortie.<br />

Pour une répartition symétrique du courant, nous conseillons de réaliser toutes les<br />

liaisons de câbles de l'alimentation vers une barre omnibus avec la même longueur et la<br />

même section !<br />

Compte tenu du système, si vous montez en parallèle plus de deux alimentations, il faut<br />

prévoir un circuit de protection à chaque sortie des modules (par ex. une diode de découplage<br />

ou fusible DC). Ainsi, en cas de défaut sur le secondaire du module, vous éviterez<br />

des courant d'alimentation élevés arrivant de l'amont.<br />

5.3.1. Fonctionnement en redondance (Fig. 15)<br />

Les circuits redondants sont préconisés pour l'alimentation<br />

d'<strong>install</strong>ations soumises à des exigences<br />

particulièrement élevées de fiabilité de fonctionnement.<br />

En cas de défaut dans le circuit primaire de la<br />

première alimentation, le second module prend immédiatement<br />

le relais pour assurer l'alimentation intégrale<br />

sans interruption, et vice-versa.<br />

Pour cela, les alimentations à brancher en parallèle<br />

doivent être dimensionnés de manière qu'un seul module<br />

puisse couvrir intégralement la demande totale<br />

en courant de tous les appareils consommateurs.<br />

Une redondance à 100 % nécessite des diodes de découplage externes !<br />

5.3.2. Augmentation de puissance (Fig. 16)<br />

Avec n modules branchés en parallèle, le courant de<br />

sortie peut être augmenté jusqu'à n x I N .<br />

Ce montage en parallèle pour augmenter la puissance<br />

s'utilise en cas d'extension d'<strong>install</strong>ations existantes.<br />

Cette solution est recommandée lorsque l'alimentation<br />

ne couvre pas la demande en courant du consommateur<br />

le plus puissant. Sinon, il faut répartir les appareils<br />

sur différents modules indépendant les uns des autres.<br />

Vous pouvez brancher en parallèle cinq modules au<br />

maximum !<br />

QUINT QUINT<br />

10 A + – 10 A + –<br />

+<br />

–<br />

+ –<br />

DC OK<br />

Σ = 10 A<br />

Fig. 15<br />

QUINT QUINT<br />

10 A + – 10 A + –<br />

+<br />

–<br />

+ –<br />

Σ = 20 A<br />

Fig. 16<br />

4.3.4. LED DC OK<br />

La LED verte DC OK permet de vérifier le fonctionnement directement sur l'armoire.<br />

LED allumée L'alimentation fonctionne normalement<br />

La LED clignote<br />

La tension de sortie est inférieure de plus de 10 % à la tension réglée.<br />

Court-circuit de la charge secondaire ou surcharge en dehors de la plage<br />

du POWER BOOST.<br />

LED éteinte Absence de tension du réseau ou module défectueux.<br />

5. Fonctionnement<br />

5.1. Courbe de sortie<br />

Pour des températures ambiantes Tamb < +40 °C,<br />

le module peut débiter en continu 15 A pour une<br />

tension de sortie 24 V DC (Pab = 360 W).<br />

Pour une charge plus élevée, le point de travail suit<br />

la courbe U/I de la fig. 13. Le courant de sortie est<br />

limité à IBOOST. La tension secondaire est diminuée tant que le<br />

court-circuit du côté secondaire n'est pas éliminé.<br />

Cette courbe U/I garantit que QUINT-POWER peut<br />

alimenter sans problèmes aussi bien de fortes<br />

charges capacitives que des appareils équipés de<br />

convertisseurs DC/DC dans le circuit d’entrée.<br />

Le déclenchement des fusibles en aval est assuré de façon fiable. La sélectivité structurelle<br />

de votre <strong>install</strong>ation est ainsi garantie en permanence.<br />

5.2. Comportement en fonction de la<br />

température<br />

Pour une température ambiante de +40 °C max., le<br />

module fournit en continu un courant de sortie de<br />

15 A.<br />

Il peut débiter le courant de sortie nominal de 10 A<br />

jusqu'à une température ambiante de +60 °C.<br />

Au-delà de +60 °C, la puissance de sortie doit être<br />

réduite de 2,5 % pour chaque élévation d'un Kelvin<br />

de la température.<br />

UOUT<br />

[V]<br />

UN24<br />

24<br />

UN<br />

< 60 °C<br />

< 60 °C<br />

240 240 W 360 360 W W<br />

< 40 °C<br />

< 40 °C<br />

10 15<br />

IOUT<br />

IN10<br />

IBOOST 15<br />

[A] IOUT<br />

IN IBOOST<br />

[A]<br />

Fig. 13<br />

Fig. 13<br />

0<br />

0 20 40 60<br />

Température ambiante [°C]<br />

Si les températures ambiantes dépassent +70 °C<br />

ou en cas de surcharge thermique, le module ne s'arrête pas. La puissance de sortie est<br />

réduite jusqu'à l'obtention d'une protection du module. Après un temps de refroidissement,<br />

