Stromversorgungen / Power Supplies Alimentations stabilisées / Fuentes de alimentación QUINT POWER 13 14 DC OK + + – – DC 13 14 OK Output DC 24V 10A + + – – DC OK Adjust 22.5-28.5V Input AC 100-240V L N 5 QUINT POWER - die Universelle - the universal model - l’alimentation universelle - la universal AC 100-240V STEP POWER - die Flache - the low-profile model - la version basse - la baja DEUTSCH ENGLISH FRANÇAIS ESPAÑOL 2 POWER OVERLOAD PROTECTION DC 5 6 7 8 IN 100-240 V AC L(+) NC NC N(-) L NC NC N MINI POWER - die Schmale - the slim model - la version étroite - la estrecha 4.5-5.5 V DC DC OK MINI-PS-100-240AC/5DC/3 Power Supply INPUT OUTPUT AC: 100-240V 5V DC 50-60Hz ±1% Range: 3A 85-264V 0.4-0.2A DC: 90-350V 0.4-0.2A MINI POWER – – + + OUT 5 V DC Weitere Informationen zum Thema Stromversorgungen erhalten Sie unter: Further information on the subject of power supply units can be found at: Vous trouverez d’autres renseignements sur les alimentations en consultant notre site: Más información sobre el tema de las fuentes de alimentación se encuentra bajo: www.interface.phoenixcontact.com Phoenix Contact GmbH & Co. KG D-32823 Blomberg, Germany Fax +49-(0)5235-330999 Tel. +49-(0)5235-300 www.phoenixcontact.com Inhaltsverzeichnis Seite 1. QUINT POWER ........................................................................................ 4 2. Geräteansicht, -anschlüsse, -bedienungselemente ............................... 3/4 3. Sicherheits- und Warnhinweise ................................................................ 4 4. Installation 4.1. Montage.................................................................................................. 5 4.2. Anschluss .............................................................................................. 6 4.3. Signalisierung ........................................................................................ 8 5. Funktion .................................................................................................... 9 6. Technische Daten ................................................................................... 11 Table of Contents Page 1. QUINT POWER ...................................................................................... 14 2. View of the device, equipment connections and operating elements ... 3/14 3. Safety and warning notes ........................................................................ 14 4. Installation 4.1. Assembly .............................................................................................. 15 4.2. Connection ........................................................................................... 16 4.3. Signaling .............................................................................................. 18 5. Function .................................................................................................. 19 6. Technical Data ........................................................................................ 21 Sommaire Page 1. QUINT POWER vous offre ...................................................................... 24 2. Vue du module, éléments de connexion et de commande................... 3/24 3. Conseils de sécurité et avertissements ................................................... 24 4. Installation 4.1. Montage................................................................................................ 25 4.2. Raccordement ..................................................................................... 26 4.3. Signalisation ........................................................................................ 28 5. Fonctionnement ...................................................................................... 29 6. Caractéristiques techniques .................................................................... 31 Indice Página 1. QUINT POWER ...................................................................................... 34 2. Vista del módulo, conexiones, elementos de operación ...................... 3/34 3. Indicaciones de seguridad y advertencias............................................... 34 4. Instalación 4.1. Montaje ................................................................................................. 35 4.2. Conexión .............................................................................................. 36 4.3. Señalización ........................................................................................ 38 5. Función ................................................................................................... 39 6. Datos técnicos ......................................................................................... 41 Read installation instructions before connecting to mains www.interface.phoenixcontact.com LISTED CONTROL EQUIPMENT 43KA TECHNOLOGY EQUIPMENT TEMPERATURE - 25 … + 60 °C - 13 … + 140 °F APPROVALS U INDUSTRIAL u INFORMATION –25 Order No.: 29 38 71 4 Phoenix Contact GmbH & Co. KG D-32823 Blomberg, Germany Fax +49-(0)5235-330999, Tel. +49-(0)5235-300 www.interface.phoenixcontact.com TNR 9011670-00 / 06.2002 D GB F E Primär getaktete Stromversorgung für den universellen Einsatz Primary Switch-Mode Power Supply for universal use Alimentation à découpage primaire pour une utilisation universelle Fuente de alimentación de primario conmutado para empleo a escala mundial QUINT-PS-100-240AC/24DC/10 QUINT POWER 13 14 DC OK + + – – DC 13 14 OK Output DC 24V 10A + + – – DC OK Adjust 22.5-28.5V Input AC 100-240V L N 5 QUINT-PS-100-240AC/24DC/10 3 4 DC 13 14 OK CONTROL EQUIPMENT 43KA U INDUSTRIAL F LISTED Output DC 24V 10A –25 B EN 60950 EN 60204 EN 61558-2-17 EN 61000-6-2 EN 50081-1 - 25 … + 60 °C - 13 … + 140 °F APPROVALS Read installation instructions before connecting to mains www.interface.phoenixcontact.com Blockschaltbild / Block Diagram / Diagramme schématique / Esquema de conjunto 1 3 L (+) N (–) PE 13 14 DC OK + + – – DC 13 14 OK Output DCC 224V 10A 2 1 + + – – – DC active QUINT POWER PFC 13 14 DC OK + + – – + + – – DC OK Adjust 22.5-28.5V Input AC 100-240V L N 5 Art.-Nr.: 29 38 60 4 7 DC OK 13 14 6 5 Abb. 1 2 3 4
- Page 2 and 3: Stromversorgung - primär getaktet
- Page 4 and 5: Allgemeine Daten Isolationsspannung
- Page 6 and 7: Protection of the secondary side: T
- Page 8 and 9: Alimentation à découpage primaire
- Page 10 and 11: Autres caractéristiques Tension d'
- Page 12 and 13: Protección por fusible del secunda
Stromversorgungen / Power Supplies<br />
Alimentations stabilisées / Fuentes de alimentación<br />
QUINT POWER<br />
13 14 DC<br />
OK + + – –<br />
DC<br />
13 14 OK<br />
Output DC 24V 10A<br />
+ + – –<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Input<br />
AC 100-240V<br />
L N 5<br />
QUINT POWER<br />
- die Universelle<br />
- the universal model<br />
- l’alimentation universelle<br />
- la universal<br />
AC 100-240V<br />
STEP POWER<br />
- die Flache<br />
- the low-profile model<br />
- la version basse<br />
- la baja<br />
DEUTSCH<br />
ENGLISH<br />
FRANÇAIS<br />
ESPAÑOL<br />
2<br />
POWER<br />
OVERLOAD<br />
PROTECTION<br />
DC<br />
5 6 7 8<br />
IN 100-240 V AC<br />
L(+) NC NC N(-)<br />
L NC NC N<br />
MINI POWER<br />
- die Schmale<br />
- the slim model<br />
- la version étroite<br />
- la estrecha<br />
4.5-5.5<br />
V DC<br />
DC<br />
OK<br />
MINI-PS-100-240AC/5DC/3<br />
Power Supply<br />
INPUT OUTPUT<br />
AC:<br />
100-240V 5V DC<br />
50-60Hz ±1%<br />
Range: 3A<br />
85-264V<br />
0.4-0.2A<br />
DC:<br />
90-350V<br />
0.4-0.2A<br />
MINI POWER<br />
– – + +<br />
OUT 5 V DC<br />
Weitere Informationen zum Thema<br />
Stromversorgungen erhalten Sie unter:<br />
Further information on the subject of<br />
power supply units can be found at:<br />
Vous trouverez d’autres renseignements<br />
sur les alimentations en consultant notre<br />
site:<br />
Más información sobre el tema de las<br />
fuentes de alimentación se encuentra<br />
bajo:<br />
www.interface.phoenixcontact.com<br />
<strong>Phoenix</strong> Contact GmbH & Co. KG<br />
D-32823 Blomberg, Germany<br />
Fax +49-(0)5235-330999 Tel. +49-(0)5235-300<br />
www.phoenixcontact.com<br />
Inhaltsverzeichnis Seite<br />
1. QUINT POWER ........................................................................................ 4<br />
2. Geräteansicht, -anschlüsse, -bedienungselemente ............................... 3/4<br />
3. Sicherheits- und Warnhinweise ................................................................ 4<br />
4. Installation<br />
4.1. Montage.................................................................................................. 5<br />
4.2. Anschluss .............................................................................................. 6<br />
4.3. Signalisierung ........................................................................................ 8<br />
5. Funktion .................................................................................................... 9<br />
6. Technische Daten ................................................................................... 11<br />
Table of Contents Page<br />
1. QUINT POWER ...................................................................................... 14<br />
2. View of the device, equipment connections and operating elements ... 3/14<br />
3. Safety and warning notes ........................................................................ 14<br />
4. Installation<br />
4.1. Assembly .............................................................................................. 15<br />
4.2. Connection ........................................................................................... 16<br />
4.3. Signaling .............................................................................................. 18<br />
5. Function .................................................................................................. 19<br />
6. Technical Data ........................................................................................ 21<br />
Sommaire Page<br />
1. QUINT POWER vous offre ...................................................................... 24<br />
2. Vue du module, éléments de connexion et de commande................... 3/24<br />
3. Conseils de sécurité et avertissements ................................................... 24<br />
4. Installation<br />
4.1. Montage................................................................................................ 25<br />
4.2. Raccordement ..................................................................................... 26<br />
4.3. Signalisation ........................................................................................ 28<br />
5. Fonctionnement ...................................................................................... 29<br />
6. Caractéristiques techniques .................................................................... 31<br />
Indice Página<br />
1. QUINT POWER ...................................................................................... 34<br />
2. Vista del módulo, conexiones, elementos de operación ...................... 3/34<br />
3. Indicaciones de seguridad y advertencias............................................... 34<br />
4. Instalación<br />
4.1. Montaje ................................................................................................. 35<br />
4.2. Conexión .............................................................................................. 36<br />
4.3. Señalización ........................................................................................ 38<br />
5. Función ................................................................................................... 39<br />
6. Datos técnicos ......................................................................................... 41<br />
Read <strong>install</strong>ation instructions<br />
before connecting to mains<br />
www.interface.phoenixcontact.com<br />
LISTED<br />
CONTROL<br />
EQUIPMENT<br />
43KA<br />
TECHNOLOGY<br />
EQUIPMENT<br />
TEMPERATURE - 25 … + 60 °C<br />
- 13 … + 140 °F<br />
APPROVALS<br />
U INDUSTRIAL<br />
u INFORMATION<br />
–25<br />
Order No.: 29 38 71 4<br />
<strong>Phoenix</strong> Contact GmbH & Co. KG<br />
D-32823 Blomberg, Germany<br />
Fax +49-(0)5235-330999, Tel. +49-(0)5235-300<br />
www.interface.phoenixcontact.com<br />
TNR 9011670-00 / 06.2002<br />
D<br />
GB<br />
F<br />
E<br />
Primär getaktete Stromversorgung<br />
für den universellen Einsatz<br />
Primary Switch-Mode Power Supply<br />
for universal use<br />
Alimentation à découpage primaire<br />
pour une utilisation universelle<br />
Fuente de alimentación de primario conmutado<br />
para empleo a escala mundial<br />
