Value range<br />
from...factory-set...to<br />
Parameter Meaning<br />
Input<br />
4 Commissioning the instrument 10<br />
Pt 100: P.1h<br />
Pt 1000: P.1t<br />
Sensor<br />
Sensor connected in 2-wire circuit<br />
KTY2X-6: PtC<br />
-99.9 ... 0.0 ... 99.9 °C/<br />
°F<br />
Temperature offset<br />
Temperature offset in °C or °F<br />
0.0 ... 0.0 ... 99.9 in Ω<br />
Lead compensation resistance<br />
This value is used for compensating the resistance of the probe lead and<br />
depends on the lead length.<br />
For best temperature measurement results, the resistance value of the probe<br />
lead (with shorted probe) has to be entered here.<br />
Total resistance in the Pt100 range: 3<strong>20</strong> Ω and<br />
Pt1000/KTY2x-6: 3<strong>20</strong>0 Ω<br />
°C or °F<br />
Unit<br />
for the displayed temperature<br />
Only the measured value is converted accordingly when changing<br />
over to °F. All other temperature variables, e. g. SP, will retain their<br />
values.<br />