la puissance de sortie augmente de nouveau.<br />

Courant sortie [A]<br />

15<br />

10<br />

U OUT = 24 V<br />

Fig. 14<br />

6. Caractéristiques techniques QUINT-PS-100-240AC/24DC/10<br />

Référence<br />

Entrée 1<br />

29 38 60 4<br />

Tension nominale d'entrée 100 - 240 V AC (plage étendue)<br />

Plage de tensions d'entrée 85 - 264 V AC 90 - 350 V DC<br />

Fréquence 45 - 65 Hz 0 Hz<br />

Courant absorbé (pour valeurs nom.)<br />

Limit. courant démarrage / I<br />

env. 2,4 A (120 V AC) / 1,3 A (230 V AC)<br />

2t (+25 °C) env. 15 A / 1,5 A2 Protection contre microcoupures<br />

s<br />

pour charge nom. (typ.) > 40 ms (120 V AC) / > 40 ms (230 V AC)<br />

Durée démarrage après connexion de la<br />

tension réseau<br />

< 1 s<br />

Protection contre les transitoires Varistance<br />

Fusible d'entrée, interne 6,3 AT (protection appareil)<br />

Fusible amont recommandé Disjoncteur de protection circuit<br />

10 A ou 16 A, caractéristique B (EN 60 898)<br />

Courant de décharge vers PE<br />

Sortie 2<br />

< 3,5 mA<br />

Tension nominale UN / tolérance 24 V DC / ± 1 %<br />

Plage de réglage de la tension de sortie 22,5 - 28,5 V DC<br />

Courant sortie (refroidis. par convection):<br />

•POWER BOOST IBOOST -25 à +40 °C<br />

•Intensité nominale IN -25 à +60 °C<br />

15 A (U out = 24 V DC)<br />

10 A (U out = 24 V DC)<br />

Derating à partir de +60 °C 2,5 % par Kelvin<br />

Limit. intensité en cas court-circuit env. I BOOST ≈ 15 A<br />

Démarrage charges capacitives. illimité<br />

Ecart de réglage pour :<br />

•Modif. charge statique 10 - 90 %<br />

•Modif. charge dynamique 10 - 90 %<br />

•Modification tension d'entrée ± 10 %<br />

typ. < 1 %<br />

typ. < 2 %<br />

typ. < 0,1 %<br />

Dissip. puis. max. : vide/charge nom. env. 4 W / 33 W<br />

Rendement > 88 % (230V AC et valeurs nom.)<br />

Temps établis. Uout (10 %-90 %) typ. 10 ms<br />

Ondul. rés./pointes commut. (20 MHz )<br />

Montage en parallèle<br />

< 100 mVc-c (pour valeurs nominales)<br />

pour redondance / augment. de puissance<br />

Protection contre surtensions internes oui, limitée à env. 35 V DC<br />

Protection c. courants d'amont<br />

Sortie signal<br />

35 V DC<br />

DC OK 33 actif :<br />

Signal +24 V DC (rapport à masse appareil)<br />

(Uout > 0,9 x UN = signal "High") 40 mA max.<br />

DC OK 4 indép. potentiel :<br />

(Uout > 0,9 x UN = contact fermé)<br />

max. 30 V AC/DC; max. 1 A<br />

LED 66 (Uout < 0,9 x UN = LED clignote) LED verte<br />

29<br />

31


Autres caractéristiques<br />

Tension d'isolement entrée/sortie<br />

Entrée / PE<br />

Sortie / PE<br />

Homologations<br />

32<br />

6. Caractéristiques techniques QUINT-PS-100-240AC/24DC/10<br />

4 kV AC (essai de type)/2 kV AC (essai indiv.)<br />

3,5 kV AC (essai de type)/2 kV AC (essai indiv.)<br />

500 V DC (essai individuel)<br />

Equipement électrique des machines EN 60 204 (catégorie de surtension III)<br />

Transformateurs de sécurité pour<br />

éléments réseaux de distribution<br />

EN 61 558-2-17<br />

Sécurité électrique des matériels de<br />

traitements de l'information<br />

EN 60950 / VDE 0805,<br />

UL/C-UL Recognized UL 60 950 u 1)<br />

Dispositif de réglage industriel<br />

1)<br />

UL/C-UL Listed UL 508 U<br />

LISTED<br />

Constructions navales Germanischer Lloyd F<br />

Equipement électronique des <strong>install</strong>ations<br />

à courant fort<br />

EN 50 178 (VDE 0160)<br />

Faible tension de protection PELV (EN 60 204)<br />

SELV (EN 60 950)<br />

Isolement sécurisé VDE 0100-410<br />

Protection contre le choc électrique DIN 57 100-410<br />

Protection contre les courants dangereux,<br />

Exigences fondamentales pour un isolement<br />

sûr dans les équipements électr.<br />

DIN VDE 0106-101<br />

Limites pour les émissions de courants<br />

harmoniques<br />

d'après EN 61 000-3-2<br />

Emplacement pour le montage sur profilé horizontal NS 35 selon EN 50 022<br />

Degré de protection IP 20<br />

Classe de protection : Ι, avec connexion PE<br />

MTBF > 500 000 h selon CEI 1709 (SN 29 500)<br />

Boîtier isolant AluNox (AlMg1), fermé<br />

Dimensions (l x H x P) Etat sortie d’usine : tourné de 90 ° :<br />

(85 x 130 x 125) mm (122 x 130 x 160) mm<br />