QUINT-PS-100-240AC/24DC/10<br />
QUINT POWER<br />
13 14 DC<br />
OK<br />
+ + – –<br />
DC<br />
13 14 OK<br />
Output DC 24V 10A<br />
+ + – –<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Input<br />
AC 100-240V<br />
L N 5<br />
QUINT-PS-100-240AC/24DC/10<br />
3<br />
4<br />
DC<br />
13 14 OK<br />
CONTROL<br />
EQUIPMENT<br />
43KA<br />
U INDUSTRIAL<br />
F<br />
LISTED<br />
Output DC 24V 10A<br />
–25<br />
B<br />
EN 60950<br />
EN 60204<br />
EN 61558-2-17<br />
EN 61000-6-2<br />
EN 50081-1<br />
- 25 … + 60 °C<br />
- 13 … + 140 °F<br />
APPROVALS<br />
Read <strong>install</strong>ation instructions<br />
before connecting to mains www.interface.phoenixcontact.com<br />
Blockschaltbild / Block Diagram / Diagramme schématique /<br />
Esquema de conjunto<br />
1<br />
3<br />
L (+)<br />
N (–)<br />
PE<br />
13 14 DC<br />
OK<br />
+ + – –<br />
DC<br />
13 14 OK<br />
Output DCC 224V<br />
10A<br />
2<br />
1<br />
+ + – – –<br />
DC<br />
active<br />
QUINT POWER<br />
PFC<br />
13 14 DC<br />
OK + + – –<br />
+ + – –<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Input<br />
AC 100-240V<br />
L N 5<br />
Art.-Nr.: 29 38 60 4<br />
7<br />
DC OK<br />
13<br />
14<br />
6<br />
5<br />
Abb. 1<br />
2<br />
3<br />
4
Stromversorgung - primär getaktet für den universellen Einsatz<br />
QUINT-PS-100-240AC/24DC/10<br />
Artikelnr.: 29 38 60 4<br />
1. QUINT POWER bietet Ihnen:<br />
• Weltweiten Einsatz durch Weitbereichseingang<br />
• Hohe Betriebssicherheit auch an schwierigen globalen Netzen<br />
• POWER BOOST - Leistungsreserve für schwierige Lasten<br />
• Präventive Funktionsüberwachung durch professionelle Signalisierung<br />
2. Geräteansicht, -anschlüsse, -bedienungselemente nach Abb. 1:<br />
1 AC-Eingang:<br />
Eingangsspannung<br />
85-264 V AC<br />
Frequenz 45-65 Hz<br />
(0,2 mm 2 bis 2,5 mm 2 starr)<br />
(0,2 mm 2 bis 2,5 mm 2 flexibel)<br />
(AWG 24-12)<br />
Interne Sicherung 6,3 AT<br />
Empfohlene Vorsicherung<br />
10 A oder 16 A LS/<br />
Charakteristik B<br />
3. Sicherheits- und Warnhinweise<br />
Um einen sicheren Betrieb des Gerätes zu gewährleisten und alle Funktionen<br />
nutzen zu können, lesen Sie diese Anleitung bitte vollständig durch!<br />
QUINT POWER sind Einbaugeräte. Die Installation und Inbetriebnahme darf nur von<br />
entsprechend qualifiziertem Fachpersonal durchgeführt werden. Dabei sind die jeweiligen<br />
landesspezifischen Vorschriften (z.B. VDE, DIN) einzuhalten.<br />
Insbesondere ist vor der Inbetriebnahme sicherzustellen, dass<br />
• der Netzanschluss fachgerecht ausgeführt und der Schutz gegen elektrischen Schlag<br />
sichergestellt ist!<br />
• das Gerät nach den Bestimmungen der EN 60950 außerhalb der Stromversorgung<br />
spannungslos schaltbar ist (z.B. durch den primärseitigen Leitungsschutz)!<br />
• der Schutzleiter angeschlossen ist!<br />
• alle Zuleitungen ausreichend abgesichert und dimensioniert sind!<br />
• alle Ausgangsleitungen dem max. Ausgangstrom des Gerätes entsprechend<br />
dimensioniert oder gesondert abgesichert sind!<br />
• ausreichend Konvektion gewährleistet ist!<br />
Je nach Umgebungstemperatur und Belastung des Gerätes kann die<br />
Gehäusetemperatur hohe Werte annehmen!<br />
Im Gerät befinden sich Bauelemente mit lebensgefährlicher Spannung<br />
und hoher gespeicherter Energie!<br />
4<br />
DEUTSCH<br />
2 DC-Ausgang:<br />
Ausgangsspannung<br />
24 V DC (voreingestellt),<br />
von 22,5 - 28,5 V DC einstellbar<br />
über Potentiometer 5<br />
(0,2 mm 2 bis 2,5 mm 2 starr)<br />
(0,2 mm 2 bis 2,5 mm 2 flexibel)<br />
(AWG 24-12)<br />
Das Gerät ist leerlauf- und<br />
kurzschlussfest.<br />
Vorsicht: Niemals bei anliegender Spannung arbeiten!<br />
Lebensgefahr!<br />
4.1.2. Schmale Einbaulage<br />
Das Gerät wird ab Werk für eine schmale<br />
Einbaulage ausgeliefert.<br />
Montage:<br />
6<br />
Setzen Sie das Modul mit der<br />
Tragschienenführung an die Oberkante<br />
der Tragschiene an und rasten<br />
Sie es nach unten ein (Abb. 4a).<br />
Demontage: Ziehen Sie den Schnappriegel mit<br />
Hilfe eines Schraubendrehers auf<br />
und hängen das Modul an der Unterkante<br />
der Tragschiene aus (Abb. 4b).<br />
3 DC OK-Ausgang aktiv<br />
44 DC OK-Ausgang<br />
potentialfrei<br />
5 Potentiometer (abgedeckt)<br />
22,5 - 28,5 V DC<br />
6 DC OK-Kontrollleuchte<br />
77 Universal-Tragschienen-<br />
Adapter UTA 107<br />
4.1.3. Flache Einbaulage<br />
Eine flache Einbaulage erreichen Sie durch Montage 90 ° zur Tragschiene.<br />
Montieren Sie dazu den Tragschienenadapter (UTA 107) 7 wie in Abb. 5 beschrieben<br />
(Befestigungsschrauben Torx T10, Anzugsmoment 0,8 - 0,9 Nm).<br />
Hierzu ist kein weiteres Montagematerial erforderlich.<br />
4.2. Anschluss<br />
Netzformen: 100-240 V AC-Netze<br />
TN-S-Netz TN-C-Netz TT-Netz<br />
L N PE<br />
QUINT<br />
+ –<br />
L<br />
N<br />
PE<br />
L N PE<br />
QUINT<br />
+ –<br />
L<br />
PEN<br />
L N PE<br />
QUINT<br />
+ –<br />
Abb. 6a Abb. 6b Abb. 6c<br />
L<br />
N<br />
Abb. 4a<br />
Abb. 4b<br />
Abb. 5<br />
4. Installation<br />
4.1. Montage<br />
Die Stromversorgung ist auf alle Tragschienen<br />
nach EN 50022-35 aufrastbar und soll waagerecht<br />
erfolgen (Eingangsklemmen unten).<br />
4.1.1. Einbaumaße<br />
290<br />
Um eine ausreichende Konvektion<br />
zu gewährleisten, empfehlen wir<br />
den folgenden Mindestabstand zu<br />
anderen Modulen:<br />
8,0 cm in vertikaler Richtung und<br />
1,5 cm in horizontaler Richtung.<br />
Schmale Einbaulage:<br />
Einbautiefe 125 mm (+ Tragschiene)<br />
145<br />
80<br />
15<br />
QUINT POWER<br />
115 15 15 152<br />
85 122<br />
DC<br />
13 14 OK + + – –<br />
Output DC 24V 10A<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Input<br />
AC 100-240V<br />
L N 5<br />
QUINT POWER<br />
13 14 DC<br />
OK<br />
+ + – –<br />
DC<br />
13 14 OK<br />
Output DC 24V 10A<br />
+ + – –<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Input<br />
AC 100-240V<br />
L N 5<br />
- 25 … + 60 °C<br />
- 13 … + 140 °F<br />
APPROVALS<br />
Read <strong>install</strong>ation instructions<br />
before connecting to mains www.interface.phoenixcontact.com<br />
U INDUSTRIAL<br />
F<br />
LISTED<br />
–25<br />
B<br />
CONTROL<br />
EQUIPMENT<br />
43KA<br />
EN 60950<br />
EN 60204<br />
EN 61558-2-17<br />
EN 61000-6-2<br />
EN 50081-1<br />
Abb. 2<br />
Flache Einbaulage:<br />
Einbautiefe 1) 103 mm (+ Tragschiene)<br />
1) (inkl. 15 mm Konvektionsabstand)<br />
15<br />
130<br />
Abb. 3<br />
4.2.1. Verbindungskabel:<br />
Das Gerät ist mit COMBICON-Steckverbindern ausgerüstet. Diese zuverlässige und<br />
montagefreundliche Verbindungsart ermöglicht einen schnellen Geräteanschluss und<br />
eine sichtbare Trennung der elektrischen Verbindung im Bedarfsfall.<br />
Steckverbinder nur leistungslos betätigen!<br />
Sie können folgende Kabelquerschnitte anschließen:<br />
Starr [mm 2 ] Flexibel [mm 2 ] AWG Anzugsmoment [Nm]<br />
1 Eingang: 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />
22 Ausgang: 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />
4 Signal: 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />
Für zuverlässigen und berührsicheren Anschluss:<br />
• Isolieren Sie die Anschlussenden 8 mm ab<br />
(siehe Abb. 7)!<br />
4.2.2. Eingang (Abb.8)<br />
Der 100-240 V-AC Anschluss erfolgt über die<br />
Schraubverbindungen L, N und 5 .<br />
Absicherung der Primärseite<br />
Die Installation des Gerätes muss entsprechend den<br />
Bestimmungen der EN 60 950 erfolgen. Das Gerät<br />
muss über eine geeignete Trennvorrichtung außerhalb<br />
der Stromversorgung spannungslos schaltbar<br />
sein. Hierzu eignet sich z.B. der primärseitige Leitungsschutz.<br />
Ein weiterer Geräteschutz ist nicht erforderlich, da<br />
eine interne Sicherung vorhanden ist.<br />
Empfohlene Vorsicherung:<br />
Leitungsschutzschalter 10 A oder 16 A, Charakteristik B (oder funktionsgleich).<br />
Bei DC-Anwendungen ist eine geeignete Sicherung vorzuschalten!<br />
Löst die interne Sicherung aus, liegt mit<br />
hoher Wahrscheinlichkeit ein Gerätedefekt<br />
vor.<br />
In dem Fall ist eine Überprüfung des<br />
Gerätes im Werk erforderlich!<br />
4.2.3. Ausgang (Abb.9)<br />
Der 24 V DC-Anschluss erfolgt über die Schraubverbindungen<br />
"+" und "–" am Schraubanschluss 22 .<br />
Die eingestellte Ausgangsspannung beträgt bei Auslieferung<br />
24 V DC. Am Potentiometer 55 ist die Ausgangsspannung<br />
von 22,5 bis 28,5 V DC einstellbar.<br />
8 mm<br />
Input<br />
AC 100-240V<br />
L N 5<br />
4 3<br />
13 14 DC<br />
OK<br />
+ + – –<br />
DC<br />
13 14 OK<br />
Output DC 24V 10A<br />
+ + – –<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Abb. 7<br />
Abb. 8<br />
2<br />
5<br />
Abb. 9<br />
5<br />
7
Absicherung der Sekundärseite:<br />
Das Gerät ist elektronisch kurzschluss- und leerlauffest. Die Ausgangsspannung wird im<br />
Fehlerfall auf maximal 35 V DC begrenzt.<br />
Es ist sicherzustellen, dass alle Ausgangsleitungen dem maximalen Ausgangsstrom entsprechend<br />
dimensioniert oder gesondert abgesichert sind.<br />
Die sekundärseitigen Kabel sollten große Querschnitte haben, um die Spannungsfälle<br />
auf den Leitungen so klein wie möglich zu halten.<br />
4.3. Signalisierung<br />
Die beiden DC OK-Ausgänge dienen der präventiven Funktionsüberwachung der Stromversorgung.<br />
Es steht ein potentialfreier Signalkontakt 4 und ein aktives DC OK-Signal 3<br />
zur Verfügung. Zusätzlich ermöglicht die DC OK-LED 6 eine Funktionsauswertung der<br />
Stromversorgung direkt am Einsatzort.<br />
4.3.1. Potentialfreier Kontakt (Abb.10)<br />
Der potentialfreie Signalkontakt meldet durch Öffnen eine<br />
Unterschreitung der eingestellten Ausgangsspannung um<br />
mehr als 10 %. Es können Signale und ohmsche Lasten bis<br />
max. 30 V und Ströme von max. 1 A geschaltet werden.<br />
Bei stark induktiven Lasten wie z.B. einem Relais ist eine<br />
geeignete Schutzbeschaltung (z.B. Freilaufdiode) erforderlich.<br />
4.3.2. Aktiver Signalausgang (Abb.11)<br />
Das 24 V DC-Signal liegt zwischen den Anschlussklemmen<br />
"DC OK" und "–" an und kann bis zu 40 mA belastet werden.<br />
Dieser Signalausgang meldet durch Wechsel von "aktiv<br />
high" auf "low" eine Unterschreitung der eingestellten Ausgangsspannung<br />
um mehr als 10 %.<br />
Das DC OK-Signal ist vom Power-Ausgang entkoppelt. Somit<br />
ist eine Fremdeinspeisung durch parallelgeschaltete Geräte<br />
ausgeschlossen.<br />
Das 24 V DC-Signal kann zur Auswertung direkt an einen Logikeingang angeschlossen<br />
werden.<br />
4.3.3. Signalschleife (Abb.12)<br />
Die beiden vorher genannten Signalausgänge lassen sich auf einfache<br />
Weise kombinieren.<br />
Beispiel: Überwachung von zwei Geräten.<br />
Nutzen Sie den aktiven Meldeausgang vom Gerät<br />
1 und schleifen Sie den potentialfreien Meldeausgang<br />
von Gerät 2 ein. Bei Funktionsstörung<br />
erhalten Sie eine Sammelstörmeldung. Es<br />
können beliebig viele Geräte eingeschleift werden.<br />
Diese Signalkombination spart Verdrahtungskosten<br />
und Logikeingänge.<br />
8<br />
10<br />
24 V DC<br />
40 mA<br />
13 14<br />
Output 24V DC<br />
DC OK<br />
+ + – –<br />
DC OK<br />
max.<br />
30 VAC/DC, 1 A Abb. 10<br />
13 14<br />
24 V DC<br />
40 mA<br />
Output 24V DC<br />
DC OK<br />
Gerät 1<br />
Output 24V DC<br />
13 14<br />
DC OK<br />
+ + – –<br />
DC OK<br />
+ + – –<br />
DC OK<br />
Abb. 11<br />
Gerät 2<br />
Outpu<br />
13 14<br />
DC OK<br />
Abb. 12<br />
5.3. Parallelbetrieb<br />
Typgleiche Geräte können sowohl zur Redundanz als auch zur Leistungserhöhung<br />
parallelgeschaltet werden. Im Lieferzustand ist dazu kein weiterer Abgleich erforderlich.<br />
Wird eine Justierung der Ausgangsspannung durchgeführt, so wird eine gleichmäßige<br />
Stromaufteilung durch eine exakte Einstellung sämtlicher parallel betriebener Stromversorgungen<br />
auf eine gleiche Ausgangsspannung gewährleistet.<br />
Für eine symmetrische Stromaufteilung empfehlen wir, alle Kabelverbindungen von der<br />
Stromversorgung zu einer Sammelschiene in gleicher Länge und mit gleichem Leiterquerschnitt<br />
auszuführen!<br />
Systembedingt sollte bei der Parallelschaltung von mehr als zwei Stromversorgungen<br />
eine Schutzbeschaltung an jedem einzelnen Geräteausgang <strong>install</strong>iert werden (z.B. Entkoppeldiode<br />
oder DC-Sicherung). Somit werden bei einem sekundären Gerätedefekt<br />
hohe rückwärtsgespeiste Ströme vermieden.<br />
5.3.1. Redundanzbetrieb (Abb. 15)<br />
Redundante Schaltungen eignen sich zur Versorgung<br />
von Anlagen, die besonders hohe Anforderungen an<br />
die Betriebssicherheit stellen. Kommt es im Primärkreis<br />
der ersten Stromversorgung zu einem Defekt, so<br />
übernimmt automatisch das zweite Gerät unterbrechungsfrei<br />
