DigiTrace TCON-CSD/20
DigiTrace TCON-CSD/20
DigiTrace TCON-CSD/20
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Value range<br />
from...factory-set...to<br />
Parameter Meaning<br />
0...0 ... 60min<br />
Switch-on delay after power ON<br />
for staggered switch-on of several equipment units<br />
4 Commissioning the instrument 9<br />
0 ... 0 ... 999 sec<br />
Minimum ON time<br />
Here you can set the minimum time for which the equipment unit, for<br />
example, has to remain switched on. These values depend on the heating<br />
or cooling unit being used (observe manufacturer’s specifications).<br />
0 ... 0 ... 999 sec<br />
Minimum OFF time<br />
Here you can set the minimum time for which the equipment unit, for<br />
example, has to remain switched off. These values depend on the heating<br />
or cooling unit being used (observe manufacturer’s specifications).<br />
Alarms<br />
-300 ... 1°C ... 900°C/°F<br />
Low alarm limit temperature<br />
As soon as the process value falls below this limit, the alarm message<br />
is displayed, see Chapter 7 “Alarm messages”.<br />
-300 ... <strong>20</strong>0 ... 900°C/°F<br />
High alarm limit temperature<br />
As soon as the process value goes above this limit, the alarm message<br />
is displayed, see Chapter 7 “Alarm message”.<br />
0 ... 0 ... 60 min<br />
Alarm suppression time<br />
The alarm or is not displayed until this time has elapsed. If an<br />
alarm is present for longer than , then it will be displayed.<br />
0. 1<br />
Response to over/underrange<br />
0: relay de-energized<br />
1: relay energized