Poids env. 1,3 kg<br />

Caractéristiques climatiques<br />

Température ambiante service<br />

stockage<br />

CB<br />

scheme<br />

-25 °C à +70 °C (> +60 °C Derating)<br />

-40 °C à +85 °C<br />

Humidité jusq. 95 % à +25 °C, sans condensation<br />

Vibration selon CEI 68-2-6 < 15 Hz, Amplitude ± 2,5 mm<br />

15 Hz-150 Hz, 2,3 g,<br />

90 min. à la fréquence de résonance<br />

Choc selon CEI 68-2-27 30 g dans toutes les directions spatiales<br />

Degré de pollution 2 (selon EN 50 178)<br />

Classe d'atmosphère 3K3 (selon EN 60 721)<br />

1) Homologation UL pour tension d'entrée AC et température ambiantejusqu'à<br />

+70 °C (+158 °F)<br />

B<br />

c<br />

Conforme à la directive CEM 89/336/CEE<br />

et à la directive basse tension 73/23/CEE<br />

CEM (Compatibilité électromagnétique) Exigences<br />

QUINT-PS-100-240AC/<br />

immunité selon EN 61000-6-2<br />

EN 61 000-6-2 24DC/10<br />

EN 61000-4-2 2)<br />

Boîtiers<br />

Niveau 4<br />

• Décharge électrostati- par contact : 4 kV<br />

8 kV<br />

que (ESD)<br />

dans l'air : 8 kV<br />

15 kV<br />

EN 61000-4-3 1)<br />

Boîtiers<br />

Niveau 3<br />

• Champ magnétique HF Fréquence : 80-1000 MHz<br />

80-1000 MHz/1,4-2,0GHz<br />

intensité champ : 10 V/m<br />

10 V/m<br />

EN 61000-4-4 2)<br />

• Transitoires électriques<br />

rapides (en salves)<br />

Entrée :<br />

Sortie :<br />

Signal :<br />

2 kV asymétrique 4)<br />

2 kV asymétrique 4)<br />

1 kV asymétrique 4)<br />

4 kV (Niveau 4)<br />

2 kV (Niveau 3)<br />

1 kV (Niveau 2)<br />

EN 61000-4-5 2)<br />

• Ondes de choc (Surge) :<br />

Entrée :<br />

Sortie :<br />

Signal :<br />

2 kV asymétrique 4)<br />

1 kV symétrique 3)<br />

0,5 kV asymétrique 4)<br />

0,5 kV symétrique3) 1 kV asymétrique4) 4 kV (classe d'inst. 4)<br />

2 kV (classe d'inst. 4)<br />

0,5 kV (Niveau 1)<br />

0,5 kV (Niveau 1)<br />

1 kV (Niveau 2)<br />

EN 61000-4-6 1)<br />

E/S/A :<br />

asymétrique<br />

• Perturbations conduites Fréquence :<br />

Uo :<br />

4)<br />

Niveau 3<br />

0,15-80 MHz<br />

0,15-80 MHz<br />

10 V<br />

10 V<br />

EN 61000-4-11 2) Entrée : Réduction de 30 % de voir entrée : Protection<br />

• Creux de tension<br />

la tension de sortie pour contre micro-coupures<br />

demi-périodes > 20 ms<br />

ENV 50204<br />

Fréquence : non requises 900 MHz/ 1800 MHz<br />

• Simulation téléph. mobiles intensité champ :<br />

20 V/m<br />

Emission selon EN 50081-2<br />

• Perturbations radioélectriques<br />

EN 55011<br />

Classe A 5)<br />

EN 55011 (EN 55022)<br />

Classe B 6)<br />

• Tension perturbatrice<br />

radioélectrique<br />

EN 55011<br />

Classe A 5)<br />

EN 55011 (EN 55022)<br />

Classe B 6)<br />

EN 55011 correspond à CISPR11 / EN 55022 correspond à CISPR22<br />

EN 61000 correspond à CEI 1000<br />

1) Critère A : Fonctionnement normal à l'intérieur de limites déterminées.<br />

2)<br />

Critère B : Perturbation provisoire du fonctionnement,<br />

que le module corrige de lui-même.<br />

3) symétrique : ligne contre ligne.<br />

4) asymétrique : ligne contre terre.<br />

5)<br />

Classe A : Secteur d'application Industrie.<br />

6) Classe B : Secteur d'application Industrie et zone résidentielle.<br />

33


Fuente de alimentación conmutada en primario, para empleo universal<br />

QUINT-PS-100-240AC/24DC/10<br />

Código: 29 38 60 4<br />

1. QUINT POWER ofrece:<br />

• Empleo a escala mundial mediante amplio rango de entrada<br />

• Alta seguridad de servicio también en redes globales difíciles<br />

• POWER BOOST - reserva de potencia para cargas difíciles<br />

• Control funcional preventivo mediante señalización profesional<br />

2. Vista del módulo, conexiones, elementos de operación según Fig. 1:<br />

1 Entrada AC:<br />

Tensión de entrada<br />

85-264 V AC<br />

Frecuencia 45-65 Hz<br />

(0,2 mm2 a 2,5 mm2 en c. rígido)<br />

(0,2 mm2 a 2,5 mm2 2 Salida DC:<br />

en c. flexible)<br />

(AWG 24-12)<br />

Fusible interno 6,3 AT<br />

Fusible previo recomendado<br />

10 A ó 16 A interruptor<br />

automático/característica B<br />

3. Indicaciones de seguridad y advertencias<br />

Para garantizar un funcionamiento seguro del módulo y poder utilizar todas las<br />