die vollständige Stromversorgung und umgekehrt.<br />
Zu diesem Zweck werden die parallel zu schaltenden<br />
Stromversorgungen so dimensioniert, dass der Gesamtstrombedarf<br />
aller Verbraucher von einer Stromversorgung<br />
vollständig abgedeckt werden kann.<br />
100 % Redundanz erfordert externe Entkoppeldioden!<br />
5.3.2. Leistungserhöhung (Abb. 16)<br />
Bei n parallel geschalteten Geräten kann der Ausgangsstrom<br />
auf n x I N erhöht werden.<br />
Die Parallelschaltung zur Leistungserhöhung findet ihren<br />
Einsatz bei der Erweiterung bestehender Anlagen.<br />
Es wird eine Parallelschaltung empfohlen, wenn die<br />
Stromversorgung nicht den Strombedarf des leistungsstärksten<br />
Verbrauchers abdeckt. Ansonsten sollten die<br />
Verbraucher auf voneinander unabhängige<br />
Einzelgeräte aufgeteilt werden.<br />
Es können maximal fünf Geräte parallelgeschaltet werden!<br />
QUINT QUINT<br />
10 A + – 10 A + –<br />
+<br />
–<br />
+ –<br />
Σ = 10 A<br />
Abb. 15<br />
QUINT QUINT<br />
10 A + – 10 A + –<br />
+<br />
–<br />
+ –<br />
Σ = 20 A<br />
Abb. 16<br />
4.3.4. DC OK-LED<br />
Die grüne DC OK-LED ermöglicht eine Funktionsauswertung vor Ort am Schaltschrank.<br />
LED leuchtet Normaler Betrieb der Stromversorgung<br />
LED blinkt Die eingestellte Ausgangsspannung ist um mehr als 10 % abgesunken.<br />
Es liegt ein sekundärer Verbraucherkurzschluss bzw. Überlast außerhalb<br />
des POWER BOOST-Bereiches vor.<br />
LED aus Es liegt keine Netzspannung an bzw. es liegt ein Gerätedefekt vor.<br />
5. Funktion<br />
5.1. Ausgangskennlinie<br />
Das Gerät kann bei Umgebungstemperaturen<br />
T amb < +40 °C kontinuierlich 15 A bei 24 V DC Ausgangsspannung<br />
(P ab = 360 W) liefern.<br />
Bei stärkerer Belastung durchläuft der Arbeitspunkt<br />
die in Abb.13 dargestellte U/I-Kennlinie. Der Ausgangsstrom<br />
wird auf I BOOST begrenzt.<br />
Die Sekundärspannung wird dabei so lange abgesenkt,<br />
bis der sekundärseitige Kurzschluss behoben<br />
ist.<br />
Die U/I-Kennlinie gewährleistet, dass sowohl stark<br />
kapazitive Lasten als auch Verbraucher mit DC/DC-<br />
Wandlern im Eingangskreis problemlos mit QUINT POWER versorgt werden können.<br />
Nachgeschaltete Sicherungen werden zuverlässig ausgelöst. Die Selektivität in ihrem<br />
Anlagenaufbau ist zu jeder Zeit garantiert.<br />
5.2. Temperaturverhalten<br />
Bei einer Umgebungstemperatur bis zu +40 °C<br />
stellt das Gerät einen kontinuierlichen Ausgangsstrom<br />
von 15 A zur Verfügung.<br />
Das Gerät kann den Nennausgangsstrom von 10 A<br />
bis zu einer Umgebungstemperatur von +60 °C liefern.<br />
Bei Umgebungstemperaturen über +60 °C muss<br />
die Ausgangsleistung um 2,5 % je Kelvin Temperaturerhöhung<br />
reduziert werden.<br />
UOUT<br />
[V]<br />
UN 24<br />
< 60 °C<br />
240 W<br />
15<br />
IBOOST<br />
Bei Umgebungstemperaturen über +70 °C bzw.<br />
thermischer Überlastung schaltet das Gerät nicht ab. Die Ausgangsleistung wird so weit<br />
reduziert, dass ein Geräteschutz gegeben ist. Nach Abkühlung wird die Ausgangsleistung<br />
wieder erhöht.<br />
Ausgangsstrom [A]<br />
15<br />
10<br />
10<br />
IN<br />
< 40 °C<br />
U OUT = 24 V<br />
360 W<br />
0<br />
0 20 40 60<br />
Umgebungstemperatur [°C]<br />
IOUT<br />
[A]<br />
Abb. 13<br />
Abb. 14<br />
6. Technische Daten QUINT-PS-100-240AC/24DC/10<br />
Artikel Nr.<br />
Eingangsdaten 1<br />
29 38 60 4<br />
Nenneingangsspannung 100 - 240 V AC (Weitbereichseingang)<br />
Eingangsspannungsbereich 85 - 264 V AC 90 - 350 V DC<br />
Frequenz 45 - 65 Hz 0 Hz<br />
Stromaufnahme (bei Nennwerten)<br />
Einschaltstrombegrenzung / I<br />
ca. 2,4 A (120 V AC) / 1,3 A (230 V AC)<br />
2t (+25 °C) ca. 15 A / 1,5 A2 Netzausfallüberbrückung<br />
s<br />
bei Nennlast (typ.) > 40 ms (120 V AC) / > 40 ms (230 V AC)<br />
Einschaltzeit nach Anlegen der Netzspannung<br />
< 1 s<br />
Transientenüberspannungsschutz Varistor<br />
Eingangssicherung, intern 6,3 AT (Geräteschutz)<br />
Empfohlene Vorsicherung Leitungsschutzschalter 10 A oder 16 A,<br />
Charakteristik B (EN 60 898)<br />
Ableitstrom gegen PE < 3,5 mA<br />
Ausgangsdaten 2<br />
Nennausgangsspannung U N / Toleranz 24 V DC / ± 1 %<br />
Einstellbereich der Ausgangsspannung 22,5 - 28,5 V DC<br />
Ausgangsstrom bei Konvektionskühlung:<br />
•POWER BOOST I BOOST -25 bis +40 °C<br />
•Nennausgangsstrom I N -25 bis +60 °C<br />
15 A (U out = 24 V DC)<br />
10 A (U out = 24 V DC)<br />
Derating ab +60 °C 2,5 % pro Kelvin<br />
Strombegrenzung bei Kurzschluss ca. I BOOST ≈ 15 A<br />
Anlauf kapazitiver Lasten unbegrenzt<br />
Regelabweichung bei:<br />
•Laständerung statisch 10 - 90 %<br />
•Laständerung dynamisch 10 - 90 %<br />
typ. < 1 %<br />
typ. < 2 %<br />
typ. < 0,1 %<br />
•Eingangsspannungsänderung ± 10 %<br />
max. Verlustleistung Leerlauf/Nennlast ca. 4 W / 33 W<br />
Wirkungsgrad > 88 % (bei 230V AC und Nennwerten)<br />
Anstiegszeit Uout (10 % - 90 %) typ. 10 ms<br />
Restwelligkeit / Schaltspitzen (20 MHz)<br />
Parallelschaltbar<br />
< 100 mVSS (bei Nennwerten)<br />
zur Redundanz und Leistungserhöhung<br />
Überspannungsschutz gegen interne<br />
Überspannungen<br />
ja, begrenzt auf ca. 35 V DC<br />
Rückeinspeisungsfestigkeit<br />
Signalausgangsdaten<br />
35 V DC<br />
DC OK 3 aktiv:<br />
+24 V DC-Signal (in Bezug auf Gerätemasse)<br />
(Uout > 0,9 x UN = High-Signal) max. 40 mA<br />
DC OK 4 potentialfrei:<br />
(Uout > 0,9 x UN = Kontakt geschlossen)<br />
max. 30 V AC/DC; max. 1 A<br />
LED 6 (Uout < 0,9 x UN = LED blinkt) LED grün<br />
9<br />
11
Allgemeine Daten<br />
Isolationsspannung Ein- /Ausgang<br />
Eingang / PE<br />
Ausgang / PE<br />
Zulassungspaket<br />
12<br />
6. Technische Daten QUINT-PS-100-240AC/24DC/10<br />
4 kV AC (Typprüfung)/2 kV AC (Stückprüfung)<br />
3,5 kV AC (Typprüfung)/2 kV AC (Stückprüfung)<br />
500 V DC (Stückprüfung)<br />
CB<br />
scheme<br />
Elektrische Ausrüstung von Maschinen EN 60 204 (Überspannungskategorie III)<br />
Sicherheitstransformatoren für<br />
Schaltnetzteile<br />
EN 61 558-2-17<br />
Elektrische Sicherheit (von Einrichtungen<br />
der Informationstechnik)<br />
EN 60950 / VDE 0805,<br />
UL/C-UL Recognized UL 60 950 u 1)<br />
Industrielle Regeleinrichtung 1)<br />
UL/C-UL Listed UL 508 U<br />
LISTED<br />
Schiffbau Germanischer Lloyd F<br />
Ausrüstung von Starkstromanlagen mit<br />
elektronischen Betriebsmitteln<br />
EN 50 178 (VDE 0160)<br />
Schutzkleinspannung PELV (EN 60 204)<br />
SELV (EN 60 950)<br />
Sichere Trennung VDE 0100-410<br />
Schutz gegen elektrischen Schlag DIN 57 100-410<br />
Schutz gegen gefährliche Körperströme,<br />
Grundanforderungen für sichere Trennung<br />
in elektrischen Betriebsmitteln<br />
DIN VDE 0106-101<br />
Begrenzung Netz-Oberschwingungsströme<br />
gemäß EN 61 000-3-2<br />
Einbaulage auf waagerechter Tragschiene NS 35 nach<br />
EN 50 022<br />
Schutzart IP 20<br />
Schutzklasse Ι, mit PE Anschluss<br />
MTBF > 500 000 h nach IEC 1709 (SN 29 500)<br />
Ausführung des Gehäuses AluNox (AlMg1), geschlossen<br />
Abmessungen (B x H x T) Lieferzustand: 90 ° gedreht:<br />
+ Tragschiene (85 x 130 x 125) mm (122 x 130 x 160) mm<br />
Gewicht<br />
Klimatische Daten<br />
ca. 1,3 kg<br />
Umgebungstemperatur Betrieb -25 °C bis +70 °C (> +60 °C Derating)<br />
Lagerung -40 °C bis +85 °C<br />
Feuchtigkeit bis 95 % bei +25 °C, keine Betauung<br />
Vibration nach IEC 68-2-6 < 15 Hz, Amplitude ± 2,5 mm<br />
15 Hz-150 Hz, 2,3 g,<br />
90 min. in Resonanzfrequenz<br />
Schock nach IEC 68-2-27 30 g in alle Raumrichtungen<br />
Verschmutzungsgrad 2 (nach EN 50 178)<br />
Klimaklasse 3K3 (nach EN 60 721)<br />
1) UL-Zulassung für AC-Eingangsspannung und Umgebungstemperatur<br />
bis +70 °C (+158 °F)<br />
B<br />
c<br />
Konform zur EMV-Richtlinie 89/336/EWG<br />
und zur Niederspannungsrichtlinie 73/23/EWG<br />
EMV (Elektromagnetische Verträglichkeit) Anforderungen QUINT-PS-100-240AC/<br />
Störfestigkeit nach EN 61000-6-2<br />
EN 61 000-6-2 24DC/10<br />
EN 61000-4-2 2)<br />
Gehäuse<br />
Level 4<br />
• Entladung statischer Kontaktentladung: 4 kV<br />
8 kV<br />
Elektrizität (ESD) Luftentladung: 8 kV<br />
15 kV<br />
EN 61000-4-3 1)<br />
Gehäuse<br />
Level 3<br />
• elektromagnetisches Frequenz: 80-1000 MHz<br />
80-1000 MHz/1,4-2,0GHz<br />
HF-Feld<br />
Feldstärke: 10 V/m<br />
10 V/m<br />
EN 61000-4-4 2)<br />
• schnelle Transienten<br />
(Burst):<br />
Eingang:<br />
Ausgang:<br />
Signal:<br />
2 kV unsymmetrisch 4)<br />
2 kV unsymmetrisch 4)<br />
1 kV unsymmetrisch 4)<br />
4 kV (Level 4)<br />
2 kV (Level 3)<br />
1 kV (Level 2)<br />
EN 61000-4-5 2)<br />
• Stoßstrombelastungen<br />
(Surge):<br />
Eingang:<br />
Ausgang:<br />
Signal:<br />
2 kV unsymmetrisch 4)<br />
1 kV symmetrisch 3)<br />
0,5 kV unsymmetrisch 4)<br />
0,5 kV symmetrisch3) 1 kV unsymmetrisch4) 4 kV (Inst.-Klasse 4)<br />
2 kV (Inst.-Klasse 4)<br />
0,5 kV (Level 1)<br />
0,5 kV (Level 1)<br />
1 kV (Level 2)<br />
EN 61000-4-6 1)<br />
E/A/S:<br />
unsymmetrisch<br />
• leitungsgeführte Frequenz:<br />
Beeinflussung<br />
Uo: 4)<br />
Level 3<br />
0,15-80 MHz<br />
0,15-80 MHz<br />
EN 61000-4-11<br />
10 V<br />
10 V<br />
2) Eingang: 30 % Reduktion der siehe Eingangsdaten:<br />
• Spannungseinbrüche<br />
Ausgangsspannung für Netzausfallüberbrückung<br />
0,5-Perioden<br />
> 20 ms<br />
ENV 50204<br />
Frequenz: nicht gefordert 900 MHz/ 1800 MHz<br />
• Simulation Funktelefone Feldstärke:<br />
20 V/m<br />
Störabstrahlung nach EN 50081-2<br />
• Funkstörstrahlung EN 55011<br />
Klasse A 5)<br />
EN 55011 (EN 55022)<br />
Klasse B 6)<br />
• Funkstörspannung EN 55011<br />
Klasse A 5)<br />
EN 55011 (EN 55022)<br />
Klasse B 6)<br />
EN 55011 entspricht der CISPR11 / EN 55022 entspricht der CISPR22<br />
EN 61000 entspricht der IEC 1000<br />
1) Kriterium A: Normales Betriebsverhalten innerhalb der festgelegten Grenzen.<br />
2)<br />
Kriterium B: Vorübergehende Beeinträchtigung des Betriebsverhaltens,<br />
die das Gerät selbst wieder korrigiert.<br />
3) symmetrisch: Leitung gegen Leitung.<br />
4) unsymmetrisch: Leitung gegen Erde.<br />
5)<br />
Klasse A: Einsatzgebiet Industrie.<br />
6) Klasse B: Einsatzgebiet Industrie und Wohnbereich.<br />
13
Primary Switched-Mode Power Supply Unit - for Universal Use<br />
QUINT-PS-100-240AC/24DC/10<br />
Order No.: 29 38 60 4<br />
1. QUINT POWER offers:<br />
• Worldwide application due to wide-range input<br />
• High operational reliability even in complex global networks<br />
• POWER BOOST power reserve for complex loads<br />
• Preventive function monitoring thanks to professional signaling<br />
2. View of the device, equipment connections and operating elements acc. to fig. 1:<br />
1 AC input:<br />
Input voltage<br />
85-264 V AC<br />
Frequency 45-65 Hz<br />
(0.2 mm2 to 2.5 mm2 solid)<br />
0.2 mm2 to 2.5 mm2 2 DC output:<br />
stranded)<br />
(AWG 24-12)<br />
Internal fusing 6.3 AT<br />
Recommended backup fuse<br />
10 A or 16 A m.c.b./<br />
characteristic B<br />
3. Safety and warning notes<br />
In order to guarantee safe operation of the device and to be able to make use of all<br />
the functions, please read these instructions thoroughly!<br />
QUINT POWER are devices for <strong>install</strong>ation as built-in equipment. The device may only be<br />
<strong>install</strong>ed and put into operation by qualified personnel. The corresponding national<br />
regulations (e.g. VDE, DIN) must be observed.<br />
Before putting the device into operation, ensure that<br />
• the mains connection has been carried out by a competent person and protection<br />
against electric shock is guaranteed!<br />
• the device can be disconnected outside the power supply unit in accordance with the<br />
regulations as in EN 60950 (e.g. through primary side line protection)!<br />
• the ground conductor is connected!<br />
• all feed lines are sufficiently protected and dimensioned!<br />
• all output lines are dimensioned according to the maximum output current of the device<br />
or separately protected!<br />
• sufficient convection is guaranteed!<br />
Depending on the ambient temperature and load of the device, the temperature of<br />
the housing can become very high!<br />
Components with dangerously high voltage and high stored energy are located in<br />
the device!<br />
14<br />
16<br />
ENGLISH<br />
Output voltage<br />
24 V DC (preset),<br />
can be adjusted from 22.5 to<br />
28.5 V DC via potentiometer 5<br />
(0.2 mm 2 to 2.5 mm 2 solid)<br />
(0.2 mm 2 to 2.5 mm 2 stranded)<br />
(AWG 24-12)<br />
The device is protected<br />
against idling and shortcircuit.<br />
Caution: Never carry out work on live parts!<br />
Danger of fatal injury!<br />
4.1.2. Slim-style <strong>install</strong>ation<br />
