The control system is set for normal operation. The gate<br />

can be moved in impulse operation (OPEN-STOP-<br />

CLOSE-STOP) by pressing circuit board button T, the<br />

external button or if impulse 1 is triggered.<br />

Leaf A (traffic leaf) will be opened if impulse 2 is triggered,<br />

if the leaf was previously closed (see Figure 4.5/4.7 ).<br />

If the leaf offset has been activated, leaf A can only be<br />

moved if leaf B is in the CLOSE end-of-travel position.<br />

7.1 Reversing with force limit<br />

7.2 Reversing while opening<br />

If the force limit is triggered while opening, the respective<br />

leaf will briefly reverse towards CLOSE, i.e. the operator<br />

moves the gate in the opposite direction and subsequently<br />

stops. The non-participating leaf is stopped in double-leaf<br />

operation.<br />

7.3 Reversing while closing<br />

If the force limit is triggered while closing, the behaviour<br />

of the leaves will depend on the setting for DIL switch 8<br />

(reversing towards OPEN).<br />

8 OFF The leaf where the force limit occurred will<br />

briefly reverse towards OPEN. The nonparticipating<br />

leaf stops.<br />

8 ON Both leaves reverse to the OPEN end-oftravel<br />

position<br />

7.4 Behaviour during a power failure<br />

The hinged gate must be uncoupled from the operator in<br />

order to open or close it during a power failure (see Figure<br />

9.1 ). If the gate is additionally secured with floor locking,<br />

this must first be unlocked with an appropriate key.<br />

7.5 Behaviour following a power failure<br />

Re-couple the gate to the operator after power has<br />

been restored (see Figure 9.2 ). A necessary reference<br />

cycle following a power failure is automatically performed<br />

during the next command impulse.<br />

During this reference cycle the options relay clocks and<br />

a connected warning light flashes slowly.<br />

8 MAINTENANCE<br />

60<br />

ENGLISH<br />

The hinged gate operator and control are maintenancefree.<br />

Have the gate system checked by a specialist in<br />

accordance with the manufacturer's specifications.<br />

Note<br />

Inspection and maintenance work may only be carried out by<br />

a specialist. In this connection, please contact your supplier.<br />

A visual inspection may be carried out by the owner. If repairs<br />

become necessary, please contact your supplier.<br />

We would like to point out that any repairs not carried out<br />

properly or with due professionalism shall render the warranty<br />

null and void.<br />

8.1 Operation, error and warning messages<br />

8.1.1 LED GN<br />

The green LED (Figure 4.1 ) indicates the operating state<br />

of the controller:<br />

- Steady illumination: normal state, all OPEN end-of-travel<br />

positions and forces learned.<br />

- Fast flashing: force learning cycles must be performed.<br />

- Slow flashing: set-up mode – end-of-travel setting<br />

8.1.2 LED RD<br />

• In set-up mode:<br />

-Off: limit switch of the selected leaf actuated<br />

- On: limit switch of the selected leaf not actuated<br />

• Setting the reversing limits:<br />

-Flashing frequency is dependent on (proportional to)<br />

the selected reversing limit<br />

- Minimum reversing limit: red LED is permanently off<br />

- Maximum reversing limit: red LED is permanently on<br />

• Radio programming display<br />

- Flashing as described in Chapter 5.3 above<br />

• Display of the push button inputs<br />

- Actuated = on<br />

- Not actuated = off<br />

Error/diagnosis display<br />

The red LED helps to easily identify causes when<br />

operation does not go according to plan<br />

Display: 2x flashing<br />

Error/warning: Safety/protection device has responded<br />

Possible cause: - Safety/protection device has been<br />

actuated.<br />

- Safety/protection device defective<br />

- Without the SE, 8k2 resistance<br />

between terminal 20 and 71 missing<br />

Remedy: - Check safety/protection device<br />

-Check whether the appropriate<br />

resistance is available without a<br />

connected security/safety device<br />

Display: 3x flashing<br />

Error/warning: Force limit in CLOSE direction<br />

Possible cause: Obstruction in gate area<br />

Remedy: Remove obstruction; check forces,<br />

and increase if necessary<br />

Display: 5x flashing<br />

Error/warning: Force limit in OPEN direction<br />

Possible cause: Obstruction in gate area<br />

Remedy: Remove obstruction; check forces,<br />

and increase if necessary<br />

Display: 6x flashing<br />

Error/warning: System error<br />

Possible cause: Internal error<br />

Remedy: Restore the factory setting (see<br />

Chapter 6) and repeat the learning<br />

procedure for the control system;<br />

replace, if necessary.<br />