funciones, rogamos lea estas instrucciones atentamente.<br />

QUINT POWER son módulos para instalación. La instalación y la puesta en marcha<br />

solo puede ser efectuada por personal correspondientemente especializado. A tal efecto,<br />

deben considerarse las normas respectivas del país (p.ej. VDE, DIN).<br />

En particular, antes de la puesta en marcha hay que asegurarse de que,<br />

• la conexión a la red se ha instalado profesionalmente y que está garantizada la protección<br />

contra descarga eléctrica,<br />

• el módulo puede desconectarse de la tensión desde el exterior de la fuente de alimentación<br />

según las especificaciones de la EN 60950 (p.ej. mediante la protección de la<br />

línea del primario),<br />

• el conductor de protección a tierra está conectado,<br />

• todos los cables de alimentación están suficientemente protegidos y dimensionados,<br />

• todos los cables de salida están dimensionados para la corriente de salida máxima del<br />

módulo, o protegidos por fusible por separado,<br />

• está garantizada una convección suficiente.<br />

La temperatura de la caja puede adoptar valores más altos, según sea la temperatura<br />

ambiente y la carga del módulo.<br />

¡En el módulo se encuentran componentes en tensión con peligro de muerte y alta<br />

energía almacenada!<br />

34<br />

36<br />

ESPAÑOL<br />

Tensión de salida<br />

24 V DC (ajuste previo),<br />

de 22,5 - 28,5 V DC ajustable<br />

mediante potenciómetro 5<br />

(0,2 mm 2 a 2,5 mm 2 en c. rígido)<br />

(0,2 mm 2 a 2,5 mm 2 en c. flexible)<br />

(AWG 24-12)<br />

El módulo es resistente al<br />

circuito abierto y cortocircuito.<br />

Atención: ¡No trabajar nunca con la tensión conectada!<br />

¡Peligro de muerte!<br />

4.1.2. Posición para montaje estrecho<br />

El módulo se suministra de fábrica para la posición<br />

de montaje estrecho.<br />

Montaje:<br />

Coloque el módulo con la guía para<br />

carril en el borde superior del carril<br />

y encájelo hacia abajo (Fig. 4a).<br />

Desmontaje: Con ayuda de un destornillador, retire<br />

el cerrojo de encaje y descuelgue el<br />

módulo del borne inferior del carril<br />

(Fig. 4b).<br />

3 Salida activa OK DC<br />

44 Salida sin potencial OK DC<br />

55 Potenciómetro (cubierto)<br />

22,5 - 28,5 V DC<br />

6 Piloto de control OK DC<br />

7 Adaptador universal para<br />

carril UTA 107<br />

4.1.3. Posición para montaje bajo<br />

Una posición de montaje bajo se consigue mediante el montaje a 90° del carril. A tal efecto,<br />

monte el adaptador para carril (UTA 107) 7 tal como descrito en la Fig. 5 (Tornillos<br />

"Torx" T10, par de apriete 0,8 - 0,9 Nm). Para eso no se necesita material de montaje.<br />

4.2. Conexión<br />

Formas de red: redes de 100-240 V AC<br />

Red TN-S Red-C Red TT<br />

L N PE<br />

QUINT<br />

+ –<br />

L<br />

N<br />

PE<br />

L N PE<br />

QUINT<br />

+ –<br />

L<br />

PEN<br />

L N PE<br />

QUINT<br />

+ –<br />

Fig. 6a Fig. 6b Fig. 6c<br />

L<br />

N<br />

Fig. 4a<br />

Fig. 4b<br />

Fig. 5<br />

4. Instalación<br />

4.1. Montaje<br />

La fuente de alimentación puede encajarse en<br />

todos los carriles según EN 50022-35 y debe realizarse<br />

en posición horizontal (bornes de entrada<br />

abajo).<br />

4.1.1. Dimensiones de montaje<br />

290<br />

Para garantizar una suficiente convección,<br />

recomendamos guardar las<br />

siguientes separaciones mínimas<br />

respecto a otros módulos:<br />

8,0 cm en dirección vertical y<br />

1,5 cm en dirección horizontal.<br />

Posición para montaje estrecho:<br />

Profundidad de montaje 125 mm (+ carril)<br />

145<br />

80<br />

15<br />

QUINT POWER<br />

115 15 15 152<br />

85 122<br />

DC<br />

13 14 OK + + – –<br />

Output DC 24V 10A<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Input<br />

AC 100-240V<br />

L N 5<br />

QUINT POWER<br />

13 14 DC<br />

OK<br />

+ + – –<br />

DC<br />

13 14 OK<br />

Output DC 24V 10A<br />

+ + – –<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Input<br />

AC 100-240V<br />

L N 5<br />

- 25 … + 60 °C<br />

- 13 … + 140 °F<br />

APPROVALS<br />

Read <strong>install</strong>ation instructions<br />

before connecting to mains www.interface.phoenixcontact.com<br />

U INDUSTRIAL<br />

F<br />

LISTED<br />

–25<br />

B<br />

CONTROL<br />

EQUIPMENT<br />

43KA<br />

EN 60950<br />

EN 60204<br />

EN 61558-2-17<br />

EN 61000-6-2<br />

EN 50081-1<br />

Fig. 2<br />

Posición para montaje bajo:<br />

Profundidad de montaje 1) 103 mm (+ carril)<br />

1) (incl. 15 mm separación p. convección)<br />

15<br />

130<br />

Fig. 3<br />

4.2.1. Cables de conexión:<br />

El módulo está equipado con conectores enchufables COMBICON. Este tipo de conexión<br />

fiable y de práctica instalación facilita una conexión rápida de los módulos y una separación<br />