The device is supplied ready for <strong>install</strong>ation in a<br />
narrow position.<br />
Assembly:<br />
Position the module with the<br />
mounting rail guide on the upper<br />
edge of the mounting rail, and snap it<br />
in with a downward motion (Fig. 4a).<br />
Dismantling: Pull the snap lever open with the aid<br />
of a screwdriver and slide the module<br />
out at the lower edge of the mounting<br />
rail (Fig. 4b).<br />
3 DC OK output active<br />
44 DC OK output<br />
floating<br />
5 Potentiometer (covered)<br />
22.5 – 28.5 V DC<br />
6 DC OK control lamp<br />
7 Universal mounting rail<br />
adapter UTA 107<br />
4.1.3. Low-profile <strong>install</strong>ation<br />
Low-profile <strong>install</strong>ation can be achieved by mounting the device at right-angles to the<br />
mounting rail. Mount the mounting rail adapter (UTA 107) 7 as described in Fig. 5<br />
(T10 torx screws, tightening torque 0.8 - 0.9 Nm).<br />
No additional mounting material is required.<br />
4.2. Connection<br />
Network types: 100-240 V AC networks<br />
TN-S network TN-C network TT network<br />
L N PE<br />
QUINT<br />
+ –<br />
L<br />
N<br />
PE<br />
L N PE<br />
QUINT<br />
+ –<br />
L<br />
PEN<br />
L N PE<br />
QUINT<br />
+ –<br />
Fig. 6a Fig. 6b Fig. 6c<br />
L<br />
N<br />
Fig. 4a<br />
Fig. 4b<br />
Fig. 5<br />
4. Installation<br />
4.1. Installation<br />
The power supply unit can be snapped onto all<br />
mounting rails in acc. with EN 50022-35. They<br />
should be horizontal (input terminal blocks below)<br />
4.1.1. Installation dimensions<br />
290<br />
In order to guarantee sufficient<br />
convection, we recommend<br />
observing the following minimum<br />
distance to other modules:<br />
8.0 cm in a vertical direction and<br />
1.5 cm in a horizontal direction.<br />
Slim-style <strong>install</strong>ation:<br />
Installation depth 125 mm (+ mount. rail)<br />
145<br />
80<br />
15<br />
QUINT POWER<br />
115 15 15 152<br />
85 122<br />
DC<br />
13 14 OK + + – –<br />
Output DC 24V 10A<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Input<br />
AC 100-240V<br />
L N 5<br />
QUINT POWER<br />
13 14 DC<br />
OK<br />
+ + – –<br />
DC<br />
13 14 OK<br />
Output DC 24V 10A<br />
+ + – –<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Input<br />
AC 100-240V<br />
L N 5<br />
- 25 … + 60 °C<br />
- 13 … + 140 °F<br />
APPROVALS<br />
Read <strong>install</strong>ation instructions<br />
before connecting to mains www.interface.phoenixcontact.com<br />
U INDUSTRIAL<br />
F<br />
LISTED<br />
–25<br />
B<br />
CONTROL<br />
EQUIPMENT<br />
43KA<br />
EN 60950<br />
EN 60204<br />
EN 61558-2-17<br />
EN 61000-6-2<br />
EN 50081-1<br />
Fig. 2<br />
Low-profile <strong>install</strong>ation:<br />
Installation depth 1) 103 mm (+ mount. rail)<br />
1) (incl. 15 mm convection distance)<br />
15<br />
130<br />
Fig. 3<br />
4.2.1. Connecting cable:<br />
The device is equipped with COMBICON plug connectors. This reliable and easy-toassemble<br />
connection method enables a fast connection of devices and a visible isolation<br />
of the electric connection if necessary.<br />
Only plug in or unplug connectors in a power off state!<br />
You can connect the following cable cross sections:<br />
2<br />
Solid [mm ]<br />
2<br />
Stranded [mm ] AWG Torque [Nm]<br />
1 Input: 0.2-2.5 0.2-2.5 24-12 0.5 - 0.6<br />
22 Output: 0.2-2.5 0.2-2.5 24-12 0.5 - 0.6<br />
4 Signal: 0.2-2.5 0.2-2.5 24-12 0.5 - 0.6<br />
To achieve a reliable and shockproof connection:<br />
• Strip the connecting ends 8 mm<br />
(see Fig. 7)!<br />
4.2.2. Input (Fig.8)<br />
The 100-240 V AC connection is made using the L, N<br />
and 5 screw connections.<br />
Protection of the primary side<br />
The device must be <strong>install</strong>ed in acc. with the<br />
regulations as in EN 60 950. It must be possible to<br />
disconnect the device using a suitable isolating facility<br />
outside the power supply. The primary side line<br />
protection, for example, is suitable.<br />
No further device protection is necessary, since there<br />
is an internal fuse.<br />
Recommended backup fuse:<br />
Power circuit-breaker 10 A or 16 A, characteristic B (or identical function).<br />
In DC applications, a suitable backup fuse must be wired in!<br />
If the internal fuse is triggered, there is<br />
most probably a malfunction in the device.<br />
In this case, the device must be inspected<br />
in the factory!<br />
4.2.3. Output (Fig. 9)<br />
The 24 V DC connection is made using the "+" and "–"<br />
screw connections on screw connector 22 .<br />
At the time of delivery, the output voltage is 24 V DC.<br />
The output voltage can be set from 22.5 to 28.5 V DC<br />
on the potentiometer 5.<br />
8 mm<br />
Input<br />
AC 100-240V<br />
L N 5<br />
4 33<br />
13 14 DC<br />
OK<br />
+ + – –<br />
DC<br />
13 14 OK<br />
Output DC 24V 10A<br />
+ + – –<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Fig. 7<br />
Fig. 8<br />
22<br />
5<br />
Fig. 9<br />
15<br />
17
Protection of the secondary side:<br />
The device is electronically protected against short-circuit and idling. In the event of a<br />
malfunction, the output voltage is limited to 35 V DC.<br />
Make sure that all output lines are dimensioned according to the maximum output current<br />
or are separately protected!<br />
The cables on the secondary side should have large cross sections in order to keep the<br />
voltage drops on the lines as low as possible.<br />
4.3. Signaling<br />
The two DC OK outputs are for preventive monitoring of the functions of the power supply<br />
unit. A floating signal contact 44 and an active DC OK signal 3 are available. The DC OK<br />
LED 6 also enables evaluation of the function of the power supply directly on site.<br />
4.3.1. Floating contact (Fig.10)<br />
The floating signal contact opens and signalizes a drop in<br />
the output voltage as set of more than 10 %. Signals and<br />
ohmic loads of up to 30 V and currents of up to 1 A can be<br />
connected.<br />
For heavily inductive loads such as a relay, a suitable<br />
protection circuit (e.g. damping diode) is necessary.<br />
4.3.2. Active signal output (Fig. 11)<br />
The 24 V DC signal is applied between the "DC OK" and "–"<br />
connection terminal blocks and can carry up to 40 mA. This<br />
signal output signalizes when the output voltage is more<br />
than 10 % below the set output voltage by switching from<br />
"active high" to "low".<br />
The DC OK signal is decoupled from the power output. It is<br />
thus not possible for parallel switched devices to provide<br />
external supply.<br />
The 24 V DC signal can be directly connected to a logic input for evaluation.<br />
4.3.3. Signal loop (Fig.12)<br />
The two above-mentioned signal outputs can be easily combined.<br />
Example: Monitoring of two devices.<br />
Use the active signal output of device 1 and loop<br />
in the floating signal output of device 2. In the<br />
event of malfunctioning, a common alarm is<br />
output. Any number of devices can be looped in.<br />
This signal combination saves wiring costs and<br />
logic inputs.<br />
18<br />
20<br />
24 V DC<br />
40 mA<br />
13 14<br />
Output 24V DC<br />
DC OK<br />
+ + – –<br />
DC OK<br />
max.<br />
30 VAC/DC, 1 A Fig. 10<br />
13 14<br />
24 V DC<br />
40 mA<br />
Output 24V DC<br />
DC OK<br />
Device 1<br />
Output 24V DC<br />
13 14<br />
DC OK<br />
+ + – –<br />
DC OK<br />
+ + – –<br />
DC OK<br />
Fig. 11<br />
Device 2<br />
Outpu<br />
13 14<br />
Fig. 12<br />
5.3. Parallel operation<br />
Devices of the same type can be connected in parallel to enable both redundancy and an<br />
increase in efficiency. No other alignment is necessary when in the state of delivery.<br />
If the output voltage is adjusted, a uniform distribution of power is guaranteed by setting<br />
all parallel operated power supply units to exactly the same output voltage.<br />
To ensure symmetrical distribution of power, we recommend designing all cable<br />
connections from the power supply unit to a busbar of the same length and with the same<br />
conductor cross section.<br />
The system makes it advisable to <strong>install</strong> a protective circuit at the output of each device<br />
when more than two power supply units are connected in parallel (e.g. decoupling diode<br />
or DC fuse). This prevents high reverse feed currents in the event of a secondary device<br />
fault.<br />
5.3.1. Redundant operation (Fig. 15)<br />
Redundant circuits are suitable for the supply of<br />
systems which make especially high requirements on<br />
the operational safety. If a fault occurs in the primary<br />
circuit of the first power supply unit, the second device<br />
automatically takes over the entire power supply,<br />
without interruption, and vice versa.<br />
For this reason, the power supply units to be<br />
connected in parallel are dimensioned in such a way<br />
that the total current requirement of all consumers can<br />
be completely covered by one power supply unit.<br />
100% redundancy makes external decoupling diodes necessary!<br />
5.3.2. Increased capacity (Fig. 16)<br />
For n parallel connected devices, the output current<br />
can be increased to n x I N .<br />
Parallel connection to increase efficiency is used for<br />
the expansion of existing systems. It is advisable to use<br />
parallel connection if the power supply unit does not<br />
cover the current requirement of the most powerful<br />
consumer. Otherwise the consumers should be spread<br />
among individual devices independent of one another.<br />
A maximum of five devices can be connected in parallel!<br />
QUINT QUINT<br />
10 A + – 10 A + –<br />
+<br />
–<br />
+ –<br />
DC OK<br />
Σ = 10 A<br />
Fig. 15<br />
QUINT QUINT<br />
10 A + – 10 A + –<br />
+<br />
–<br />
+ –<br />
Σ = 20 A<br />
Fig. 16<br />
4.3.4. DC OK LED<br />
The green DC OK LED enables evaluation of the function locally in the control cabinet.<br />
LED lit Normal operation of the power supply<br />
LED flashes The set output voltage has dropped by more than 10 %.<br />
There is a secondary consumer short-circuit or overload outside the<br />
POWER BOOST area.<br />
LED off There is no mains voltage or there is a device fault.<br />
5. Function<br />
5.1. Output characteristic curve<br />
In the case of ambient temperatures Tamb < +40°C,<br />
the device can continuously supply 15 A with 24 V<br />
DC output voltage (Pamb = 360 W).<br />
In the event of a higher load, the operating point<br />
follows the U/I characteristic curve depicted in<br />
Fig. 13. The output current is limited to IBOOST. The secondary voltage is reduced until the short<br />
circuit on the secondary side has been remedied.<br />
The U/I characteristic curve ensures that both<br />
heavily capacitive loads and devices with DC/DC<br />
converters in the primary circuit can be fed without<br />
problems using QUINT POWER.<br />
Downstream fuses are triggered reliably. Selectivity in the design of your system is<br />
guaranteed at all times.<br />
5.2. Thermal behavior<br />
With an ambient temperature of up to +40°C, the<br />
device supplies a continuous output current of 15 A.<br />
The device can supply a nominal output current of<br />
10 A with ambient temperatures of up to +60°C.<br />
In the case of ambient temperatures above +60°C,<br />
the output capacity has to be reduced by 2.5% per<br />
Kelvin increase in temperature.<br />
UOUT<br />
[V]<br />
UN 24<br />
< 60 °C<br />
240 W<br />
15<br />
IBOOST<br />
The device does not switch off at ambient<br />
temperatures of +70°C or thermal overload. The<br />
Fig. 14<br />
output capacity is reduced as far as necessary to<br />
provide device protection. After it has cooled down, the output capacity is increased<br />
again.<br />
Output current [A]<br />
15<br />
10<br />
10<br />
IN<br />
< 40 °C<br />
U OUT = 24 V<br />
360 W<br />
0<br />
0 20 40 60<br />
Ambient temperature [°C]<br />
IOUT<br />
[A]<br />
Fig. 13<br />
6. Technical data QUINT-PS-100-240AC/24DC/10<br />
Order No.<br />
Input data 1<br />
29 38 60 4<br />
Nominal input voltage 100-240 V AC (Wide-range input)<br />
Input voltage range 85-264 V AC 90 - 350 V DC<br />
Frequency 45-65 Hz 0 Hz<br />
Current consumption (at nom. values)<br />
Inrush current limitation / I<br />
approx. 2.4 A (120 V AC) / 1.3 A (230 V AC)<br />
2t (+25°C) approx. 15 A / 1.5 A2 Mains buffering<br />
s<br />
at nominal load (typ.) > 40 ms (120 V AC) / > 40 ms (230 V AC)<br />
Turn-on time after applying the mains<br />
voltage<br />
88 % (at 230 V AC and nominal values)<br />
Ascent time Uout (10 % - 90 %) 10 ms, typical<br />
Residual ripple / peak switching<br />
voltages (20 MHz)<br />