óptica de las conexiones eléctricas en caso necesario.<br />

¡Accionar los conectores enchufables solo en estado inerte!<br />

Se pueden conectar las siguientes secciones de cable:<br />

2<br />

Rígido [mm ]<br />

2<br />

Flexible [mm ] AWG Par de apriete [Nm]<br />

1 Entrada: 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />

22 Salida: 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />

4 Señal: 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />

Para contactos fiables y protegidos contra roces casuales:<br />

• Desaisle los finales de conductor 8 mm (ver Fig. 7)<br />

4.2.2. Entrada (Fig.8)<br />

La conexión de 100-240 V AC se efectúa a través de<br />

las conexiones de tornillo L, N y 5.<br />

Protección por fusible del primario<br />

La instalación del módulo tiene que realizarse conforme<br />

a las especificaciones de la EN 60 950. El módulo<br />

tiene que poderse desconectar de la tensión desde el<br />

exterior de la fuente de alimentación mediante un dispositivo<br />

de separación apropiado. Para eso puede utilizase,<br />

p.ej. la protección de la línea del primario.<br />

Otra protección de aparatos no es necesaria, dado<br />

que se dispone de un fusible interno.<br />

Fusible previo recomendado:<br />

Interruptor automático de 10 A ó 16 A, característica B (o similar).<br />

Para aplicaciones DC tiene que preverse un fusible apropiado.<br />

Si el fusible interno reacciona, es muy<br />

probable que se tenga un defecto en el<br />

módulo.<br />

En este caso, el módulo tiene que comprobarse<br />

en fábrica.<br />

4.2.3. Salida (Fig.9)<br />

La conexión de 24 V DC se efectúa mediante las<br />

conexiones de tornillo "+" y "–" en la conexión por<br />

tornillo 2.<br />

La tensión de salida está ajustada de fábrica a<br />

24 V DC. Con el potenciómetro 5,<br />

la tensión de<br />

salida puede ajustarse entre 22,5 y 28,5 V DC.<br />

8 mm<br />

Input<br />

AC 100-240V<br />

L N 5<br />

4 33<br />

13 14 DC<br />

OK<br />

+ + – –<br />

DC<br />

13 14 OK<br />

Output DC 24V 10A<br />

+ + – –<br />

DC OK<br />

Adjust<br />

22.5-28.5V<br />

Fig. 7<br />

Fig. 8<br />

22<br />

5<br />

Fig. 9<br />

35<br />

37


Protección por fusible del secundario:<br />

El módulo está protegido electrónicamente contra cortocircuito y en circuito abierto.<br />

En caso de fallo, la tensión de salida se limita como máximo a 35 V DC.<br />

Hay que asegurarse de que todos los cables de salida están correspondientemente dimensionados<br />

para la corriente de salida máxima o protegidos por fusible por separado.<br />

Los cables del secundario deben ser de sección grande para mantener la caída de tensión<br />

en los conductores lo más pequeña posible.<br />

4.3. Señalización<br />

Las dos salidas OK DC sirven para el control funcional preventivo de la fuente de alimentación.<br />

Se dispone de un contacto de señales sin potencial 4 y de una señal OK DC 3.<br />

Adicionalmente, el LED OK DC 6 facilita una evaluación de la fuente de alimentación,<br />

directamente en el lugar de empleo.<br />

4.3.1. Contacto sin potencial (Fig.10)<br />

El contacto de señales sin potencial notifica, mediante<br />

apertura, el no alcance de la tensión de salida en más del<br />

10 %. Pueden conmutarse señales y cargas resistivas de<br />

hasta máx. 30 V y corrientes de hasta máx. 1 A.<br />

Para cargas altamente inductivas, p.ej. de un relé, es necesario<br />

un circuito de protección apropiado (p.ej. diodo de<br />

protección).<br />

4.3.2. Señal de salida activa (Fig.11)<br />

La señal de 24 V DC se tiene entre los bornes de conexión<br />

"DC OK" y "–", y puede someterse a una carga de hasta<br />

40 mA. Esta salida de señal notifica, mediante el cambio de<br />

"nivel alto" a "bajo", el no alcance de la tensión de salida<br />

ajustada en más del 10 %.<br />

La señal OK DC está desacoplada de la salida de potencia.<br />

De esta manera, se excluye una alimentación ajena debida<br />

a módulos conectados en paralelo.<br />

La señal de 24 V DC puede conectarse para evaluación, directamente a una entrada de<br />

lógica.<br />

4.3.3. Bucle de señales (Fig.12)<br />

Las dos salidas de señal mencionadas anteriormente pueden combinarse de modo<br />

sencillo.<br />

Ejemplo: control de dos módulos.<br />

Utilice la salida de aviso activa del módulo 1 e<br />

inserte en bucle la salida de aviso sin potencial<br />

del módulo 2. En caso de fallo funcional se obtiene<br />

una indicación colectiva de fallo. Se pueden<br />

insertar en bucle tantos módulos como se desee.<br />

Esta combinación de señales ahorra costes de<br />

cableado y entradas lógicas.<br />

38<br />

40<br />

24 V DC<br />

40 mA<br />

13 14<br />

Output 24V DC<br />

DC OK<br />

+ + – –<br />

DC OK<br />

max.<br />

30 VAC/DC, 1 A Fig. 10<br />

13 14<br />

24 V DC<br />

40 mA<br />

Output 24V DC<br />

DC OK<br />

Módulo 1<br />

Output 24V DC<br />

13 14<br />

DC OK<br />

+ + – –<br />

DC OK<br />

+ + – –<br />

DC OK<br />

Fig. 11<br />

Módulo 2<br />

Outpu<br />

13 14<br />

Fig. 12<br />

5.3. Funcionamiento en paralelo<br />

Los módulos de igual tipo pueden conectarse en paralelo, tanto para redundancia como<br />

para aumento de potencia. Para ello, en estado de suministro no se necesitan efectuar<br />

ajustes.<br />

Si se realiza un ajuste de la tensión de salida, se garantiza un reparto de corriente uniforme<br />

mediante un ajuste exacto de todas las fuentes de alimentación conectadas en paralelo<br />

a la misma tensión de salida.<br />

Para obtener un reparto de corriente simétrico, recomendamos que todas las conexiones<br />

de los cables de la fuente de alimentación se realicen a una barra colectora con igual longitud<br />

y sección de conductor.<br />

Debido a efectos del sistema, en la conexión en paralelo de más de dos fuentes de alimentación<br />

debe instalarse un circuito de protección a cada salida de módulo (p.ej. diodo<br />

de desacoplamiento o fusible DC). De esta manera, en un defecto del secundario del módulo<br />

se evitan corrientes altas alimentadas de retorno.<br />

5.3.1. Servicio redundante (Fig. 15)<br />

Los circuitos redundantes se utilizan para la alimentación<br />

de instalaciones que deben cumplir altos requisitos<br />

en lo que a la seguridad de servicio se refiere. Si<br />

en el primario de la primera fuente de alimentación se<br />

tiene un defecto, el segundo módulo adopta automáticamente,<br />

sin interrupción, la alimentación de corriente<br />

completa y viceversa.<br />

A tal fin, las fuentes de alimentación a conectar en paralelo<br />

se dimensionan de forma, que el consumo de<br />

corriente total de todos los receptores conectados se<br />

pueda cubrir por completo por una sola fuente de alimentación.<br />

La redundancia del 100 % requiere diodos de desacoplamiento externos.<br />

5.3.2. Aumento de potencia (Fig. 16)<br />

Para n módulos conectados en paralelo, la corriente<br />

de salida puede aumentarse a n x I N .<br />

La conexión en paralelo para aumento de potencia se<br />

utiliza para la ampliación de instalaciones existentes.<br />

Una conexión en paralelo se aconseja cuando la fuente<br />

de alimentación no cubre el consumo de corriente<br />

del receptor más potente. Además, los receptores deben<br />

repartirse a módulos individuales, independientemente<br />

unos de otros.<br />

En total pueden conectarse en paralelo cinco módulos.<br />

QUINT QUINT<br />

10 A + – 10 A + –<br />

+<br />

–<br />

+ –<br />

DC OK<br />

Σ = 10 A<br />

Fig. 15<br />

QUINT QUINT<br />

10 A + – 10 A + –<br />

+<br />

–<br />

+ –<br />

Σ = 20 A<br />

Fig. 16<br />

4.3.4. LED OK DC<br />

El LED OK DC verde facilita una evaluación funcional "in situ" en el armario de distribución.<br />

LED iluminado Funcionamiento normal de la fuente de alimentación<br />

LED parpadea La tensión de salida ajustada ha descendido en más del 10 %.<br />

Se tiene un cortocircuito de receptor en el secundario o sobrecarga fuera<br />

del margen POWER BOOST.<br />

LED apagado Sin tensión de red o módulo en defecto.<br />

5. Función<br />

5.1. Característica de salida<br />

Para temperaturas ambiente T amb < +40 °C, el módulo<br />

puede suministrar constantemente 15 A para<br />

tensión de salida de 24 V DC (P ev. = 360 W).<br />

Para una carga más elevada, el punto de trabajo recorre<br />

la curva característica U/I representada en la<br />

Fig. 13. La corriente de salida se limita a I BOOST .<br />

En eso, la tensión del secundario permanece reducida<br />

hasta que se haya eliminado el cortocircuito<br />

del secundario.<br />

La curva característica U/I garantiza que, tanto cargas<br />

capacitivas altas como receptores con conver-<br />

tidores DC/DC en el circuito de entrada, pueden alimentarse con QUINT POWER sin problemas.<br />