Can be connected in parallel<br />
< 100 mVpp (at nominal values)<br />
for redundancy and increased capacity<br />
Surge voltage protection against<br />
internal surge voltages<br />
yes, limited to approx. 35 V DC<br />
Resistance to reverse feed<br />
Signal output data<br />
35 V DC<br />
DC OK 3 active:<br />
+24 V DC signal (with regard to equip. dim.)<br />
(Uout > 0.9 x UN = High signal)<br />
max. 40 mA<br />
DC OK 4 floating:<br />
max. 30 V AC/DC; max. 1 A<br />
(Uout > 0.9 x UN = contact closed)<br />
LED 6 (Uout < 0.9 x UN = LED flashes) LED green<br />
19<br />
21
General data<br />
Isolation voltage input/output<br />
input / PE<br />
output / PE<br />
Approval package<br />
22<br />
6. Technical data QUINT-PS-100-240AC/24DC/10<br />
4 kV AC (type test)/2 kV AC (routine test)<br />
3.5 kV AC (type test)/2 kV AC (routine test)<br />
500 V DC (routine test)<br />
Electrical equipment of machines EN 60 204 (Surge voltage category III)<br />
Safety transformers for switched-mode<br />
power supply units<br />
EN 61 558-2-17<br />
Electrical safety (of information<br />
technology equipment)<br />
EN 60950 / VDE 0805,<br />
UL/C-UL Recognized UL 60 950 u 1)<br />
Industrial regulating devices 1)<br />
UL/C-UL Listed UL 508 U<br />
LISTED<br />
Shipbuilding German Lloyd F<br />
Electronic equip. for use in electr. power<br />
inst. and assembly in electr. power inst.<br />
EN 50 178 (VDE 0160)<br />
Protective low voltage PELV (EN 60 204)<br />
SELV (EN 60 950)<br />
Safe isolation VDE 0100-410<br />
Protection against electric shock DIN 57 100-410<br />
Protection against shock currents, basic<br />
requirements for protective separation<br />
in electrical equipment<br />
DIN VDE 0106-101<br />
Limitation of mains harmonic currents acc. to EN 61 000-3-2<br />
Installation position on horizontal NS 35 mounting rail in acc. with<br />
EN 50 022<br />
Degree of protection IP 20<br />
Class of protection Ι, with PE connection<br />
MTBF > 500 000 h in acc. with IEC 1709 (SN 29 500)<br />
Type of housing AluNox (AlMg1), enclosed<br />
Dimensions (W x H x D) State of delivery: 90° turned:<br />
(85 x 130 x 125) mm (122 x 130 x 160) mm<br />
Weight approx. 1.3 kg<br />
Climatic data<br />
Ambient temperature operation<br />
storage<br />
CB<br />
scheme<br />
-25°C to +70°C (> +60°C derating)<br />
-40°C to +85°C<br />
Humidity up to 95% at +25°C, no condensation<br />
Vibration in acc. with IEC 68-2-6 < 15 Hz, amplitude ± 2.5 mm<br />
15 Hz-150 Hz, 2.3 g,<br />
90 min. in resonant frequency<br />
Shock in acc. with IEC 68-2-27 30 g in all directions<br />
Contamination class 2 (in acc. with EN 50 178)<br />
Climatic class 3K3 (in acc. with EN 60 721)<br />
1) UL approval for AC input voltage and ambient temperature up to +70°C (+158°F)<br />
B<br />
c<br />
in conformance with EMC guideline 89/336/EEC<br />
and low voltage directive 73/23/EEC<br />
EMC (electromagnetic compatibility) Requirements<br />
Immunity to interference acc. to EN 61000-6-2 EN 61 000-6-2<br />
EN 61000-4-2 2)<br />
Housing<br />
• Discharge of static Contact discharge: 4 kV<br />
electricity (ESD) Discharge in air: 8 kV<br />
EN 61000-4-3 1)<br />
Housing<br />
• Electromagnetic Frequency: 80-1000 MHz<br />
HF field<br />
Field intensity: 10 V/m<br />
EN 61000-4-4 2)<br />
• Fast transients<br />
(Burst):<br />
Input:<br />
Output:<br />
Signal:<br />
2 kV asymmetrical 4)<br />
2 kV asymmetrical4) 1 kV asymmetrical4) EN 61000-5-4 2)<br />
• Surge voltage capacities<br />
(Surge):<br />
Input:<br />
Output:<br />
Signal:<br />
2 kV asymmetrical4) 1 kV symmetrical3) 0.5 kV asymmetrical 4)<br />
0.5 kV symmetrical 3)<br />
1 kV asymmetrical 4)<br />
EN 61000-4-6 1)<br />
I/O/S:<br />
asymmetrical<br />
• Conducted disturbance Frequency:<br />
Uo: 4)<br />
0.15-80 MHz<br />
10 V<br />
EN 61000-11-4 2) Input: 30% reduction in output<br />
• Voltage dips<br />
voltage for 0.5 periods<br />
ENV 50204<br />
• Simulation mobile phones<br />
Frequency:<br />
Field intensity:<br />
QUINT-PS-100-240AC/<br />
24DC/10<br />
Level 4<br />
8 kV<br />
15 kV<br />
Level 3<br />
80-1000 MHz/1.4-2.0 GHz<br />
10 V/m<br />
4 kV (Level 4)<br />
2 kV (Level 3)<br />
1 kV (Level 2)<br />
4 kV (Inst. class 4)<br />
2 kV (Inst. class 4)<br />
0.5 kV (Level 1)<br />
0.5 kV (Level 1)<br />
1 kV (Level 2)<br />
Level 3<br />
0.15-80 MHz<br />
10 V<br />
see input data: Mains<br />
buffering > 20 ms<br />
not required 900 MHz/1800 MHz<br />
20 V/m<br />
Noise emission acc. to EN 50081-2<br />
• Emitted radio<br />
EN 55011<br />
interference<br />
class A 5)<br />
• Radio interference<br />
EN 55011<br />
voltage<br />
class A 5)<br />
EN 55011 corresponds to CISPR11 / EN 55022 corresponds to CISPR22<br />
EN 61000 corresponds to IEC 1000<br />
EN 55011 (EN 55022)<br />
class B 6)<br />
EN 55011 (EN 55022)<br />
class B 6)<br />
1) Criterion A: Normal operating behavior within the defined limits.<br />
2)<br />
Criterion B: Temporary impairment to operational behavior that is corrected by the device<br />
itself.<br />
3) Symmetrical: Conductor to conductor.<br />
4)<br />
Asymmetrical: Conductor to ground.<br />
5)<br />
Class A: Area of application industry<br />
6) Class B: Area of application industry and residential<br />
23
Alimentation à découpage primaire universelle<br />
QUINT-PS-100-240AC/24DC/10<br />
Référence: 29 38 60 4<br />
1. QUINT POWER vous offre :<br />
• une utilisation universelle grâce à une plage étendue de tensions d'entrée<br />
• une sécurité de fonctionnement élevée même sur des réseaux globaux difficiles<br />
• POWER BOOST - réserve de puissance pour des charges difficiles<br />
• une surveillance fonctionnelle préventive par une signalisation professionnelle<br />
2. Vue du module, éléments de connexion et de commande selon la fig. 1:<br />
1 Entrée AC :<br />
Tension d’entrée<br />
85-264 V AC<br />
Fréquence 45-65 Hz<br />
(0,2 mm 2 à 2,5 mm 2 rigide)<br />
(0,2 mm 2 à 2,5 mm 2 souple)<br />
(AWG 24-12)<br />
Fusible interne 6,3 AT<br />
Fusible amont recommandé<br />
disjoncteur de circuit 10 A ou<br />
16 A / Caractéristique B<br />
3. Conseils de sécurité et avertissements<br />
Pour garantir un fonctionnement fiable du module et pouvoir utiliser toutes ses<br />
fonctions, veuillez lire la présente notice dans son intégralité !<br />
Les QUINT POWER sont des modules à encastrer. Leur <strong>install</strong>ation et leur mise en<br />
service ne doivent être confiées qu'à un personnel spécialisé dûment qualifié. Il faut par<br />
ailleurs respecter les normes nationales spécifiques applicables (par exemple NF, etc.).<br />
Il faut en particulier, avant la mise en service, s'assurer que<br />
• la connexion au réseau est réalisée selon les règles et que la protection contre les<br />
chocs électriques est assurée !<br />
• l'appareil peut être mis hors tension selon les dispositions de la norme EN 60950 en<br />
dehors de l'alimentation (par ex. via le disjoncteur du circuit côté primaire) !<br />
• le conducteur de protection est raccordé !<br />
• toutes les lignes d'arrivée sont suffisamment dimensionnées et protégées !<br />
• toutes les lignes de sortie sont dimensionnées pour l'intensité max. de sortie de l'appareil<br />
ou protégées par un fusible spécial !<br />
• la convection est suffisante !<br />
Selon la température ambiante et la sollicitation du module, la température du boîtier<br />
peut atteindre des valeurs élevées !<br />
Le module contient des éléments présentant une tension dangereuse et une forte<br />
accumulation d'énergie !<br />
24<br />
26<br />
FRANÇAIS<br />
2 Sortie DC :<br />
Tension de sortie<br />
24 V DC (préréglée),<br />
de 22,5 - 28,5 V DC réglable<br />
via potentiomètre 5<br />
(0,2 mm2 à 2,5 mm2 rigide)<br />
(0,2 mm 2 à 2,5 mm 2 3 Sortie DC OK active<br />
souple)<br />
44 Sortie DC OK<br />
indépend. du potentiel<br />
5 Potentiomètre (recouvert)<br />
22,5 - 28,5 V DC<br />
6 Témoin DC OK<br />
(AWG 24-12)<br />
77 Adaptateur pour profilé<br />
Ce module est protégé contre<br />
la marche à vide et les courtscircuits.<br />
universel UTA 107<br />
Attention : Ne jamais travailler sur un module sous tension !<br />
Danger de mort !<br />
4.1.2. Montage faible largeur<br />
Le module est livré départ usine pour être monté<br />
dans un emplacement étroit.<br />
Montage :<br />
Posez le module en plaçant le dispositif<br />
de guidage pour le profilé sur le<br />
bord supérieur du profilé et encliquetez-le<br />
vers le bas (Fig. 4a).<br />
Démontage : Tirez la fixation à ressort vers le haut<br />
à l'aide d'un tournevis et décrochez le<br />
module du bord inférieur du profilé<br />
(Fig. 4b).<br />
4.1.3. Montage faible hauteur<br />
Vous obtiendrez un montage de faible hauteur en tournant le module à 90° par rapport au<br />
profilé. Pour cela, montez l'adaptateur (UTA 107) 77 comme cela est décrit dans la fig. 5<br />
(Vis "Torx" T10, couple de serrage 0,8 - 0,9 Nm).<br />
Vous n'avez besoin d'aucun autre accessoire.<br />
4.2. Raccordement<br />
Types de réseaux : Réseaux 100-240 V AC<br />
Système TN-S Système TN-C Système TT<br />
L N PE<br />
QUINT<br />
+ –<br />
L<br />
N<br />
PE<br />
L N PE<br />
QUINT<br />
+ –<br />
L<br />
PEN<br />
L N PE<br />
QUINT<br />
+ –<br />
Fig. 6a Fig. 6b Fig. 6c<br />
L<br />
N<br />
Fig. 4a<br />
Fig. 4b<br />
Fig. 5<br />
4. Installation<br />
4.1. Montage<br />
Cette alimentation s'encliquette sur tous les profilés<br />
EN 50022-35 et doit être montée verticalement<br />
(blocs de jonction d'entrée vers le bas).<br />
4.1.1. Cotes de montage<br />
290<br />
Pour garantir un refroidissement par<br />
convection suffisant, nous recommandons<br />
de respecter les distances<br />
minimales suivantes avec les autres<br />
modules :<br />
8,0 cm dans le sens vertical et<br />
1,5 cm dans le sens horizontal.<br />
Montage faible largeur :<br />
Prof. montage 125 mm (+ profilé)<br />
145<br />
80<br />
15<br />
QUINT POWER<br />
115 15 15 152<br />
85 122<br />
DC<br />
13 14 OK + + – –<br />
Output DC 24V 10A<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Input<br />
AC 100-240V<br />
L N 5<br />
QUINT POWER<br />
13 14 DC<br />
OK<br />
+ + – –<br />
DC<br />
13 14 OK<br />
Output DC 24V 10A<br />
+ + – –<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Input<br />
AC 100-240V<br />
L N 5<br />
- 25 … + 60 °C<br />
- 13 … + 140 °F<br />
APPROVALS<br />
Read <strong>install</strong>ation instructions<br />
before connecting to mains www.interface.phoenixcontact.com<br />
U INDUSTRIAL<br />
F<br />
LISTED<br />
–25<br />
B<br />
CONTROL<br />
EQUIPMENT<br />
43KA<br />
EN 60950<br />
EN 60204<br />
EN 61558-2-17<br />
EN 61000-6-2<br />
EN 50081-1<br />
Fig. 2<br />
Montage faible hauteur :<br />
Prof. montage 1) 103 mm (+ profilé)<br />
1) (incl. 15 mm distance de convection)<br />
15<br />
130<br />
Fig. 3<br />
4.2.1. Câble de liaison :<br />
Le module est équipé de connecteurs MINICONNEC. Ce mode de raccordement fiable<br />
et pratique permet un raccordement rapide des modules et, au besoin, une déconnexion<br />
visible de la liaison électrique.<br />
Les connecteurs ne doivent être manipulés que hors tension !<br />
Vous pouvez raccorder des câbles avec les sections suivantes :<br />
2<br />
Rigide [mm ]<br />
2<br />
Souple [mm ] AWG Couple de serrage [Nm]<br />
1 Entrée : 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />
22 Sortie : 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />
4 Signal : 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />
Pour un raccordement fiable et protégé contre les<br />
contacts fortuits :<br />
• Dénuder les extrémités à raccorder sur 8 mm (v. Fig. 7)!<br />
4.2.2. Entrée (Fig. 8)<br />
Pour le raccordement 100-240 V AC on utilise les connexions<br />
à vis L, N et 5 .<br />
Protection du côté primaire<br />
Installez le module conformément aux dispositions de<br />
la norme EN 60 950. Il doit pouvoir être mis hors tension<br />
au moyen d'un dispositif de sectionnement approprié<br />
en dehors de l'alimentation. Par exemple à<br />
l'aide du disjoncteur du circuit côté primaire.<br />
Il est inutile de prévoir une autre protection, puisque<br />
le module comporte un fusible interne.<br />
Fusible amont recommandé :<br />
Disjoncteur de protection 10 A ou 16 A, caractéristique B (ou équivalent).<br />
Pour les applications DC, prévoir un fusible adéquat en amont !<br />
Le déclenchement du fusible interne traduit<br />
très probablement un défaut au niveau<br />
du module.<br />
Dans ce cas, il convient de faire contrôler le<br />
module en usine !<br />
4.2.3. Sortie (Fig. 9)<br />
Le raccordement 24 V DC se fait via les connexions<br />
vissées "+" et "–" sur la borne à vis 22 .<br />
A la livraison, la tension de sortie est réglée sur 24 V<br />