Los fusibles posconectados reaccionan fiablemente. La selectividad en la construcción<br />

de la instalación está garantizada en todo momento.<br />

5.2. Comportamiento de temperatura<br />

Para una temperatura ambiente de hasta +40 °C,<br />

el módulo pone a disposición una corriente de salida<br />

constante de 15 A.<br />

El módulo puede suministrar la corriente nominal<br />

de salida de 10 A hasta una temperatura ambiente<br />

de +60 °C.<br />

Para temperaturas ambiente superiores a +60 °C,<br />

la potencia de salida tiene que reducirse en 2,5 %<br />

por grado Kelvin de aumento de temperatura.<br />

UOUT<br />

[V]<br />

UN 24<br />

< 60 °C<br />

240 W<br />

15<br />

IBOOST<br />

Para temperaturas ambiente superiores a +70 °C o<br />

sobrecarga térmica se desconecta el módulo. La potencia de salida se reduce hasta el<br />

punto en el que el módulo ofrece de nuevo protección. Después de enfriarse el módulo,<br />

aumenta de nuevo la potencia de salida.<br />

Corriente de salida [A]<br />

15<br />

10<br />

10<br />

IN<br />

< 40 °C<br />

U OUT = 24 V<br />

360 W<br />

0<br />

0 20 40 60<br />

Temperatura ambiente [°C]<br />

IOUT<br />

[A]<br />

Fig. 13<br />

Fig. 14<br />

6. Datos técnicos QUINT-PS-100-240AC/24DC/10<br />

Código<br />

Entrada 1<br />

29 38 60 4<br />

Tensión nominal de entrada 100 - 240 V AC (amplio rango de entrada)<br />

Rango de tensión de entrada 85 - 264 V AC 90 - 350 V DC<br />

Frecuencia 45 - 65 Hz 0 Hz<br />

Absorción de corriente (p. valores nominales)<br />

Limitación de la corriente de cierre / I<br />

aprox. 2,4 A (120 V AC) / 1,3 A (230 V AC)<br />

2t (+25°C) aprox. 15 A / 1,5 A2 Puenteo en fallo de red<br />

s<br />

para carga nominal (típ.) > 40 ms (120 V AC) / > 40 ms (230 V AC)<br />

Tiempo de conexión al aplicar la tensión<br />

de red<br />

< 1 s<br />

Protección contra sobretensiones transitorias varistor<br />

Fusible de entrada, interno 6,3 AT (protección de aparatos))<br />

Fusible previo recomendado interruptor automático de 10 A ó 16 A,<br />

característica B (EN 60 898)<br />

Corriente de derivación a tierra (PE)<br />

Salida 2<br />

< 3,5 mA<br />

Tensión nominal de salida UN/tolerancia 24 V DC / ± 1 %<br />

Margen ajustable de la tensión de salida<br />

Corr. de salida p. refrigeración por convección:<br />

22,5 - 28,5 V DC<br />

•POWER BOOST IBOOST -25 hasta +40 °C<br />

•Corriente nominal de salida IN -25 hasta +60°C<br />

15 A (Uout = 24 V DC)<br />

10 A (Uout = 24 V DC)<br />

Derating a partir de +60 °C 2,5 % por grado Kelvin<br />

Limitación de corriente en cortocircuito aprox. I BOOST ≈ 15 A<br />

Arranque de cargas capacitivas ilimitado<br />

Error repetido para:<br />

•cambio de carga estático 10 - 90 %<br />

•cambio de carga dinámico 10 - 90 %<br />

•cambio de tensión de entrada ± 10 %<br />

típ. < 1 %<br />

típ. < 2 %<br />

típ. < 0,1 %<br />

Disipación máx.: en circuito abierto/a carga nom. aprox. 4 W / 33 W<br />

Rendimiento > 88 % (para 230V AC y valores nominales)<br />

Tiempo de ascenso Uout (10 % - 90 %) típ. 10 ms<br />

Ondulación residual/picos de conexión (20 MHz)<br />

Conectable en paralelo<br />

< 100 mVpp (para valores nominales)<br />

para redundancia y aumento de potencia<br />

Protección contra sobretensiones contra<br />

sobretensiones internas<br />

sí, limitada a aprox. 35 V DC<br />

Resistencia a la alimentación de retorno<br />

Salida de señal<br />

35 V DC<br />

DC OK 3 activo:<br />

señal +24 V DC (referida a la masa del módulo)<br />

(Uout > 0,9 x UN = señal alta)<br />

máx. 40 mA<br />

DC OK 4 sin potencial:<br />

(Uout > 0,9 x UN = contacto cerrado)<br />

máx. 30 V AC/DC; máx. 1 A<br />

LED 6 (Uout < 0,9 x UN = LED parpadea) LED verde<br />

39<br />

41


Datos generales<br />

Tensión de aislamiento entrada/salida<br />

entrada / PE<br />

salida / PE<br />

Paquete de homologaciones<br />

42<br />

6. Datos técnicos QUINT-PS-100-240AC/24DC/10<br />

4 kV AC (prueba tipo)/2 kV AC (ensayo individual)<br />

3,5 kV AC (prueba tipo)/2 kV AC (ensayo individual)<br />

500 V DC (ensayo individual)<br />

CB<br />

scheme<br />

Equipamiento eléctrico de máquinas EN 60 204 (categoría de sobretensiones III)<br />

Transformadores de seguridad para<br />

fuentes de conmutación<br />

EN 61 558-2-17<br />

Seguridad eléctrica (de dispositivos de<br />

la técnica de información)<br />

EN 60950 / VDE 0805,<br />

UL/C-UL Recognized UL 60 950 u 1)<br />

Regulación industrial<br />

1)<br />

UL/C-UL Listed UL 508 U<br />

LISTED<br />

Construcción de navíos Germanisch Lloyd F<br />

Equipamiento de instalaciones de alta<br />

intensidad con aparatos electrónicos<br />

EN 50 178 (VDE 0160)<br />

Tensión baja de protección PELV (EN 60 204)<br />

SELV (EN 60 950)<br />

Separación segura VDE 0100-410<br />

Protección contra descarga eléctrica DIN 57 100-410<br />

Protección contra corrientes corpóreas peligrosas,<br />

exigencias básicas para la separación<br />

segura de aparatos eléctricos<br />

DIN VDE 0106-101<br />

Limitación de corrientes armónicas de<br />

la red<br />

según EN 61 000-3-2<br />

Posición para el montaje sobre carril horizontal NS 35 según<br />

EN 50 022<br />

Protección IP 20<br />

Clase de protección Ι, con conexión a tierra (PE)<br />

MTBF > 500 000 h según IEC 1709 (SN 29 500)<br />

Aislamiento AluNox (AlMg1), cerrado<br />

Dimensiones (A x A x P) Estado de suministro: girado a 90 °:<br />

(85 x 130 x 125) mm (122 x 130 x 160) mm<br />

Peso<br />

Datos climáticos<br />

aprox. 1,3 kg<br />

Temperatura ambiente servicio -25 °C hasta +70 °C (> +60 °C Derating)<br />

almacenamiento -40 °C hasta +85 °C<br />

Humedad hasta el 95% para +25 °C, sin condensación<br />

Vibración según IEC 68-2-6 < 15 Hz, amplitud ± 2,5 mm<br />

15 Hz-150 Hz, 2,3 g,<br />

90 mín. en frecuencia propia<br />

Choque según IEC 68-2-27 30 g en todas las direcciones espaciales<br />

Grado de suciedad 2 (según EN 50 178)<br />

Clima 3K3 (según EN 60 721)<br />

1) Homologación UL para tensión de entrada AC y temperatura ambiente<br />

hasta +70 °C (+158 °F)<br />

B<br />

c<br />

Conformidad con la directriz EMV 89/336/EWG<br />

y con la directriz de baja tensión 73/23/EWG<br />

Compatibilidad electromagnética (EMV) Requisitos<br />

QUINT-PS-100-240AC/<br />

Resistencia a interferencias s. EN 61000-6-2 EN 61 000-6-2 24DC/10<br />

EN 61000-4-2 2)<br />

caja<br />

nivel 4<br />

• Descarga de electrici- descarga e. contactos: 4 kV<br />

8 kV<br />

dad estática (ESD) descarga en el aire: 8 kV<br />

15 kV<br />

EN 61000-4-3 1)<br />

caja<br />

nivel 3<br />

• Campo electromagnéti- frecuencia: 80-1000 MHz<br />

80-1000 MHz/1,4-2,0GHz<br />

co de AF<br />

intensidad de campo: 10 V/m<br />

10 V/m<br />

EN 61000-4-4 2)<br />

• Transitorios rápidos<br />

(Burst):<br />

entrada:<br />

salida:<br />

señal:<br />

2 kV asimétrica 4)<br />

2 kV asimétrica 4)<br />

1 kV asimétrica 4)<br />

4 kV (nivel 4)<br />

2 kV (nivel 3)<br />

1 kV (nivel 2)<br />

EN 61000-4-5 2)<br />

• Cargas de sobrecorriente<br />

(Surge):<br />

entrada:<br />

salida:<br />

señal:<br />

2 kV asimétrica 4)<br />

1 kV simétrica 3)<br />

0,5 kV asimétrica 4)<br />

0,5 kV simétrica3) 1 kV asimétrica4) 4 kV (inst. clase 4)<br />

2 kV (inst. clase 4)<br />

0,5 kV (nivel 1)<br />

0,5 kV (nivel 1)<br />

1 kV (nivel 2)<br />

EN 61000-4-6 1)<br />

E/S/S:<br />

asimétrica<br />

• Perturbaciones en la línea frecuencia:<br />

Uo: 4)<br />

nivel 3<br />

0,15-80 MHz<br />

0,15-80 MHz<br />

10 V<br />

10 V<br />

EN 61000-4-11 2) entrada: reducción del 30 % de ver datos de entrada:<br />

• Fallos de tensión<br />

la tensión de salida puenteado en fallo de la red<br />

para 0,5 periodos > 20 ms<br />

ENV 50204<br />

frecuencia: no se exige 900 MHz/ 1800 MHz<br />

• Simulación de radioteléfonos intensidad de campo:<br />

20 V/m<br />

Radiación de perturbaciones según EN 50081-2<br />

• Radiointerferencias EN 55011<br />

clase A 5)<br />

EN 55011 (EN 55022)<br />

clase B 6)<br />

• Tensión<br />

radiointerferencia<br />

EN 55011<br />

clase A 5)<br />

EN 55011 (EN 55022)<br />

clase B 6)<br />

EN 55011 equivale a la CISPR11 / EN 55022 equivale a la CISPR22<br />

EN 61000 equivale a la IEC 1000<br />

1) Criterio A: Comportamiento de servicio normal dentro de los límites determinados.<br />

2)<br />

Criterio B: Alteración transitoria del comportamiento de servicio<br />

que corrige el propio aparato.<br />

3) simétrica: Conductor contra conductor.<br />

4) asimétrica: Conductor contra tierra.<br />

5)<br />

clase A: Campo de empleo industrial.<br />

6) clase B: Campo de empleo industrial y de viviendas.<br />

43