DC. Le potentiomètre 5 permet de la régler de 22,5<br />
à 28,5 V DC.<br />
8 mm<br />
Input<br />
AC 100-240V<br />
L N 5<br />
4 33<br />
13 14 DC<br />
OK<br />
+ + – –<br />
DC<br />
13 14 OK<br />
Output DC 24V 10A<br />
+ + – –<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Fig. 7<br />
Fig. 8<br />
22<br />
5<br />
Fig. 9<br />
25<br />
27
Protection du côté secondaire :<br />
Le module est doté d'une protection électronique contre les courts-circuits et la marche<br />
à vide. En cas de défaut, la tension de sortie est limitée à 35 V DC.<br />
Il convient de s'assurer que toutes les lignes de sortie sont dimensionnées en fonction du<br />
courant de sortie max. ou qu'elles sont protégées par un fusible spécial.<br />
Du côté secondaire, choisir des câbles de grande section, afin de réduire au minimum les<br />
chutes de tension sur les lignes.<br />
4.3. Signalisation<br />
Les deux sorties DC OK permettent de surveiller le bon fonctionnement de l'alimentation.<br />
On dispose d'un contact de signalisation 4 et d'un signal DC OK actif 3. En outre, la<br />
LED DC OK 6 permet de contrôler le fonctionnement de l'alimentation directement sur<br />
place.<br />
4.3.1. Contact indépendant du potentiel (Fig. 10)<br />
L'ouverture du contact de signalisation indépendant du potentiel<br />
indique que la tension de sortie est inférieure de plus<br />
de 10 % à la tension réglée. Le module accepte des signaux<br />
et des charges ohmiques jusqu'à 30 V et des intensités<br />
jusqu'à 1 A max.<br />
Pour les charges fortement inductives, tel un relais, il est<br />
nécessaire de prévoir un circuit de protection approprié<br />
(par ex. une diode de roue-libre).<br />
4.3.2. Sortie signal active (Fig. 11)<br />
Le signal 24 V DC est situé entre les bornes "DC OK" et "–"<br />
et supporte des charges jusqu'à 40 mA. Lorsqu'elle passe<br />
de "active high" à "low", cette sortie de signal indique que la<br />
tension de sortie est inférieure de plus de 10 % à la tension<br />
réglée.<br />
Le signal DC OK est découplé de la sortie Puissance. On<br />
exclut ainsi les risques d'une alimentation extérieure via des<br />
modules branchés en parallèle.<br />
Le signal 24 V DC peut être raccordé directement à une entrée TOR d’automate.<br />
4.3.3. Boucle de signal (Fig. 12)<br />
Les deux sorties de signal ci-dessus peuvent être facilement combinées.<br />
Exemple : Surveillance de deux modules.<br />
Utilisez la sortie signalisation active du module 1<br />
et bouclez une ligne depuis la sortie de signalisation<br />
indépendante du potentiel du module 2. En<br />
cas de dysfonctionnement, vous obtenez une signalisation<br />
défaut groupée. Vous pouvez boucler<br />
en ligne un nombre quelconque de modules.<br />
Cette combinaison de signaux économise des<br />
frais de câblage et des entrées logiques.<br />
28<br />
30<br />
24 V DC<br />
40 mA<br />
13 14<br />
Output 24V DC<br />
DC OK<br />
+ + – –<br />
DC OK<br />
max.<br />
30 VAC/DC, 1 A Fig. 10<br />
13 14<br />
24 V DC<br />
40 mA<br />
Output 24V DC<br />
DC OK<br />
Module 1<br />
Output 24V DC<br />
13 14<br />
DC OK<br />
+ + – –<br />
DC OK<br />
+ + – –<br />
DC OK<br />
Fig. 11<br />
Module 2<br />
Outpu<br />
13 14<br />
Fig. 12<br />
5.3. Fonctionnement en parallèle<br />
Des modules de même type peuvent être branchés en parallèle pour réaliser un circuit<br />
redondant ou augmenter la puissance. Cela ne nécessite aucun réglage supplémentaire<br />
des modules sortant d'usine.<br />
Si vous ajustez la tension de sortie, le courant sera réparti de façon équilibrée grâce à un<br />
réglage précis de toutes les alimentations fonctionnant en parallèle sur une même tension<br />
de sortie.<br />
Pour une répartition symétrique du courant, nous conseillons de réaliser toutes les<br />
liaisons de câbles de l'alimentation vers une barre omnibus avec la même longueur et la<br />
même section !<br />
Compte tenu du système, si vous montez en parallèle plus de deux alimentations, il faut<br />
prévoir un circuit de protection à chaque sortie des modules (par ex. une diode de découplage<br />
ou fusible DC). Ainsi, en cas de défaut sur le secondaire du module, vous éviterez<br />
des courant d'alimentation élevés arrivant de l'amont.<br />
5.3.1. Fonctionnement en redondance (Fig. 15)<br />
Les circuits redondants sont préconisés pour l'alimentation<br />
d'<strong>install</strong>ations soumises à des exigences<br />
particulièrement élevées de fiabilité de fonctionnement.<br />
En cas de défaut dans le circuit primaire de la<br />
première alimentation, le second module prend immédiatement<br />
le relais pour assurer l'alimentation intégrale<br />
sans interruption, et vice-versa.<br />
Pour cela, les alimentations à brancher en parallèle<br />
doivent être dimensionnés de manière qu'un seul module<br />
puisse couvrir intégralement la demande totale<br />
en courant de tous les appareils consommateurs.<br />
Une redondance à 100 % nécessite des diodes de découplage externes !<br />
5.3.2. Augmentation de puissance (Fig. 16)<br />
Avec n modules branchés en parallèle, le courant de<br />
sortie peut être augmenté jusqu'à n x I N .<br />
Ce montage en parallèle pour augmenter la puissance<br />
s'utilise en cas d'extension d'<strong>install</strong>ations existantes.<br />
Cette solution est recommandée lorsque l'alimentation<br />
ne couvre pas la demande en courant du consommateur<br />
le plus puissant. Sinon, il faut répartir les appareils<br />
sur différents modules indépendant les uns des autres.<br />
Vous pouvez brancher en parallèle cinq modules au<br />
maximum !<br />
QUINT QUINT<br />
10 A + – 10 A + –<br />
+<br />
–<br />
+ –<br />
DC OK<br />
Σ = 10 A<br />
Fig. 15<br />
QUINT QUINT<br />
10 A + – 10 A + –<br />
+<br />
–<br />
+ –<br />
Σ = 20 A<br />
Fig. 16<br />
4.3.4. LED DC OK<br />
La LED verte DC OK permet de vérifier le fonctionnement directement sur l'armoire.<br />
LED allumée L'alimentation fonctionne normalement<br />
La LED clignote<br />
La tension de sortie est inférieure de plus de 10 % à la tension réglée.<br />
Court-circuit de la charge secondaire ou surcharge en dehors de la plage<br />
du POWER BOOST.<br />
LED éteinte Absence de tension du réseau ou module défectueux.<br />
5. Fonctionnement<br />
5.1. Courbe de sortie<br />
Pour des températures ambiantes Tamb < +40 °C,<br />
le module peut débiter en continu 15 A pour une<br />
tension de sortie 24 V DC (Pab = 360 W).<br />
Pour une charge plus élevée, le point de travail suit<br />
la courbe U/I de la fig. 13. Le courant de sortie est<br />
limité à IBOOST. La tension secondaire est diminuée tant que le<br />
court-circuit du côté secondaire n'est pas éliminé.<br />
Cette courbe U/I garantit que QUINT-POWER peut<br />
alimenter sans problèmes aussi bien de fortes<br />
charges capacitives que des appareils équipés de<br />
convertisseurs DC/DC dans le circuit d’entrée.<br />
Le déclenchement des fusibles en aval est assuré de façon fiable. La sélectivité structurelle<br />
de votre <strong>install</strong>ation est ainsi garantie en permanence.<br />
5.2. Comportement en fonction de la<br />
température<br />
Pour une température ambiante de +40 °C max., le<br />
module fournit en continu un courant de sortie de<br />
15 A.<br />
Il peut débiter le courant de sortie nominal de 10 A<br />
jusqu'à une température ambiante de +60 °C.<br />
Au-delà de +60 °C, la puissance de sortie doit être<br />
réduite de 2,5 % pour chaque élévation d'un Kelvin<br />
de la température.<br />
UOUT<br />
[V]<br />
UN24<br />
24<br />
UN<br />
< 60 °C<br />
< 60 °C<br />
240 240 W 360 360 W W<br />
< 40 °C<br />
< 40 °C<br />
10 15<br />
IOUT<br />
IN10<br />
IBOOST 15<br />
[A] IOUT<br />
IN IBOOST<br />
[A]<br />
Fig. 13<br />
Fig. 13<br />
0<br />
0 20 40 60<br />
Température ambiante [°C]<br />
Si les températures ambiantes dépassent +70 °C<br />
ou en cas de surcharge thermique, le module ne s'arrête pas. La puissance de sortie est<br />
réduite jusqu'à l'obtention d'une protection du module. Après un temps de refroidissement,<br />
la puissance de sortie augmente de nouveau.<br />
Courant sortie [A]<br />
15<br />
10<br />
U OUT = 24 V<br />
Fig. 14<br />
6. Caractéristiques techniques QUINT-PS-100-240AC/24DC/10<br />
Référence<br />
Entrée 1<br />
29 38 60 4<br />
Tension nominale d'entrée 100 - 240 V AC (plage étendue)<br />
Plage de tensions d'entrée 85 - 264 V AC 90 - 350 V DC<br />
Fréquence 45 - 65 Hz 0 Hz<br />
Courant absorbé (pour valeurs nom.)<br />
Limit. courant démarrage / I<br />
env. 2,4 A (120 V AC) / 1,3 A (230 V AC)<br />
2t (+25 °C) env. 15 A / 1,5 A2 Protection contre microcoupures<br />
s<br />
pour charge nom. (typ.) > 40 ms (120 V AC) / > 40 ms (230 V AC)<br />
Durée démarrage après connexion de la<br />
tension réseau<br />
< 1 s<br />
Protection contre les transitoires Varistance<br />
Fusible d'entrée, interne 6,3 AT (protection appareil)<br />
Fusible amont recommandé Disjoncteur de protection circuit<br />
10 A ou 16 A, caractéristique B (EN 60 898)<br />
Courant de décharge vers PE<br />
Sortie 2<br />
< 3,5 mA<br />
Tension nominale UN / tolérance 24 V DC / ± 1 %<br />
Plage de réglage de la tension de sortie 22,5 - 28,5 V DC<br />
Courant sortie (refroidis. par convection):<br />
•POWER BOOST IBOOST -25 à +40 °C<br />
•Intensité nominale IN -25 à +60 °C<br />
15 A (U out = 24 V DC)<br />
10 A (U out = 24 V DC)<br />
Derating à partir de +60 °C 2,5 % par Kelvin<br />
Limit. intensité en cas court-circuit env. I BOOST ≈ 15 A<br />
Démarrage charges capacitives. illimité<br />
Ecart de réglage pour :<br />
•Modif. charge statique 10 - 90 %<br />
•Modif. charge dynamique 10 - 90 %<br />
•Modification tension d'entrée ± 10 %<br />
typ. < 1 %<br />
typ. < 2 %<br />
typ. < 0,1 %<br />
Dissip. puis. max. : vide/charge nom. env. 4 W / 33 W<br />
Rendement > 88 % (230V AC et valeurs nom.)<br />
Temps établis. Uout (10 %-90 %) typ. 10 ms<br />
Ondul. rés./pointes commut. (20 MHz )<br />
Montage en parallèle<br />
< 100 mVc-c (pour valeurs nominales)<br />
pour redondance / augment. de puissance<br />
Protection contre surtensions internes oui, limitée à env. 35 V DC<br />
Protection c. courants d'amont<br />
Sortie signal<br />
35 V DC<br />
DC OK 33 actif :<br />
Signal +24 V DC (rapport à masse appareil)<br />
(Uout > 0,9 x UN = signal "High") 40 mA max.<br />
DC OK 4 indép. potentiel :<br />
(Uout > 0,9 x UN = contact fermé)<br />
max. 30 V AC/DC; max. 1 A<br />
LED 66 (Uout < 0,9 x UN = LED clignote) LED verte<br />
29<br />
31
Autres caractéristiques<br />
Tension d'isolement entrée/sortie<br />
Entrée / PE<br />
Sortie / PE<br />
Homologations<br />
32<br />
6. Caractéristiques techniques QUINT-PS-100-240AC/24DC/10<br />
4 kV AC (essai de type)/2 kV AC (essai indiv.)<br />
3,5 kV AC (essai de type)/2 kV AC (essai indiv.)<br />
500 V DC (essai individuel)<br />
Equipement électrique des machines EN 60 204 (catégorie de surtension III)<br />
Transformateurs de sécurité pour<br />
éléments réseaux de distribution<br />
EN 61 558-2-17<br />
Sécurité électrique des matériels de<br />
traitements de l'information<br />
EN 60950 / VDE 0805,<br />
UL/C-UL Recognized UL 60 950 u 1)<br />
Dispositif de réglage industriel<br />
1)<br />
UL/C-UL Listed UL 508 U<br />
LISTED<br />
Constructions navales Germanischer Lloyd F<br />
Equipement électronique des <strong>install</strong>ations<br />
à courant fort<br />
EN 50 178 (VDE 0160)<br />
Faible tension de protection PELV (EN 60 204)<br />
SELV (EN 60 950)<br />
Isolement sécurisé VDE 0100-410<br />
Protection contre le choc électrique DIN 57 100-410<br />
Protection contre les courants dangereux,<br />
Exigences fondamentales pour un isolement<br />
sûr dans les équipements électr.<br />
DIN VDE 0106-101<br />
Limites pour les émissions de courants<br />
harmoniques<br />
d'après EN 61 000-3-2<br />
Emplacement pour le montage sur profilé horizontal NS 35 selon EN 50 022<br />
Degré de protection IP 20<br />
Classe de protection : Ι, avec connexion PE<br />
MTBF > 500 000 h selon CEI 1709 (SN 29 500)<br />
Boîtier isolant AluNox (AlMg1), fermé<br />
Dimensions (l x H x P) Etat sortie d’usine : tourné de 90 ° :<br />
(85 x 130 x 125) mm (122 x 130 x 160) mm<br />
Poids env. 1,3 kg<br />
Caractéristiques climatiques<br />
Température ambiante service<br />
stockage<br />
CB<br />
scheme<br />
-25 °C à +70 °C (> +60 °C Derating)<br />
-40 °C à +85 °C<br />
Humidité jusq. 95 % à +25 °C, sans condensation<br />
Vibration selon CEI 68-2-6 < 15 Hz, Amplitude ± 2,5 mm<br />
15 Hz-150 Hz, 2,3 g,<br />
90 min. à la fréquence de résonance<br />
Choc selon CEI 68-2-27 30 g dans toutes les directions spatiales<br />
Degré de pollution 2 (selon EN 50 178)<br />
Classe d'atmosphère 3K3 (selon EN 60 721)<br />
1) Homologation UL pour tension d'entrée AC et température ambiantejusqu'à<br />
+70 °C (+158 °F)<br />
B<br />
c<br />
Conforme à la directive CEM 89/336/CEE<br />
et à la directive basse tension 73/23/CEE<br />
CEM (Compatibilité électromagnétique) Exigences<br />
QUINT-PS-100-240AC/<br />
immunité selon EN 61000-6-2<br />
EN 61 000-6-2 24DC/10<br />
EN 61000-4-2 2)<br />
Boîtiers<br />
Niveau 4<br />
• Décharge électrostati- par contact : 4 kV<br />
8 kV<br />
que (ESD)<br />
dans l'air : 8 kV<br />
15 kV<br />
EN 61000-4-3 1)<br />
Boîtiers<br />
Niveau 3<br />
• Champ magnétique HF Fréquence : 80-1000 MHz<br />
80-1000 MHz/1,4-2,0GHz<br />
intensité champ : 10 V/m<br />
10 V/m<br />
EN 61000-4-4 2)<br />
• Transitoires électriques<br />
rapides (en salves)<br />
Entrée :<br />
Sortie :<br />
Signal :<br />
2 kV asymétrique 4)<br />
2 kV asymétrique 4)<br />
1 kV asymétrique 4)<br />
4 kV (Niveau 4)<br />
2 kV (Niveau 3)<br />
1 kV (Niveau 2)<br />
EN 61000-4-5 2)<br />
• Ondes de choc (Surge) :<br />
Entrée :<br />
Sortie :<br />
Signal :<br />
2 kV asymétrique 4)<br />
1 kV symétrique 3)<br />
0,5 kV asymétrique 4)<br />
0,5 kV symétrique3) 1 kV asymétrique4) 4 kV (classe d'inst. 4)<br />
2 kV (classe d'inst. 4)<br />
0,5 kV (Niveau 1)<br />
0,5 kV (Niveau 1)<br />
1 kV (Niveau 2)<br />
EN 61000-4-6 1)<br />
E/S/A :<br />
asymétrique<br />
• Perturbations conduites Fréquence :<br />
Uo :<br />
4)<br />
Niveau 3<br />
0,15-80 MHz<br />
0,15-80 MHz<br />
10 V<br />
10 V<br />
EN 61000-4-11 2) Entrée : Réduction de 30 % de voir entrée : Protection<br />
• Creux de tension<br />
la tension de sortie pour contre micro-coupures<br />
demi-périodes > 20 ms<br />
ENV 50204<br />
Fréquence : non requises 900 MHz/ 1800 MHz<br />
• Simulation téléph. mobiles intensité champ :<br />
20 V/m<br />
Emission selon EN 50081-2<br />
• Perturbations radioélectriques<br />
EN 55011<br />
Classe A 5)<br />
EN 55011 (EN 55022)<br />
Classe B 6)<br />
• Tension perturbatrice<br />
radioélectrique<br />
EN 55011<br />
Classe A 5)<br />
EN 55011 (EN 55022)<br />
Classe B 6)<br />
EN 55011 correspond à CISPR11 / EN 55022 correspond à CISPR22<br />
EN 61000 correspond à CEI 1000<br />
1) Critère A : Fonctionnement normal à l'intérieur de limites déterminées.<br />
2)<br />
Critère B : Perturbation provisoire du fonctionnement,<br />
que le module corrige de lui-même.<br />
3) symétrique : ligne contre ligne.<br />
4) asymétrique : ligne contre terre.<br />
5)<br />
Classe A : Secteur d'application Industrie.<br />
6) Classe B : Secteur d'application Industrie et zone résidentielle.<br />
33
Fuente de alimentación conmutada en primario, para empleo universal<br />
QUINT-PS-100-240AC/24DC/10<br />
Código: 29 38 60 4<br />
1. QUINT POWER ofrece:<br />
• Empleo a escala mundial mediante amplio rango de entrada<br />
• Alta seguridad de servicio también en redes globales difíciles<br />
• POWER BOOST - reserva de potencia para cargas difíciles<br />
• Control funcional preventivo mediante señalización profesional<br />
2. Vista del módulo, conexiones, elementos de operación según Fig. 1:<br />
1 Entrada AC:<br />
Tensión de entrada<br />
85-264 V AC<br />
Frecuencia 45-65 Hz<br />
(0,2 mm2 a 2,5 mm2 en c. rígido)<br />
(0,2 mm2 a 2,5 mm2 2 Salida DC:<br />
en c. flexible)<br />
(AWG 24-12)<br />
Fusible interno 6,3 AT<br />
Fusible previo recomendado<br />
10 A ó 16 A interruptor<br />
automático/característica B<br />
3. Indicaciones de seguridad y advertencias<br />
Para garantizar un funcionamiento seguro del módulo y poder utilizar todas las<br />
funciones, rogamos lea estas instrucciones atentamente.<br />
QUINT POWER son módulos para instalación. La instalación y la puesta en marcha<br />
solo puede ser efectuada por personal correspondientemente especializado. A tal efecto,<br />
deben considerarse las normas respectivas del país (p.ej. VDE, DIN).<br />
En particular, antes de la puesta en marcha hay que asegurarse de que,<br />
• la conexión a la red se ha instalado profesionalmente y que está garantizada la protección<br />
contra descarga eléctrica,<br />
• el módulo puede desconectarse de la tensión desde el exterior de la fuente de alimentación<br />
según las especificaciones de la EN 60950 (p.ej. mediante la protección de la<br />
línea del primario),<br />
• el conductor de protección a tierra está conectado,<br />
• todos los cables de alimentación están suficientemente protegidos y dimensionados,<br />
• todos los cables de salida están dimensionados para la corriente de salida máxima del<br />
módulo, o protegidos por fusible por separado,<br />
• está garantizada una convección suficiente.<br />
La temperatura de la caja puede adoptar valores más altos, según sea la temperatura<br />
ambiente y la carga del módulo.<br />
¡En el módulo se encuentran componentes en tensión con peligro de muerte y alta<br />
energía almacenada!<br />
34<br />
36<br />
ESPAÑOL<br />
Tensión de salida<br />
24 V DC (ajuste previo),<br />
de 22,5 - 28,5 V DC ajustable<br />
mediante potenciómetro 5<br />
(0,2 mm 2 a 2,5 mm 2 en c. rígido)<br />
(0,2 mm 2 a 2,5 mm 2 en c. flexible)<br />
(AWG 24-12)<br />
El módulo es resistente al<br />
circuito abierto y cortocircuito.<br />
Atención: ¡No trabajar nunca con la tensión conectada!<br />
¡Peligro de muerte!<br />
4.1.2. Posición para montaje estrecho<br />
El módulo se suministra de fábrica para la posición<br />
de montaje estrecho.<br />
Montaje:<br />
Coloque el módulo con la guía para<br />
carril en el borde superior del carril<br />
y encájelo hacia abajo (Fig. 4a).<br />
Desmontaje: Con ayuda de un destornillador, retire<br />
el cerrojo de encaje y descuelgue el<br />
módulo del borne inferior del carril<br />
(Fig. 4b).<br />
3 Salida activa OK DC<br />
44 Salida sin potencial OK DC<br />
55 Potenciómetro (cubierto)<br />
22,5 - 28,5 V DC<br />
6 Piloto de control OK DC<br />
7 Adaptador universal para<br />
carril UTA 107<br />
4.1.3. Posición para montaje bajo<br />
Una posición de montaje bajo se consigue mediante el montaje a 90° del carril. A tal efecto,<br />
monte el adaptador para carril (UTA 107) 7 tal como descrito en la Fig. 5 (Tornillos<br />
"Torx" T10, par de apriete 0,8 - 0,9 Nm). Para eso no se necesita material de montaje.<br />
4.2. Conexión<br />
Formas de red: redes de 100-240 V AC<br />
Red TN-S Red-C Red TT<br />
L N PE<br />
QUINT<br />
+ –<br />
L<br />
N<br />
PE<br />
L N PE<br />
QUINT<br />
+ –<br />
L<br />
PEN<br />
L N PE<br />
QUINT<br />
+ –<br />
Fig. 6a Fig. 6b Fig. 6c<br />
L<br />
N<br />
Fig. 4a<br />
Fig. 4b<br />
Fig. 5<br />
4. Instalación<br />
4.1. Montaje<br />
La fuente de alimentación puede encajarse en<br />
todos los carriles según EN 50022-35 y debe realizarse<br />
en posición horizontal (bornes de entrada<br />
abajo).<br />
4.1.1. Dimensiones de montaje<br />
290<br />
Para garantizar una suficiente convección,<br />
recomendamos guardar las<br />
siguientes separaciones mínimas<br />
respecto a otros módulos:<br />
8,0 cm en dirección vertical y<br />
1,5 cm en dirección horizontal.<br />
Posición para montaje estrecho:<br />
Profundidad de montaje 125 mm (+ carril)<br />
145<br />
80<br />
15<br />
QUINT POWER<br />
115 15 15 152<br />
85 122<br />
DC<br />
13 14 OK + + – –<br />
Output DC 24V 10A<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Input<br />
AC 100-240V<br />
L N 5<br />
QUINT POWER<br />
13 14 DC<br />
OK<br />
+ + – –<br />
DC<br />
13 14 OK<br />
Output DC 24V 10A<br />
+ + – –<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Input<br />
AC 100-240V<br />
L N 5<br />
- 25 … + 60 °C<br />
- 13 … + 140 °F<br />
APPROVALS<br />
Read <strong>install</strong>ation instructions<br />
before connecting to mains www.interface.phoenixcontact.com<br />
U INDUSTRIAL<br />
F<br />
LISTED<br />
–25<br />
B<br />
CONTROL<br />
EQUIPMENT<br />
43KA<br />
EN 60950<br />
EN 60204<br />
EN 61558-2-17<br />
EN 61000-6-2<br />
EN 50081-1<br />
Fig. 2<br />
Posición para montaje bajo:<br />
Profundidad de montaje 1) 103 mm (+ carril)<br />
1) (incl. 15 mm separación p. convección)<br />
15<br />
130<br />
Fig. 3<br />
4.2.1. Cables de conexión:<br />
El módulo está equipado con conectores enchufables COMBICON. Este tipo de conexión<br />
fiable y de práctica instalación facilita una conexión rápida de los módulos y una separación<br />
óptica de las conexiones eléctricas en caso necesario.<br />
¡Accionar los conectores enchufables solo en estado inerte!<br />
Se pueden conectar las siguientes secciones de cable:<br />
2<br />
Rígido [mm ]<br />
2<br />
Flexible [mm ] AWG Par de apriete [Nm]<br />
1 Entrada: 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />
22 Salida: 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />
4 Señal: 0,2-2,5 0,2-2,5 24-12 0,5 - 0,6<br />
Para contactos fiables y protegidos contra roces casuales:<br />
• Desaisle los finales de conductor 8 mm (ver Fig. 7)<br />
4.2.2. Entrada (Fig.8)<br />
La conexión de 100-240 V AC se efectúa a través de<br />
las conexiones de tornillo L, N y 5.<br />
Protección por fusible del primario<br />
La instalación del módulo tiene que realizarse conforme<br />
a las especificaciones de la EN 60 950. El módulo<br />
tiene que poderse desconectar de la tensión desde el<br />
exterior de la fuente de alimentación mediante un dispositivo<br />
de separación apropiado. Para eso puede utilizase,<br />
p.ej. la protección de la línea del primario.<br />
Otra protección de aparatos no es necesaria, dado<br />
que se dispone de un fusible interno.<br />
Fusible previo recomendado:<br />
Interruptor automático de 10 A ó 16 A, característica B (o similar).<br />
Para aplicaciones DC tiene que preverse un fusible apropiado.<br />
Si el fusible interno reacciona, es muy<br />
probable que se tenga un defecto en el<br />
módulo.<br />
En este caso, el módulo tiene que comprobarse<br />
en fábrica.<br />
4.2.3. Salida (Fig.9)<br />
La conexión de 24 V DC se efectúa mediante las<br />
conexiones de tornillo "+" y "–" en la conexión por<br />
tornillo 2.<br />
La tensión de salida está ajustada de fábrica a<br />
24 V DC. Con el potenciómetro 5,<br />
la tensión de<br />
salida puede ajustarse entre 22,5 y 28,5 V DC.<br />
8 mm<br />
Input<br />
AC 100-240V<br />
L N 5<br />
4 33<br />
13 14 DC<br />
OK<br />
+ + – –<br />
DC<br />
13 14 OK<br />
Output DC 24V 10A<br />
+ + – –<br />
DC OK<br />
Adjust<br />
22.5-28.5V<br />
Fig. 7<br />
Fig. 8<br />
22<br />
5<br />
Fig. 9<br />
35<br />
37
Protección por fusible del secundario:<br />
El módulo está protegido electrónicamente contra cortocircuito y en circuito abierto.<br />
En caso de fallo, la tensión de salida se limita como máximo a 35 V DC.<br />
Hay que asegurarse de que todos los cables de salida están correspondientemente dimensionados<br />
para la corriente de salida máxima o protegidos por fusible por separado.<br />
Los cables del secundario deben ser de sección grande para mantener la caída de tensión<br />
en los conductores lo más pequeña posible.<br />
4.3. Señalización<br />
Las dos salidas OK DC sirven para el control funcional preventivo de la fuente de alimentación.<br />
Se dispone de un contacto de señales sin potencial 4 y de una señal OK DC 3.<br />
Adicionalmente, el LED OK DC 6 facilita una evaluación de la fuente de alimentación,<br />
directamente en el lugar de empleo.<br />
4.3.1. Contacto sin potencial (Fig.10)<br />
El contacto de señales sin potencial notifica, mediante<br />
apertura, el no alcance de la tensión de salida en más del<br />
10 %. Pueden conmutarse señales y cargas resistivas de<br />
hasta máx. 30 V y corrientes de hasta máx. 1 A.<br />
Para cargas altamente inductivas, p.ej. de un relé, es necesario<br />
un circuito de protección apropiado (p.ej. diodo de<br />
protección).<br />
4.3.2. Señal de salida activa (Fig.11)<br />
La señal de 24 V DC se tiene entre los bornes de conexión<br />
"DC OK" y "–", y puede someterse a una carga de hasta<br />
40 mA. Esta salida de señal notifica, mediante el cambio de<br />
"nivel alto" a "bajo", el no alcance de la tensión de salida<br />
ajustada en más del 10 %.<br />
La señal OK DC está desacoplada de la salida de potencia.<br />
De esta manera, se excluye una alimentación ajena debida<br />
a módulos conectados en paralelo.<br />
La señal de 24 V DC puede conectarse para evaluación, directamente a una entrada de<br />
lógica.<br />
4.3.3. Bucle de señales (Fig.12)<br />
Las dos salidas de señal mencionadas anteriormente pueden combinarse de modo<br />
sencillo.<br />
Ejemplo: control de dos módulos.<br />
Utilice la salida de aviso activa del módulo 1 e<br />
inserte en bucle la salida de aviso sin potencial<br />
del módulo 2. En caso de fallo funcional se obtiene<br />
una indicación colectiva de fallo. Se pueden<br />
insertar en bucle tantos módulos como se desee.<br />
Esta combinación de señales ahorra costes de<br />
cableado y entradas lógicas.<br />
38<br />
40<br />
24 V DC<br />
40 mA<br />
13 14<br />
Output 24V DC<br />
DC OK<br />
+ + – –<br />
DC OK<br />
max.<br />
30 VAC/DC, 1 A Fig. 10<br />
13 14<br />
24 V DC<br />
40 mA<br />
Output 24V DC<br />
DC OK<br />
Módulo 1<br />
Output 24V DC<br />
13 14<br />
DC OK<br />
+ + – –<br />
DC OK<br />
+ + – –<br />
DC OK<br />
Fig. 11<br />
Módulo 2<br />
Outpu<br />
13 14<br />
Fig. 12<br />
5.3. Funcionamiento en paralelo<br />
Los módulos de igual tipo pueden conectarse en paralelo, tanto para redundancia como<br />
para aumento de potencia. Para ello, en estado de suministro no se necesitan efectuar<br />
ajustes.<br />
Si se realiza un ajuste de la tensión de salida, se garantiza un reparto de corriente uniforme<br />
mediante un ajuste exacto de todas las fuentes de alimentación conectadas en paralelo<br />
a la misma tensión de salida.<br />
Para obtener un reparto de corriente simétrico, recomendamos que todas las conexiones<br />
de los cables de la fuente de alimentación se realicen a una barra colectora con igual longitud<br />
y sección de conductor.<br />
Debido a efectos del sistema, en la conexión en paralelo de más de dos fuentes de alimentación<br />
debe instalarse un circuito de protección a cada salida de módulo (p.ej. diodo<br />
de desacoplamiento o fusible DC). De esta manera, en un defecto del secundario del módulo<br />
se evitan corrientes altas alimentadas de retorno.<br />
5.3.1. Servicio redundante (Fig. 15)<br />
Los circuitos redundantes se utilizan para la alimentación<br />
de instalaciones que deben cumplir altos requisitos<br />
en lo que a la seguridad de servicio se refiere. Si<br />
en el primario de la primera fuente de alimentación se<br />
tiene un defecto, el segundo módulo adopta automáticamente,<br />
sin interrupción, la alimentación de corriente<br />
completa y viceversa.<br />
A tal fin, las fuentes de alimentación a conectar en paralelo<br />
se dimensionan de forma, que el consumo de<br />
corriente total de todos los receptores conectados se<br />
pueda cubrir por completo por una sola fuente de alimentación.<br />
La redundancia del 100 % requiere diodos de desacoplamiento externos.<br />
5.3.2. Aumento de potencia (Fig. 16)<br />
Para n módulos conectados en paralelo, la corriente<br />
de salida puede aumentarse a n x I N .<br />
La conexión en paralelo para aumento de potencia se<br />
utiliza para la ampliación de instalaciones existentes.<br />
Una conexión en paralelo se aconseja cuando la fuente<br />
de alimentación no cubre el consumo de corriente<br />
del receptor más potente. Además, los receptores deben<br />
repartirse a módulos individuales, independientemente<br />
unos de otros.<br />
En total pueden conectarse en paralelo cinco módulos.<br />
QUINT QUINT<br />
10 A + – 10 A + –<br />
+<br />
–<br />
+ –<br />
DC OK<br />
Σ = 10 A<br />
Fig. 15<br />
QUINT QUINT<br />
10 A + – 10 A + –<br />
+<br />
–<br />
+ –<br />
Σ = 20 A<br />
Fig. 16<br />
4.3.4. LED OK DC<br />
El LED OK DC verde facilita una evaluación funcional "in situ" en el armario de distribución.<br />
LED iluminado Funcionamiento normal de la fuente de alimentación<br />
LED parpadea La tensión de salida ajustada ha descendido en más del 10 %.<br />
Se tiene un cortocircuito de receptor en el secundario o sobrecarga fuera<br />
del margen POWER BOOST.<br />
LED apagado Sin tensión de red o módulo en defecto.<br />
5. Función<br />
5.1. Característica de salida<br />
Para temperaturas ambiente T amb < +40 °C, el módulo<br />
puede suministrar constantemente 15 A para<br />
tensión de salida de 24 V DC (P ev. = 360 W).<br />
Para una carga más elevada, el punto de trabajo recorre<br />
la curva característica U/I representada en la<br />
Fig. 13. La corriente de salida se limita a I BOOST .<br />
En eso, la tensión del secundario permanece reducida<br />
hasta que se haya eliminado el cortocircuito<br />
del secundario.<br />
La curva característica U/I garantiza que, tanto cargas<br />
capacitivas altas como receptores con conver-<br />
tidores DC/DC en el circuito de entrada, pueden alimentarse con QUINT POWER sin problemas.<br />
Los fusibles posconectados reaccionan fiablemente. La selectividad en la construcción<br />
de la instalación está garantizada en todo momento.<br />
5.2. Comportamiento de temperatura<br />
Para una temperatura ambiente de hasta +40 °C,<br />
el módulo pone a disposición una corriente de salida<br />
constante de 15 A.<br />
El módulo puede suministrar la corriente nominal<br />
de salida de 10 A hasta una temperatura ambiente<br />
de +60 °C.<br />
Para temperaturas ambiente superiores a +60 °C,<br />
la potencia de salida tiene que reducirse en 2,5 %<br />
por grado Kelvin de aumento de temperatura.<br />
UOUT<br />
[V]<br />
UN 24<br />
< 60 °C<br />
240 W<br />
15<br />
IBOOST<br />
Para temperaturas ambiente superiores a +70 °C o<br />
sobrecarga térmica se desconecta el módulo. La potencia de salida se reduce hasta el<br />
punto en el que el módulo ofrece de nuevo protección. Después de enfriarse el módulo,<br />
aumenta de nuevo la potencia de salida.<br />
Corriente de salida [A]<br />
15<br />
10<br />
10<br />
IN<br />
< 40 °C<br />
U OUT = 24 V<br />
360 W<br />
0<br />
0 20 40 60<br />
Temperatura ambiente [°C]<br />
IOUT<br />
[A]<br />
Fig. 13<br />
Fig. 14<br />
6. Datos técnicos QUINT-PS-100-240AC/24DC/10<br />
Código<br />
Entrada 1<br />
29 38 60 4<br />
Tensión nominal de entrada 100 - 240 V AC (amplio rango de entrada)<br />
Rango de tensión de entrada 85 - 264 V AC 90 - 350 V DC<br />
Frecuencia 45 - 65 Hz 0 Hz<br />
Absorción de corriente (p. valores nominales)<br />
Limitación de la corriente de cierre / I<br />
aprox. 2,4 A (120 V AC) / 1,3 A (230 V AC)<br />
2t (+25°C) aprox. 15 A / 1,5 A2 Puenteo en fallo de red<br />
s<br />
para carga nominal (típ.) > 40 ms (120 V AC) / > 40 ms (230 V AC)<br />
Tiempo de conexión al aplicar la tensión<br />
de red<br />
< 1 s<br />
Protección contra sobretensiones transitorias varistor<br />
Fusible de entrada, interno 6,3 AT (protección de aparatos))<br />
Fusible previo recomendado interruptor automático de 10 A ó 16 A,<br />
característica B (EN 60 898)<br />
Corriente de derivación a tierra (PE)<br />
Salida 2<br />
< 3,5 mA<br />
Tensión nominal de salida UN/tolerancia 24 V DC / ± 1 %<br />
Margen ajustable de la tensión de salida<br />
Corr. de salida p. refrigeración por convección:<br />
22,5 - 28,5 V DC<br />
•POWER BOOST IBOOST -25 hasta +40 °C<br />
•Corriente nominal de salida IN -25 hasta +60°C<br />
15 A (Uout = 24 V DC)<br />
10 A (Uout = 24 V DC)<br />
Derating a partir de +60 °C 2,5 % por grado Kelvin<br />
Limitación de corriente en cortocircuito aprox. I BOOST ≈ 15 A<br />
Arranque de cargas capacitivas ilimitado<br />
Error repetido para:<br />
•cambio de carga estático 10 - 90 %<br />
•cambio de carga dinámico 10 - 90 %<br />
•cambio de tensión de entrada ± 10 %<br />
típ. < 1 %<br />
típ. < 2 %<br />
típ. < 0,1 %<br />
Disipación máx.: en circuito abierto/a carga nom. aprox. 4 W / 33 W<br />
Rendimiento > 88 % (para 230V AC y valores nominales)<br />
Tiempo de ascenso Uout (10 % - 90 %) típ. 10 ms<br />
Ondulación residual/picos de conexión (20 MHz)<br />
Conectable en paralelo<br />
< 100 mVpp (para valores nominales)<br />
para redundancia y aumento de potencia<br />
Protección contra sobretensiones contra<br />
sobretensiones internas<br />
sí, limitada a aprox. 35 V DC<br />
Resistencia a la alimentación de retorno<br />
Salida de señal<br />
35 V DC<br />
DC OK 3 activo:<br />
señal +24 V DC (referida a la masa del módulo)<br />
(Uout > 0,9 x UN = señal alta)<br />
máx. 40 mA<br />
DC OK 4 sin potencial:<br />
(Uout > 0,9 x UN = contacto cerrado)<br />
máx. 30 V AC/DC; máx. 1 A<br />
LED 6 (Uout < 0,9 x UN = LED parpadea) LED verde<br />
39<br />
41
Datos generales<br />
Tensión de aislamiento entrada/salida<br />
entrada / PE<br />
salida / PE<br />
Paquete de homologaciones<br />
42<br />
6. Datos técnicos QUINT-PS-100-240AC/24DC/10<br />
4 kV AC (prueba tipo)/2 kV AC (ensayo individual)<br />
3,5 kV AC (prueba tipo)/2 kV AC (ensayo individual)<br />
500 V DC (ensayo individual)<br />
CB<br />
scheme<br />
Equipamiento eléctrico de máquinas EN 60 204 (categoría de sobretensiones III)<br />
Transformadores de seguridad para<br />
fuentes de conmutación<br />
EN 61 558-2-17<br />
Seguridad eléctrica (de dispositivos de<br />
la técnica de información)<br />
EN 60950 / VDE 0805,<br />
UL/C-UL Recognized UL 60 950 u 1)<br />
Regulación industrial<br />
1)<br />
UL/C-UL Listed UL 508 U<br />
LISTED<br />
Construcción de navíos Germanisch Lloyd F<br />
Equipamiento de instalaciones de alta<br />
intensidad con aparatos electrónicos<br />
EN 50 178 (VDE 0160)<br />
Tensión baja de protección PELV (EN 60 204)<br />
SELV (EN 60 950)<br />
Separación segura VDE 0100-410<br />
Protección contra descarga eléctrica DIN 57 100-410<br />
Protección contra corrientes corpóreas peligrosas,<br />
exigencias básicas para la separación<br />
segura de aparatos eléctricos<br />
DIN VDE 0106-101<br />
Limitación de corrientes armónicas de<br />
la red<br />
según EN 61 000-3-2<br />
Posición para el montaje sobre carril horizontal NS 35 según<br />
EN 50 022<br />
Protección IP 20<br />
Clase de protección Ι, con conexión a tierra (PE)<br />
MTBF > 500 000 h según IEC 1709 (SN 29 500)<br />
Aislamiento AluNox (AlMg1), cerrado<br />
Dimensiones (A x A x P) Estado de suministro: girado a 90 °:<br />
(85 x 130 x 125) mm (122 x 130 x 160) mm<br />
Peso<br />
Datos climáticos<br />
aprox. 1,3 kg<br />
Temperatura ambiente servicio -25 °C hasta +70 °C (> +60 °C Derating)<br />
almacenamiento -40 °C hasta +85 °C<br />
Humedad hasta el 95% para +25 °C, sin condensación<br />
Vibración según IEC 68-2-6 < 15 Hz, amplitud ± 2,5 mm<br />
15 Hz-150 Hz, 2,3 g,<br />
90 mín. en frecuencia propia<br />
Choque según IEC 68-2-27 30 g en todas las direcciones espaciales<br />
Grado de suciedad 2 (según EN 50 178)<br />
Clima 3K3 (según EN 60 721)<br />
1) Homologación UL para tensión de entrada AC y temperatura ambiente<br />
hasta +70 °C (+158 °F)<br />
B<br />
c<br />
Conformidad con la directriz EMV 89/336/EWG<br />
y con la directriz de baja tensión 73/23/EWG<br />
Compatibilidad electromagnética (EMV) Requisitos<br />
QUINT-PS-100-240AC/<br />
Resistencia a interferencias s. EN 61000-6-2 EN 61 000-6-2 24DC/10<br />
EN 61000-4-2 2)<br />
caja<br />
nivel 4<br />
• Descarga de electrici- descarga e. contactos: 4 kV<br />
8 kV<br />
dad estática (ESD) descarga en el aire: 8 kV<br />
15 kV<br />
EN 61000-4-3 1)<br />
caja<br />
nivel 3<br />
• Campo electromagnéti- frecuencia: 80-1000 MHz<br />
80-1000 MHz/1,4-2,0GHz<br />
co de AF<br />
intensidad de campo: 10 V/m<br />
10 V/m<br />
EN 61000-4-4 2)<br />
• Transitorios rápidos<br />
(Burst):<br />
entrada:<br />
salida:<br />
señal:<br />
2 kV asimétrica 4)<br />
2 kV asimétrica 4)<br />
1 kV asimétrica 4)<br />
4 kV (nivel 4)<br />
2 kV (nivel 3)<br />
1 kV (nivel 2)<br />
EN 61000-4-5 2)<br />
• Cargas de sobrecorriente<br />
(Surge):<br />
entrada:<br />
salida:<br />
señal:<br />
2 kV asimétrica 4)<br />
1 kV simétrica 3)<br />
0,5 kV asimétrica 4)<br />
0,5 kV simétrica3) 1 kV asimétrica4) 4 kV (inst. clase 4)<br />
2 kV (inst. clase 4)<br />
0,5 kV (nivel 1)<br />
0,5 kV (nivel 1)<br />
1 kV (nivel 2)<br />
EN 61000-4-6 1)<br />
E/S/S:<br />
asimétrica<br />
• Perturbaciones en la línea frecuencia:<br />
Uo: 4)<br />
nivel 3<br />
0,15-80 MHz<br />
0,15-80 MHz<br />
10 V<br />
10 V<br />
EN 61000-4-11 2) entrada: reducción del 30 % de ver datos de entrada:<br />
• Fallos de tensión<br />
la tensión de salida puenteado en fallo de la red<br />
para 0,5 periodos > 20 ms<br />
ENV 50204<br />
frecuencia: no se exige 900 MHz/ 1800 MHz<br />
• Simulación de radioteléfonos intensidad de campo:<br />
20 V/m<br />
Radiación de perturbaciones según EN 50081-2<br />
• Radiointerferencias EN 55011<br />
clase A 5)<br />
EN 55011 (EN 55022)<br />
clase B 6)<br />
• Tensión<br />
radiointerferencia<br />
EN 55011<br />
clase A 5)<br />
EN 55011 (EN 55022)<br />
clase B 6)<br />
EN 55011 equivale a la CISPR11 / EN 55022 equivale a la CISPR22<br />
EN 61000 equivale a la IEC 1000<br />
1) Criterio A: Comportamiento de servicio normal dentro de los límites determinados.<br />
2)<br />
Criterio B: Alteración transitoria del comportamiento de servicio<br />
que corrige el propio aparato.<br />
3) simétrica: Conductor contra conductor.<br />
4) asimétrica: Conductor contra tierra.<br />
5)<br />
clase A: Campo de empleo industrial.<br />
6) clase B: Campo de empleo industrial y de viviendas.<br />
43